Energetic analysis and performance improvement algorithm of transcritical CO2 heat pump water heater system

被引:10
|
作者
Liu, Xinxin [1 ,2 ]
Peng, Xu [1 ,2 ]
Yang, Yushen [1 ,2 ]
Qin, Xiang [1 ,2 ]
Wang, Dingbiao [1 ,2 ]
Wang, Guanghui [1 ,2 ]
Wang, Di [1 ,2 ]
机构
[1] Zhengzhou Univ, Sch Mech & Power Engn, Zhengzhou 450001, Peoples R China
[2] Minist Educ, Engn Res Ctr Energy Saving Technol & Equipment The, Zhengzhou 450001, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
Heat pump water heater; Optimal discharge pressure; Improvement algorithm; CO2; OPTIMUM HIGH-PRESSURE; CARBON-DIOXIDE; OPTIMIZATION; CYCLE;
D O I
10.1016/j.applthermaleng.2023.121823
中图分类号
O414.1 [热力学];
学科分类号
摘要
Transcritical CO2 heat pump water heaters have been widely studied by researchers for its environmentally friendly nature and energy efficiency. To analyze the impact of various operating parameters on the heating performance of transcritical CO2 heat pump water heater systems, simulation models were developed and their accuracy was verified through experiments. Results indicated that the discharge pressure and CO2 temperature at the gas cooler outlet (Tgc,out) had a significant effect on the system performance, the coefficient of performance (COP) increased notably with higher evaporation temperatures, and the optimal discharge pressure varied depending on the evaporation temperature. The system equipped with intermediate heat exchanger demonstrated a lower optimal discharge pressure and a higher COP compared to the basic system. The inclusion of an intermediate heat exchanger in a system, the maximum COP is 2.99 % to 3.83 % higher than the basic system under the same conditions. It has been observed that the introduction of intermediate heat exchanger significantly improved the system performance when Tgc,out were 35 degrees C, 40 degrees C and 45 degrees C, corresponding to discharge pressures lower than 10.75 MPa, 11.167 MPa and 11.625 MPa. According to the research results, the optimal discharge pressure equation was fitted and an improved algorithm was proposed. Compared to the experimental values, the improved algorithm exhibits a maximum error of 8.81 % and 7.55 % for determining the optimal discharge pressure and temperature, and the improved algorithm is effective in engineering applications. Consequently, the simulation data holds great importance in guiding the design of transcritical CO2 heat pump water heater systems.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Approaching optimum COP by refrigerant charge management in transcritical CO2 heat pump water heater
    He, Yu-Jia
    Liang, Xing-Yu
    Cheng, Jia-Hao
    Shao, Liang-Liang
    Zhang, Chun-Lu
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 161 - 172
  • [32] On the coupled system performance of transcritical CO2 heat pump and rankine cycle
    Hongli Wang
    Jingrui Tian
    Xiujuan Hou
    Heat and Mass Transfer, 2013, 49 : 1733 - 1740
  • [33] On the coupled system performance of transcritical CO2 heat pump and rankine cycle
    Wang, Hongli
    Tian, Jingrui
    Hou, Xiujuan
    HEAT AND MASS TRANSFER, 2013, 49 (12) : 1733 - 1740
  • [34] Experimental investigation on air-source transcritical CO2 heat pump water heater system at a fixed water inlet temperature
    Wang, Shouguo
    Tuo, Hanfei
    Cao, Feng
    Xing, Ziwen
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (03): : 701 - 716
  • [35] Optimal discharge pressure in transcritical CO2 heat pump water heater with internal heat exchanger based on pinch point analysis
    Ye, Zuliang
    Wang, Yikai
    Song, Yulong
    Yin, Xiang
    Cao, Feng
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 12 - 20
  • [36] Extremum seeking control of COP optimization for air-source transcritical CO2 heat pump water heater system
    Hu, Bin
    Li, Yaoyu
    Cao, Feng
    Xing, Ziwen
    APPLIED ENERGY, 2015, 147 : 361 - 372
  • [37] Ejector used in transcritical CO2 heat pump system
    Chen, Q. (zjuchenqi@zju.edu.cn), 1600, Materials China (63):
  • [38] Modeling and simulating the transcritical CO2 heat pump system
    Yang, Jun Lan
    Ma, Yi Tai
    Li, Min Xia
    Hua, Jun
    ENERGY, 2010, 35 (12) : 4812 - 4818
  • [39] Numerical performance of a water source transcritical CO2 heat pump with mechanical subcooling
    Illan-Gomez, Fernando
    Garcia-Cascales, Jose R.
    Velasco, F. J. S.
    Oton-Martinez, Ramon A.
    APPLIED THERMAL ENGINEERING, 2023, 219
  • [40] Experimental Study on the Compacts of Regenerative Heat on the Performance of the Transcritical CO2 Heat Pump System
    Zhao, Ling-Hua
    Wei, Xin-Li
    Yang, Ling-Xiao
    Qin, Xiang
    Zhang, Dong-Wei
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2020, 41 (01): : 186 - 195