Experimental study of a natural draft hybrid (wet/dry) cooling tower with a splash fill type

被引:0
|
作者
Ali, Abdullah Kadhlm [1 ]
Mohammed, Ahmed Qassem [1 ]
Mahdi, Qasim Selah [2 ]
机构
[1] Middle Tech Univ, Engn Tech Coll, Mech Eng Dept IRAQ, Baghdad, Iraq
[2] Mustansiriyah Univ, Mech Engn Dept IRAQ, Coll Engn, Baghdad, Iraq
关键词
cooling range; wet bulb temperature; cooling tower; performance factors; air velocity; splash fill type; heat exchanger; ARTIFICIAL NEURAL-NETWORK; CROSS-WIND; COUNTER-FLOW; PERFORMANCE;
D O I
10.3934/energy.2022031
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Cooling towers have such a significant influence on work and efficiency that researchers and designers are working tirelessly to enhance their performance. A prototype design for a natural draft hybrid (wet/dry) cooling tower has been created, relying on geometrical, dynamic, and thermodynamic similarities. Based on Iraqi weather, experiments have been conducted using splash fill (150 mm) in summer (hot and dry) weather conditions. This study investigated heat transfer mechanisms of both air and water in a natural draft hybrid cooling tower model(NDHCTs), both directly (wet section) and indirectly (dry section). The tower is filled with splash-style packing, and the warm water is spread throughout the building using sprayer nozzles. The influences of water flow rates, fill thickness, and air velocity on the cooling range, approach, cooling capacity, thermal efficiency of the cooling tower, water evaporation loss into the air stream and water loss percentage were explored in this study. The experimental were carried out with four different water flow rates, ranging from 7.5 to 12 (Lpm) litres per minute, and eight different air velocities, all while keeping a constant inlet water temperature and a zero (m/s) crosswind. Data has been gathered, and performance variables have been determined. The findings demonstrate that the cooling tower's efficacy increases when the water flow rate is low, and the cooling range increases with increasing air velocity and decreases with increasing water flow rate; for a 7.5 Lpm water flow rate and a 2.4 m/s air velocity, it expanded to 19.5 degrees C. The cooling capacity increased to 23.2 kW for a water flow rate of 12 Lpm and an air velocity of 2.4 m/s.
引用
收藏
页码:648 / 664
页数:17
相关论文
共 50 条
  • [21] Cooling performance of cylinder-frustum natural draft dry cooling tower
    Song, Guoqing
    Zhi, Xudong
    Fan, Feng
    Wang, Wei
    Wang, Peng
    APPLIED THERMAL ENGINEERING, 2020, 180
  • [22] Theoretical study on impact of the dissipative muffler on the cooling performance of the hybrid mechanical draft wet cooling tower
    Zhang, Xiaoyu
    Sun, Fengzhong
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2025, 164
  • [23] Numerical simulation for thermal performance of natural draft wet cooling tower
    Zhou, Lan-Xin
    Jiang, Bo
    Chen, Su-Min
    Shuili Xuebao/Journal of Hydraulic Engineering, 2009, 40 (02): : 208 - 213
  • [24] Determination of Natural Draft Wet-Cooling Tower Loss Coefficient
    Hyhlik, Tomas
    37TH MEETING OF DEPARTMENTS OF FLUID MECHANICS AND THERMODYNAMICS, 2018, 2000
  • [25] Evaluation of thermal performance for natural and forced draft wet cooling tower
    Al-Dulaimi, M. J.
    Kareem, F. A.
    Hamad, F. A.
    JOURNAL OF MECHANICAL ENGINEERING AND SCIENCES, 2019, 13 (04) : 6007 - 6021
  • [26] EXPERIMENTAL INVESTIGATION OF THE THERMAL PERFORMANCE OF WET COOLING TOWER WITH SPLASH FILLS PACKING
    Ahmed, Shaymaa A.
    Aljaberi, Forat Yasir
    Makki, Hasan F.
    THERMAL SCIENCE, 2022, 26 (02): : 1603 - 1613
  • [27] NATURAL DRAFT COOLING TOWER
    STENNING, AH
    FURZER, I
    INDUSTRIAL & ENGINEERING CHEMISTRY PROCESS DESIGN AND DEVELOPMENT, 1969, 8 (04): : 599 - &
  • [28] An exploratory research on performance improvement of super-large natural draft wet cooling tower based on the reconstructed dry-wet hybrid rain zone
    Zhang, Zhengqing
    Gao, Ming
    Dang, Zhigang
    He, Suoying
    Sun, Fengzhong
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 142
  • [29] Comparative evaluation of hybrid (dry/wet) cooling tower performance
    Asvapoositkul, Wanchai
    Kuansathan, Mantheerapol
    APPLIED THERMAL ENGINEERING, 2014, 71 (01) : 83 - 93
  • [30] Comparative evaluation of hybrid (dry/wet) cooling tower performance
    Asvapoositkul, W. (wanchai.asv@kmutt.ac.th), 1600, Elsevier Ltd (71):