Buildup of Fault Protection for High-Current Single-Phase Transformers in Ore Furnaces

被引:0
|
作者
Rakhimberdinova, Dilara [1 ]
Novozhilov, Aleksandr [1 ]
Kolesnikov, Evgeniy [1 ]
Goryunov, Vladimir [2 ]
Novozhilov, Timofey [2 ]
机构
[1] Toraighyrov Univ, Elect Engn & Automat Dept, Lomov Str 64, Pavlodar 140008, Kazakhstan
[2] Omsk State Tech Univ, Power Supply Ind Enterprises Dept, Mira Ave,11, Omsk 644050, Russia
关键词
relay protection; single-phase furnace transformer; splitting of the secondary winding; high-current system; magnetic current transformer; turn-to-turn fault; arc fault in tube buses; busbar circuit break;
D O I
10.3390/en17112630
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
High-power ore furnaces mainly use single-phase transformers supplied by phase-to-phase voltage with the secondary winding made in the form of four to eight isolated splits and a high-voltage busbar assembly made of the same number of pairs of tube buses. Due to these design features, turn-to-turn faults are the main faults in the primary winding of the transformer, and flexible coupling breaks and arc faults in splitting circuits prevail in the high-voltage system. This is why current and gas protections are currently used to protect transformers against short circuits. However, current protections are insensitive to turn faults, and the gas protection response time can be long since it strongly depends on the oil temperature. High-current systems are protected from arc faults only by insulating tube buses. However, this insulation is gradually destroyed under the impact of abrasive dust in the air, and the presence of coal dust in the air creates conditions for arc faults. There is no protection against breaks in the circuits of pairs of tube buses. The extent of damage in a transformer and its high-current system due to the faults can be significantly reduced by using new protection devices based on the measurements of the longitudinal and transverse asymmetry of the stray magnetic fields of the protected transformer. To implement these protections, this article suggests a method for protecting a transformer and a high-current system using magnetic current transformers (MCTs). The number and points for MCT winding coils are determined through the analysis of their EMF values versus their positions relative to the windings of the transformer operating under different modes. The results serve as the basis for the protection circuit design; the protection response threshold is calculated, the protection operation is described, and the results of the experiment are given.
引用
收藏
页数:16
相关论文
共 50 条
  • [31] Fault Current Limiting Investigation for a Single-Phase Dynamic Voltage Conditioner
    Faranda, Roberto
    Bahrami, Ali
    Hafezi, Hossein
    2019 IEEE MILAN POWERTECH, 2019,
  • [32] HIGH-CURRENT TRANSFORMERS AND REACTORS FOR RECTIFIER AND FURNACE INSTALLATIONS
    KREUZER, J
    BROWN BOVERI REVIEW, 1976, 63 (07): : 455 - 461
  • [33] Non-linearity of Hysteresis and Eddy Current Losses of Single-phase Distribution Transformers
    Santos, Filipe Freire
    Lopes, Gustavo Paiva
    Wanderley Neto, Estacio Tavares
    Villibor, Jansen Paula
    Faria, Gabriel Henrique
    Pereira, Matheus Penha
    2021 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2021, : 626 - 630
  • [34] Discrimination between magnetizing inrush and fault currents in single-phase transformers using power method
    Al-Tallaq, KN
    2004 LARGE ENGINEERING SYSTEMS CONFERENCE ON POWER ENGINEERING, CONFERENCE PROCEEDINGS: ENERGY FOR THE DAY AFTER TOMORROW, 2004, : 118 - 122
  • [35] Protection methods of single-phase broken-line fault for distribution line
    Kang Q.
    Cong W.
    Sheng Y.
    Wang Y.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2019, 47 (08): : 127 - 136
  • [36] ELECTRICAL-RESISTANCE OF GLASS IN SINGLE-PHASE FURNACES
    TATEVOSYAN, KM
    GLASS AND CERAMICS, 1984, 41 (1-2) : 57 - 62
  • [37] ANALYSIS OF RESIDUAL VOLTAGE OF ZERO-PHASE-SEQUENCE CURRENT TRANSFORMERS FOR SINGLE-PHASE CIRCUIT USE
    YAMAMOTO, Y
    YAMADA, H
    ELECTRICAL ENGINEERING IN JAPAN, 1972, 91 (03) : 149 - &
  • [38] Primary high-current testing of relays with low ratio current transformers
    Zocholl, SE
    Mooney, JB
    CONFERENCE RECORD OF THE 2004 ANNUAL PULP AND PAPER INDUSTRY TECHNICAL CONFERENCE, 2004, : 192 - 197
  • [39] Fault tolerant DC-link single-phase to single-phase converter
    Jacobina, C. B.
    dos Santos, E. C., Jr.
    de Freitas, I. S.
    da Silva, E. R. C.
    Oliveira, T. M.
    Correa, M. B. R.
    2006 IEEE POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-7, 2006, : 545 - 551
  • [40] Primary high-current testing of relays with low ratio current transformers
    Zocholl, SE
    Mooney, J
    2004 57TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2004, : 182 - 189