Buildup of Fault Protection for High-Current Single-Phase Transformers in Ore Furnaces

被引:0
|
作者
Rakhimberdinova, Dilara [1 ]
Novozhilov, Aleksandr [1 ]
Kolesnikov, Evgeniy [1 ]
Goryunov, Vladimir [2 ]
Novozhilov, Timofey [2 ]
机构
[1] Toraighyrov Univ, Elect Engn & Automat Dept, Lomov Str 64, Pavlodar 140008, Kazakhstan
[2] Omsk State Tech Univ, Power Supply Ind Enterprises Dept, Mira Ave,11, Omsk 644050, Russia
关键词
relay protection; single-phase furnace transformer; splitting of the secondary winding; high-current system; magnetic current transformer; turn-to-turn fault; arc fault in tube buses; busbar circuit break;
D O I
10.3390/en17112630
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
High-power ore furnaces mainly use single-phase transformers supplied by phase-to-phase voltage with the secondary winding made in the form of four to eight isolated splits and a high-voltage busbar assembly made of the same number of pairs of tube buses. Due to these design features, turn-to-turn faults are the main faults in the primary winding of the transformer, and flexible coupling breaks and arc faults in splitting circuits prevail in the high-voltage system. This is why current and gas protections are currently used to protect transformers against short circuits. However, current protections are insensitive to turn faults, and the gas protection response time can be long since it strongly depends on the oil temperature. High-current systems are protected from arc faults only by insulating tube buses. However, this insulation is gradually destroyed under the impact of abrasive dust in the air, and the presence of coal dust in the air creates conditions for arc faults. There is no protection against breaks in the circuits of pairs of tube buses. The extent of damage in a transformer and its high-current system due to the faults can be significantly reduced by using new protection devices based on the measurements of the longitudinal and transverse asymmetry of the stray magnetic fields of the protected transformer. To implement these protections, this article suggests a method for protecting a transformer and a high-current system using magnetic current transformers (MCTs). The number and points for MCT winding coils are determined through the analysis of their EMF values versus their positions relative to the windings of the transformer operating under different modes. The results serve as the basis for the protection circuit design; the protection response threshold is calculated, the protection operation is described, and the results of the experiment are given.
引用
收藏
页数:16
相关论文
共 50 条
  • [21] Single-phase earth-fault protection for network with insulated neutral
    Malafeev, S.I.
    Mamaj, V.S.
    Anuchin, A.V.
    Mikryukov, V.I.
    Serebrennikov, N.A.
    Promyshlennaya Energetika, 2003, (05): : 13 - 16
  • [22] Protection of a single-phase transformer from interwinding failure in windings of integral magnetic transformers
    Novozhilov A.N.
    Goryunov V.N.
    Novozhilov T.A.
    Russian Electrical Engineering, 2018, 89 (2) : 118 - 121
  • [23] Measurement of electrical parameters in high-current arc furnaces
    Lorenzo, A.
    Lage, M.
    Bullon, J.
    Rivas, J.
    Fondado, A.
    Torres, A.
    Farina, J.
    Rodriguez-Andina, J. J.
    2007 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, PROCEEDINGS, VOLS 1-8, 2007, : 1565 - +
  • [24] Numerical models of single-phase superconducting transformers
    Surdacki, Pawel
    Jaroszynski, Leszek
    Wozniak, Lukasz
    PRZEGLAD ELEKTROTECHNICZNY, 2021, 97 (04): : 162 - 165
  • [25] Single-phase vs. Three-phase High Density Power Transformers
    Xue, Jing
    Wang, Fred
    Boroyevich, Dushan
    Shen, Zhiyu
    2010 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION, 2010, : 4368 - 4375
  • [26] Single-phase high-impedance fault protection for low-resistance grounded distribution network
    Tang, Tao
    Huang, Chun
    Hua, Leng
    Zhu, Jiran
    Zhang, Zhidan
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (10) : 2462 - 2470
  • [27] Integration of Fault Current Limiting Function into a Single-Phase Series Compensator
    Bahrami, A.
    Faranda, R.
    Hafezi, H.
    2018 18TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP), 2018,
  • [28] Analyzing the Operating Modes of a Single-Phase Autotransformer in a Three-Phase Bank of Single-Phase Transformers
    Tiguntsev S.G.
    Vishnyakov D.A.
    Vishnyakov N.A.
    Power Technology and Engineering, 2023, 57 (04) : 629 - 632
  • [29] Single-phase motors fault current contribution to the electrical power system
    Hamza, ASHA
    AbdelGawad, NMK
    ENERGY CONVERSION AND MANAGEMENT, 1997, 38 (02) : 115 - 130
  • [30] Single-Phase Grounding Fault Location in the Small Current Grounding System
    Wu, Gui-feng
    Chen, Hong
    Wang, Xu
    Teng, Hao
    INTERNATIONAL CONFERENCE ON ARTIFICIAL INTELLIGENCE AND SOFTWARE ENGINEERING (AISE 2014), 2014, : 251 - 255