Development and Type Test of a Single-Break 126-kV/40-kA-2500-A Vacuum Circuit Breaker

被引:34
|
作者
Yao, Xiaofei [1 ]
Wang, Jianhua [1 ]
Geng, Yingsan [1 ]
Yan, Jing [1 ]
Liu, Zhiyuan [1 ]
Yao, Jianjun [2 ]
Liu, Ping [3 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] Shaanxi Ind Technol Res Inst, Xian 710049, Peoples R China
[3] Xian High Voltage Apparat Res Inst Co Ltd, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Type test; vacuum circuit breaker (VCB); vacuum interrupter; AXIAL MAGNETIC-FIELD; ARC; INTERRUPTERS; STRENGTH; CONTACTS; POWER;
D O I
10.1109/TPWRD.2015.2456033
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The objective of this paper is to present a 126-kV/40-kA-2500-A single-break vacuum circuit breaker (VCB) and its type test results based on the IEC 62271-100: 2006 and GB1984-2003 standards. A single-break 126-kV vacuum interrupter (VI), with a pair of 2/3 coil-type contacts, is used in the 126-kV VCB. The external insulation of the VI is provided by at 0.1 MPa. A spring-type operating mechanism is used to provide a closing velocity of 1.15 m/s, which is an average velocity for 4 mm before the moving contact mates with the stationary contact. The opening velocity within 20 mm, which is 1/3 of a full contact stroke of 60 mm, is 3.5 m/s. Two kinds of test circuits are used in the type tests to verify the making and breaking capabilities of this 126-kV VCB prototype. One is a direct test circuit for test duty cycles, such as out-of-phase making and breaking test duties, that is, OP1 and OP2; capacitive current switching test of class C1, that is, CC1/LC1 and CC2/LC2. The other is a synthetic circuit, used for tests, such as the terminal fault test, the short-line fault test, the double earth fault test, and the electrical endurance test of class E2. The dielectric tests of a 230-kV/1 min power frequency voltage withstand test and a 550-kV lightning impulse voltage withstand test were used to verify the dielectric withstand performance of the VCB. Experiment results presented in this paper showed that the 126-kV/40 kA-2500 A single-break VCB passed the type tests according to IEC 62271-100 and GB1984-2003.
引用
收藏
页码:182 / 190
页数:9
相关论文
共 32 条
  • [31] FACTORS INFLUENCING THE INTERRUPTING ABILITY OF SF6 PUFFER BREAKER AND DEVELOPMENT OF 300KV-50KA ONE-BREAK CIRCUIT-BREAKER
    YANABU, S
    MIZOGUCHI, H
    KOBAYASHI, A
    OZAKI, Y
    MURAKAMI, Y
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (06): : 1511 - 1518
  • [32] Prestrike Characteristics of Single-Break Vacuum Circuit Breakers With Cup-Type AMF Contacts and Spiral-Type TMF Contacts Under Inrush Current Conditions
    Geng, Yun
    Yao, Xiaofei
    Dong, Jinlong
    Huang, Jincai
    Chen, Xinggui
    Li, Haomin
    Geng, Yingsan
    Liu, Zhiyuan
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2022, 50 (09) : 2660 - 2669