A numerical study on cooling performance of different type earth-air heat exchangers

被引:1
|
作者
Tasdelen, Fatih [1 ]
Dagtekin, Ihsan [2 ]
机构
[1] Bitlis Eren Univ, Vocat Sch Tech Sci, TR-13000 Bitlis, Turkiye
[2] Firat Univ, Dept Mech Engn, TR-23119 Elazig, Turkiye
关键词
Earth-air heat exchanger; Temperature; Cooling performance; Soil; CFD; Re number; FLOW CHARACTERISTICS; THERMAL PERFORMANCE; SYSTEM; SOIL; SIMULATION; EAHE; VENTILATION; HOT; VALIDATION; BUILDINGS;
D O I
10.1016/j.renene.2024.122325
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Greenhouse gases released into the atmosphere are among the most important causes of climate change which affects the whole world today. The use of renewable energy sources should be encouraged in order to minimize greenhouse gas emissions increasing with the consumption of fossil energy sources. Energy consumption and greenhouse gas emission values of Earth-Air Heat Exchangers (EAHEs), which are systems based on renewable energy are quite low. In this study, analyses regarding the cooling performance of 3D-modeled different type (4 horizontal and 4 vertical) EAHEs with equal pipe lengths have been carried out in ANSYS FLUENT 19.2 software based on Computational Fluid Dynamics (CFD). The cooling performances of EAHEs have been examined within the Reynolds numbers range of (5x103 < Re < 105). Rises in the Reynolds number significantly influence the cooling efficacy of the EAHEs, whereas the soil thermal conductivity has less impact on their cooling efficiency. Mean air temperature reductions of 14.90 K and 18.44 K have been recorded for the Re = 5x103 value, while reductions of 8.12 K and 8.07 K have been seen for the Re = 105 value of the horizontal and vertical EAHEs, respectively. The energy savings for the EAHEs demonstrating better cooling performance over the summer season have been examined. The optimal energy saving for these EAHEs has been attained at the Reynolds number of 6x104. At the Reynolds number of 6x104, 378.048 kWh and 397.275 kWh of energy savings have been obtained for horizontal and vertical EAHEs, respectively. The maximum financial savings for H-model III and Vmodel IV EAHE over the summer season were 32.285 euros and 33.927 euros, respectively, at the Reynolds number of 6x104.
引用
收藏
页数:16
相关论文
共 50 条
  • [1] The experimental study and numerical of pipe finned as a earth-air heat exchangers
    Pintoro, A.
    Manik, T. U. H. S. G.
    Sitorus, T. B.
    Sihombing, E. A.
    1ST INTERNATIONAL CONFERENCE ON INDUSTRIAL AND MANUFACTURING ENGINEERING, 2019, 505
  • [2] Earth-air heat exchangers: Performance prediction assessment
    De Paepe, M.
    Steeman, M.
    Janssens, A.
    RESEARCH IN BUILDING PHYSICS AND BUILDING ENGINEERING, 2006, : 677 - +
  • [3] Design of earth-air heat exchangers
    Janssens, A
    De Paepe, M
    RESEARCH IN BUILDING PHYSICS, 2003, : 835 - 842
  • [4] Numerical Simulation of Vertical Helical Earth-Air Heat Exchangers: Multiobjective Performance Assessment
    Razera, Andre Luis
    Vaz, Igor Silva
    Kepes Rodrigues, Michel
    Domingues Dos Santos, Elizaldo
    Oliveira Rocha, Luiz Alberto
    Isoldi, Liércio Andre
    Defect and Diffusion Forum, 2024, 435 : 77 - 89
  • [5] A NUMERICAL STUDY ON HEATING PERFORMANCE OF HORIZONTAL AND VERTICAL EARTH-AIR HEAT EXCHANGERS WITH EQUAL PIPE LENGTHS
    Tasdelen, Fatih
    Dagtekin, Ihsan
    THERMAL SCIENCE, 2022, 26 (04): : 2929 - 2939
  • [6] An experimental study on the use of Earth-Air Heat Exchangers (EAHE)
    Vaz, Joaquim
    Sattler, Miguel A.
    Brum, Ruth da S.
    dos Santos, Elizaldo D.
    Isoldi, Liercio A.
    ENERGY AND BUILDINGS, 2014, 72 : 122 - 131
  • [7] The cooling potential of earth-air heat exchangers for domestic buildings in a desert climate
    Al-Ajmi, F
    Loveday, DL
    Hanby, VI
    BUILDING AND ENVIRONMENT, 2006, 41 (03) : 235 - 244
  • [8] The potential of earth-air heat exchangers for low energy cooling of buildings in South Algeria
    Sehli, Abdelkrim
    Hasni, Abdelhafid
    Tamali, Mohammed
    TERRAGREEN 2012: CLEAN ENERGY SOLUTIONS FOR SUSTAINABLE ENVIRONMENT (CESSE), 2012, 18 : 496 - 506
  • [9] A Numerical Investigation of Thermal Performance of Earth-Air Heat Exchanger
    Tasdelen, F.
    Dagtekin, I.
    ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2019, 44 (02) : 1151 - 1163
  • [10] Accessing the thermal performance of Earth-air heat exchangers surrounded by galvanized structures
    Ramalho, J. V. A.
    Fernando, H. J.
    Brum, R. S.
    Domingues, A. M. B.
    Navarro Pastor, N. R.
    Burlon Olivera, M. R.
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2022, 54