Accurate fault location element for series compensated double-circuit transmission lines utilizing negative-sequence phasors

被引:12
|
作者
Nemati, Mojtaba [1 ]
Bigdeli, Mehdi [1 ]
Ghorbani, Amir [2 ]
Mehrjerdi, Hasan [3 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, Zanjan Branch, Zanjan, Iran
[2] Islamic Azad Univ, Dept Elect Engn, Abhar Branch, Abhar, Iran
[3] Qatar Univ, Dept Elect Engn, Doha, Qatar
关键词
Fault location element (FLE); fault resistance; series compensated lines; double-circuit transmission lines; MOV-protected SC;
D O I
10.1016/j.epsr.2021.107064
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Obtaining the accurate fault location in the series compensated double-circuit transmission lines (SCDCTL) is a challenge due to the presence of series compensator, fault resistance, and mutual the coupling between parallel lines. Although by using the pilot fault location methods, the effect of all the aforementioned factors can be eliminated and the location of the fault can be calculated. However, the number of communication channels available for pilot schemes is limited. In addition, the reliability of the communication links for long transmission lines may be particularly reduced. On the other hand, most of the non-pilot methods need to calculate the series compensator data and the accuracy of the fault location in them depends on the accuracy of the series compensator parameters. To improve the limitation of conventional impedance-based methods, this paper presents a non-pilot accurate fault location element (FLE) for conventional distance relays in SCDCTL. The main concept of the proposed method is considering the proper Kirchhoff voltage law (KVL) loop in the negative sequence circuit of SCDCTL. Consideration of the shunt capacitances of lines ensures accuracy of the achieved fault location formula. It is shown that the designed FLE can improve limitations associated with similar methods such as the dependence of these methods to the fault resistance, mutual coupling between the parallel lines, and the series compensator (SC) parameters. To investigate the performance of the proposed FLE, several factors are considered in the simulation analysis including different fault resistances, fault locations, and fault types. Besides, the influence of current transformer (CT) saturation, measurement errors, external faults, bypassing of the Metal Oxide Varistor (MOV), and effect of noise on the proposed scheme is studied. Evaluation study using PSCAD verify the effectiveness and applicability of the proposed scheme.
引用
收藏
页数:16
相关论文
共 50 条
  • [31] Best ANN structures for fault location in single-and double-circuit transmission lines
    Gracia, J
    Mazón, AJ
    Zamora, I
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (04) : 2389 - 2395
  • [32] Feasibility study of intelligent fault location estimation methods for double-circuit transmission lines
    Swetapadma, Aleena
    Chakrabarti, Satarupa
    Abdelaziz, Almoataz Y.
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2021, 31 (12)
  • [33] A novel single-end fault location method for double-circuit transmission lines
    Arpanahi, Moossa Khodadadi
    Fini, Masoud Hajiakbari
    Nateghi, Abolfazl
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 158
  • [34] Fault Location Prediction on Double-circuit Transmission Lines Based on the Hierarchical Temporal Memory
    Idoniboyeobu, Dikio C.
    Wokoma, Biobele A.
    Osegi, Emmanuel N.
    2017 IEEE 3RD INTERNATIONAL CONFERENCE ON ELECTRO-TECHNOLOGY FOR NATIONAL DEVELOPMENT (NIGERCON), 2017, : 1100 - 1105
  • [35] New method of fault location on double-circuit two-terminal transmission lines
    Mazon, AJ
    Minambres, JF
    Zorrozua, MA
    Zamora, I
    AlvarezIsasi, R
    ELECTRIC POWER SYSTEMS RESEARCH, 1995, 35 (03) : 213 - 219
  • [36] An intelligent method for fault situation in double-circuit transmission lines utilizing extreme learning machine
    Gu, Hongmei
    Zhang, Qingqing
    Wang, Lei
    ELECTRICAL ENGINEERING, 2025, 107 (02) : 2051 - 2062
  • [37] Accurate fault location algorithm for shunt-compensated double circuit transmission lines using single end data
    Ghorbani, Amir
    Mehrjerdi, Hasan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 116
  • [38] High-speed auxiliary fault location element for distance relays in double-circuit lines
    Mehrjerdi, Hasan
    Ghorbani, Amir
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 200
  • [39] A Successive Geometric Segmentation Approach Applied to Double-Circuit Transmission Lines Fault Classification and Location
    Gaspar Valente W.A.
    de Mello Honório L.
    de Oliveira E.J.
    de Alcantara Barbosa D.
    Boas E.R.V.
    Journal of Control, Automation and Electrical Systems, 2016, 27 (4) : 452 - 462
  • [40] Study on Effect of Series Compensation on Double-Circuit Transmission Lines
    Reddy, S. Radha Krishna
    Subrahmanyam, J. B. V.
    Reddy, A. Srinivasula
    ARTIFICIAL INTELLIGENCE AND EVOLUTIONARY COMPUTATIONS IN ENGINEERING SYSTEMS, ICAIECES 2015, 2016, 394 : 1127 - 1143