Testing and simulation of potential energy savings in renewing used split-type and window-type air-conditioners

被引:4
|
作者
Alabdulkarem, Abdullah [1 ]
Almutairi, Zeyad [1 ]
机构
[1] King Saud Univ, Dept Mech Engn, POB 800, Riyadh 11421, Saudi Arabia
关键词
Air-conditioner; heat pump; energy efficiency; energy efficiency ratio; coefficient of performance; soft-optimization; compressor; R22; R410A; PERFORMANCE; OPTIMIZATION; R410A;
D O I
10.1177/0143624419894438
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In Saudi Arabia, air-conditioners ACs are responsible for 50% of electricity consumption due to hot weather conditions as well as the delay in implementing ACs standards. In this work, six used split-type and eight used window-type ACs that have ages from 3 to 32 years were tested according to American Society of Heating, Refrigerating and Air-Conditioning Engineers and Saudi Standard, Metrology and Quality Organization cooling test conditions and their performances were compared against new units that have 5.27 kW rated capacity. Test results show that coefficient of performance and cooling capacity of used split-type units compared to new one are 68% and 93%, respectively. For window-type, test results show that coefficient of performance and cooling capacity of used units compared to new one are 55% and 77%, respectively. The effect of replacing used compressor units with a new compressor was experimentally investigated. A model was developed using a commercially available software and was validated with experimental data. An economical map was developed to identify feasible ACs replacement regions.
引用
收藏
页码:586 / 602
页数:17
相关论文
共 42 条
  • [21] An experimental study on clothes drying using rejected heat (CDURH) with split-type residential air conditioners
    Deng, SM
    Han, H
    APPLIED THERMAL ENGINEERING, 2004, 24 (17-18) : 2789 - 2800
  • [23] Influence of vane angle on the effectiveness of air conditioning of wall-mounted split-type air conditioners in residential buildings
    Lee, Sihwan
    Lee, Juyoun
    Kato, Shinsuke
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (05) : 761 - 775
  • [24] Experimental comparison of the energy parameters of HFCs used as alternatives to HCFC-22 in split type air conditioners
    Oruc, Vedat
    Devecioglu, Atilla G.
    Berk, Ugur
    Vural, Ibrahim
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 63 : 125 - 132
  • [25] Performance testing and optimization of a split-type air conditioner with evaporatively-cooled condenser
    Atmaca, Ibrahim
    Senol, Ali
    Caglar, Ahmet
    ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH, 2022, 32
  • [26] An Experimental Evaluation of Energy Saving in a Split-type Air Conditioner with Evaporative Cooling Systems
    Chaktranond, Chainarong
    Doungsong, Peachrakha
    INTERNATIONAL TRANSACTION JOURNAL OF ENGINEERING MANAGEMENT & APPLIED SCIENCES & TECHNOLOGIES, 2010, 1 (01): : 9 - 18
  • [27] A mathematical model of critical releasable charge for R290 indoor leakage of split-type household air conditioners
    Ning, Qian
    He, Guogeng
    Xiong, Jun
    Fan, Mingjing
    Li, Xiao
    BUILDING AND ENVIRONMENT, 2023, 228
  • [28] Discrete frequency noise reduction of the cross-flow fan of the split type room air-conditioners using the skewed stabilizers
    Koo, HM
    JSME INTERNATIONAL JOURNAL SERIES C-MECHANICAL SYSTEMS MACHINE ELEMENTS AND MANUFACTURING, 2000, 43 (01): : 104 - 109
  • [29] Experimental Study on Energy Performance of a Split-type Air Conditioning System by Cooling Panel Coupled
    Kietkangsadan, S.
    Jiamrittiwong, P.
    Puangngernmak, N.
    Mangkonkaeo, A.
    2021 INTERNATIONAL CONFERENCE ON SMART CITY AND GREEN ENERGY (ICSCGE 2021), 2021, : 18 - 21
  • [30] The two-fluid numerical simulation of the inner flow of a indoor split-type air conditioner
    Xue, Yong-Fei
    Gan, Jia-Ye
    Wu, Ke-Qi
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2007, 28 (02): : 235 - 237