Modeling of an air cooler with finned heat transfer tube banks using the RELAP5-3D code

被引:5
|
作者
Mochizuki, Hiroyasu [1 ]
机构
[1] Tokyo Inst Technol, Inst Innovat Res, Lab Adv Nucl Energy, Meguro Ku, 2-12-1 Ookayama, Tokyo 1528550, Japan
关键词
REACTOR;
D O I
10.1016/j.nucengdes.2020.110902
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
The present paper proposes a calculation model of an air cooler using the RELAP5-3D code. Up to now, the modeling of an air cooler using RELAP5-3D was not described in detail, and there was a problem when calculating the decay heat removal system with the air cooler. Above all, the study of the heat transfer model for an air cooler with finned heat transfer tube banks is few. Since a decay heat removal system with air coolers is essential in liquid metal cooled fast nuclear reactors, it is anticipated how to model the air cooler using implemented heat transfer models in the RELAP5-3D code. The finned heat transfer tube is simulated with multiple bare tubes which have the equivalent heat transfer characteristics considering fin efficiency. Two kinds of simulations have been compared to the measured results of the "Monju" reactor under the forced and natural convection conditions in order to confirm the applicability of the proposed model. The simulation result under the forced convection condition is in good agreement with the test result except the operation mode under the natural convection. Since the simulation result under the natural convection condition overpredicts the test result, the surface area is lessened in order to decrease the heat transfer. As a result, good agreement has been obtained between the simulation and the test result under the natural convection condition. Sensitivity analysis has been performed for the cases where the outside diameter and the number of the simulated heat transfer tubes, and number of divisions of the calculation meshes are changed. It has been confirmed that there is almost no change in the total heat transfer rate even if various diameter tubes are used and the number of divisions is changed. The number of heat transfer tubes has a non-linear sensitivity to the removal heat rate.
引用
收藏
页数:14
相关论文
共 50 条
  • [31] A new assessment of relap5-3d using a general electric level swell problem
    Aumiller, DL
    Tomlinson, ET
    Clarke, WG
    NUCLEAR TECHNOLOGY, 2002, 137 (03) : 213 - 227
  • [32] Analysis of the hot gas flow in the outlet plenum of the very high temperature reactor using coupled RELAP5-3D system code and a CFD code
    Anderson, Nolan
    Hassan, Yassin
    Schultz, Richard
    NUCLEAR ENGINEERING AND DESIGN, 2008, 238 (01) : 274 - 279
  • [33] Qualification of RELAP5-3D code condensation model against full-scale PERSEO Test 9
    Bersano, A.
    Falcone, N.
    Bertani, C.
    De Salve, M.
    Meloni, P.
    Mascari, F.
    PROGRESS IN NUCLEAR ENERGY, 2021, 139
  • [34] Numerical Simulation of Flow and Heat Transfer of Air Flowing Across 3D Rectangular Finned Tube
    Zhao, Si-Yan
    Li, Jing
    Xu, Ju-Wu
    Zhu, Xun
    Liao, Qiang
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2019, 40 (04): : 907 - 915
  • [35] THALLIUM: An experimental facility for simulation of HCLL In-box LOCA and validation of RELAP5-3D system code
    Utili, M.
    Venturini, A.
    Lanfranchi, M.
    Calderoni, P.
    Malavasi, A.
    Zucchetti, M.
    FUSION ENGINEERING AND DESIGN, 2017, 123 : 102 - 106
  • [36] An integrated RELAP5-3D and multiphase CFD code system utilizing a semi-implicit coupling technique
    Aumiller, DL
    Tomlinson, ET
    Weaver, WL
    NUCLEAR ENGINEERING AND DESIGN, 2002, 216 (1-3) : 77 - 87
  • [37] Margin Assessment of AP1000 In-vessel Retention Using RELAP5-3D
    Liu, Hsiang Chun
    Lee, Min
    Liang, Thomas K. S.
    PROCEEDINGS OF THE 20TH INTERNATIONAL CONFERENCE ON NUCLEAR ENGINEERING AND THE ASME 2012 POWER CONFERENCE - 2012, VOL 1, 2012, : 647 - 655
  • [38] Performance assessment of the two-phase pump degradation model in the relap5-3d transient safety analysis code
    Lane, Jeffrey W.
    Hochreiter, L. E.
    Aumiller, D. L., Jr.
    Kushner, R. J.
    NUCLEAR TECHNOLOGY, 2008, 161 (03) : 277 - 285
  • [39] Experimental investigation on the air-side flow and heat transfer characteristics of 3-D finned tube bundle
    Chen, Zi-yong
    Cheng, Min
    Liao, Qiang
    Ding, Yu-dong
    Zhang, Jun-nan
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 131 : 506 - 516
  • [40] Flow and heat transfer characteristics of cooling air outside the flat wave-finned tube banks of air-cooled condensers
    Beijing Key Laboratory of Safe and Clean Energy Technology, North China Electric Power University, Beijing 102206, China
    Zhongguo Dianji Gongcheng Xuebao, 2008, 26 (24-28): : 24 - 28