Buildup of Fault Protection for High-Current Single-Phase Transformers in Ore Furnaces

被引:0
|
作者
Rakhimberdinova, Dilara [1 ]
Novozhilov, Aleksandr [1 ]
Kolesnikov, Evgeniy [1 ]
Goryunov, Vladimir [2 ]
Novozhilov, Timofey [2 ]
机构
[1] Toraighyrov Univ, Elect Engn & Automat Dept, Lomov Str 64, Pavlodar 140008, Kazakhstan
[2] Omsk State Tech Univ, Power Supply Ind Enterprises Dept, Mira Ave,11, Omsk 644050, Russia
关键词
relay protection; single-phase furnace transformer; splitting of the secondary winding; high-current system; magnetic current transformer; turn-to-turn fault; arc fault in tube buses; busbar circuit break;
D O I
10.3390/en17112630
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
High-power ore furnaces mainly use single-phase transformers supplied by phase-to-phase voltage with the secondary winding made in the form of four to eight isolated splits and a high-voltage busbar assembly made of the same number of pairs of tube buses. Due to these design features, turn-to-turn faults are the main faults in the primary winding of the transformer, and flexible coupling breaks and arc faults in splitting circuits prevail in the high-voltage system. This is why current and gas protections are currently used to protect transformers against short circuits. However, current protections are insensitive to turn faults, and the gas protection response time can be long since it strongly depends on the oil temperature. High-current systems are protected from arc faults only by insulating tube buses. However, this insulation is gradually destroyed under the impact of abrasive dust in the air, and the presence of coal dust in the air creates conditions for arc faults. There is no protection against breaks in the circuits of pairs of tube buses. The extent of damage in a transformer and its high-current system due to the faults can be significantly reduced by using new protection devices based on the measurements of the longitudinal and transverse asymmetry of the stray magnetic fields of the protected transformer. To implement these protections, this article suggests a method for protecting a transformer and a high-current system using magnetic current transformers (MCTs). The number and points for MCT winding coils are determined through the analysis of their EMF values versus their positions relative to the windings of the transformer operating under different modes. The results serve as the basis for the protection circuit design; the protection response threshold is calculated, the protection operation is described, and the results of the experiment are given.
引用
收藏
页数:16
相关论文
共 50 条
  • [41] A protection method of a single-phase break fault for an active distribution network based on current change rates of distributed generation
    Du X.
    Ouyang J.
    Long X.
    Liu B.
    Huang L.
    Wang Z.
    Zhang S.
    Xiaoyang
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2020, 48 (22): : 41 - 48
  • [42] A new method for single-phase high resistance grounding fault protection in low resistance grounded distribution networks
    Wang, Gang
    Wang, Liyi
    ENGINEERING REPORTS, 2024, 6 (04)
  • [43] Single-phase earth fault protection method based on combined voltage criterion in high voltage shunt capacitor
    Ma W.
    Kong S.
    Liu C.
    Song C.
    Liu Y.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2019, 47 (22): : 142 - 147
  • [44] A new method for single-phase high resistance grounding fault protection in low resistance grounded distribution networks
    Wang, Gang
    Wang, Liyi
    ENGINEERING REPORTS, 2023,
  • [45] Investigation of frequency characteristics of selected single-phase transformers
    Wyderka, Stanislaw
    PRZEGLAD ELEKTROTECHNICZNY, 2011, 87 (08): : 108 - 111
  • [46] Ferroresonance Modes Determination of Single-Phase Toroidal Transformers
    Cazacu, Emil
    Petrescu, Lucian
    Ionita, Valentin
    2017 15TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES, DRIVES AND POWER SYSTEMS (ELMA), 2017, : 358 - 361
  • [47] Nonlinear load influence on single-phase fault current in shipboard electric networks
    Kazhekin, Ilya E.
    Finko, Sergey P.
    Kharitonov, Maxim S.
    MARINE INTELLECTUAL TECHNOLOGIES, 2021, (04): : 59 - 64
  • [48] Experimental Study on Single-phase Grounding Fault Safety Current of Large Generators
    Zhang, Guodong
    Gui, Lin
    Wang, Xiangheng
    Zhang, Qixue
    He, Yingzhang
    Liu, Chuankun
    2018 IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2018 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2018,
  • [49] Current-Sharing Behaviour of Single-Phase HTS Transformers With Stacked-Tape Cables
    Rice, James H. P.
    Moseley, Dominic A.
    Petrov, Alexander
    Zhang, Heng
    Wray, Steven
    Badcock, Rodney A.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2024, 34 (03) : 1 - 5
  • [50] Single-phase grounded fault protection schemes of generator stator based on orthonormal wavelet
    Tai, Nengling
    Yin, Xianggen
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2001, 25 (01): : 34 - 37