Testing and simulation of potential energy savings in renewing used split-type and window-type air-conditioners

被引:4
|
作者
Alabdulkarem, Abdullah [1 ]
Almutairi, Zeyad [1 ]
机构
[1] King Saud Univ, Dept Mech Engn, POB 800, Riyadh 11421, Saudi Arabia
关键词
Air-conditioner; heat pump; energy efficiency; energy efficiency ratio; coefficient of performance; soft-optimization; compressor; R22; R410A; PERFORMANCE; OPTIMIZATION; R410A;
D O I
10.1177/0143624419894438
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In Saudi Arabia, air-conditioners ACs are responsible for 50% of electricity consumption due to hot weather conditions as well as the delay in implementing ACs standards. In this work, six used split-type and eight used window-type ACs that have ages from 3 to 32 years were tested according to American Society of Heating, Refrigerating and Air-Conditioning Engineers and Saudi Standard, Metrology and Quality Organization cooling test conditions and their performances were compared against new units that have 5.27 kW rated capacity. Test results show that coefficient of performance and cooling capacity of used split-type units compared to new one are 68% and 93%, respectively. For window-type, test results show that coefficient of performance and cooling capacity of used units compared to new one are 55% and 77%, respectively. The effect of replacing used compressor units with a new compressor was experimentally investigated. A model was developed using a commercially available software and was validated with experimental data. An economical map was developed to identify feasible ACs replacement regions.
引用
收藏
页码:586 / 602
页数:17
相关论文
共 42 条
  • [11] Thermoeconomic analysis and optimization of residential split-type air conditioners
    Barreira, Eduardo M.
    Negrao, Cezar O. R.
    Hermes, Christian J. L.
    APPLIED THERMAL ENGINEERING, 2013, 50 (01) : 629 - 636
  • [12] Theoretical and simulation analysis for R290 leakage from split-type air conditioners
    Ning, Qian
    He, Guogeng
    Li, Baofeng
    Li, Tiejun
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 166 : 139 - 148
  • [13] Simulation of recombined household multi-split variable refrigerant flow system with split-type air conditioners
    Li, Ziai
    Wang, Baolong
    Li, Xianting
    Shi, Wenxing
    Zhang, Shaolong
    Liu, Yunzhong
    APPLIED THERMAL ENGINEERING, 2017, 117 : 343 - 354
  • [14] Energy reduction of split-type air conditioners using a pre-cooling system for the condenser
    Thiangchanta, Surasit
    Do, Tuan Anh
    Suttakul, Pana
    Mona, Yuttana
    ENERGY REPORTS, 2021, 7 (07) : 1 - 6
  • [15] Flammable refrigerant leakage hazards control for split-type household air conditioners
    Ning, Qian
    He, Guogeng
    Fan, Mingjing
    Xiong, Jun
    Li, Xiao
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 144 : 188 - 201
  • [16] Numerical and experimental study of an ejector as an expansion device in split-type air conditioner for energy savings
    Sumeru, Kasni
    Sulaimon, Shodiya
    Nasution, Henry
    Anid, Farid Nasir
    ENERGY AND BUILDINGS, 2014, 79 : 98 - 105
  • [17] An empirical model of a split-type inverter air conditioner for building energy simulation
    Pizzatto, Leandro Reichembach
    Nascimento, Carlos A. Richter
    Mendes, Nathan
    APPLIED THERMAL ENGINEERING, 2024, 236
  • [18] COST ANALYSIS OF PRODUCING SPLIT-TYPE AIR CONDITIONERS USING HC-290
    Colbourne, D.
    Croiset, I. C.
    Ederberg, L.
    Usinger, J.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 2704 - 2711
  • [19] Structural characteristics of pathogenic bacteria in split-type air conditioners and environmental factors related to their pathogenicity
    Liu, Yan
    Wang, Zhichao
    Li, Xiaofeng
    Xu, Zhaowei
    Jiang, Sihang
    Sun, Xiaoyu
    Zhao, Xiuxiu
    BUILDING AND ENVIRONMENT, 2024, 265
  • [20] A PARAMETRIC STUDY ON THE EFFECT OF BLOWING PARAMETERS OF SPLIT-TYPE AIR CONDITIONERS ON THERMAL COMFORT AND VENTILATION
    Pulat, Erhan
    Yuce, Bahadir Erman
    HEAT TRANSFER RESEARCH, 2021, 52 (15) : 63 - 76