Development and Type Test of a Single-Break 126-kV/40-kA-2500-A Vacuum Circuit Breaker

被引:34
|
作者
Yao, Xiaofei [1 ]
Wang, Jianhua [1 ]
Geng, Yingsan [1 ]
Yan, Jing [1 ]
Liu, Zhiyuan [1 ]
Yao, Jianjun [2 ]
Liu, Ping [3 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] Shaanxi Ind Technol Res Inst, Xian 710049, Peoples R China
[3] Xian High Voltage Apparat Res Inst Co Ltd, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Type test; vacuum circuit breaker (VCB); vacuum interrupter; AXIAL MAGNETIC-FIELD; ARC; INTERRUPTERS; STRENGTH; CONTACTS; POWER;
D O I
10.1109/TPWRD.2015.2456033
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The objective of this paper is to present a 126-kV/40-kA-2500-A single-break vacuum circuit breaker (VCB) and its type test results based on the IEC 62271-100: 2006 and GB1984-2003 standards. A single-break 126-kV vacuum interrupter (VI), with a pair of 2/3 coil-type contacts, is used in the 126-kV VCB. The external insulation of the VI is provided by at 0.1 MPa. A spring-type operating mechanism is used to provide a closing velocity of 1.15 m/s, which is an average velocity for 4 mm before the moving contact mates with the stationary contact. The opening velocity within 20 mm, which is 1/3 of a full contact stroke of 60 mm, is 3.5 m/s. Two kinds of test circuits are used in the type tests to verify the making and breaking capabilities of this 126-kV VCB prototype. One is a direct test circuit for test duty cycles, such as out-of-phase making and breaking test duties, that is, OP1 and OP2; capacitive current switching test of class C1, that is, CC1/LC1 and CC2/LC2. The other is a synthetic circuit, used for tests, such as the terminal fault test, the short-line fault test, the double earth fault test, and the electrical endurance test of class E2. The dielectric tests of a 230-kV/1 min power frequency voltage withstand test and a 550-kV lightning impulse voltage withstand test were used to verify the dielectric withstand performance of the VCB. Experiment results presented in this paper showed that the 126-kV/40 kA-2500 A single-break VCB passed the type tests according to IEC 62271-100 and GB1984-2003.
引用
收藏
页码:182 / 190
页数:9
相关论文
共 32 条
  • [21] Design and Performance Test of Electro-magnetic Force Actuator for 126kV Single Break Vacuum Circuit Breaker With Controlled Switching
    Tian Y.
    Xu J.
    Wang Y.
    Dong E.
    Tian K.
    Dong, Enyuan (dey@dlut.edu.cn), 1600, Power System Technology Press (44): : 4445 - 4453
  • [22] Test on novel design and breaking capacity for 126 kV high voltage vacuum circuit breaker
    Wen, Huabin
    Song, Yongduan
    Zou, Jiyan
    Zheng, Zhanfeng
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2011, 31 (34): : 198 - 204
  • [23] Static and dynamic voltage sharing design of 126 kV modular triple-break vacuum circuit breaker
    Wu, Gaobo
    Ruan, Jiangjun
    Huang, Daochun
    Shu, Shengwen
    Tu, Qihua
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2013, 33 (19): : 215 - 223
  • [24] Comparison of Mounted Angles Between a Pair of 2/3 Coil-type AMF Electrodes in a 126 kV Single-break Vacuum Interrupter
    Feng, Weigang
    Bi, Dongli
    Wang, Quan
    Yao, Xiaofei
    Zhai, Xiaoshe
    Liu, Zhiyuan
    2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST), 2017, : 145 - 148
  • [25] Simulation and Analysis of Small Capacitive Current Interruption of a 550kV Single-break SF6 Circuit Breaker
    Hao, Xiangyu
    Guo, Yujing
    Yao, Yongqi
    Wang, Zhijun
    2018 2ND IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2018,
  • [26] Development of 550kV 63.kA one-break gas circuit breaker
    Ochiai, I
    Kohyama, H
    Ito, H
    Hidaka, M
    Sugiyama, T
    Yamamoto, H
    Matuszak, D
    IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC, 2002, : 93 - 98
  • [27] Relationship between Displacement Characteristics of a 126kV Vacuum Circuit Breaker and Spring Type Operating Mechanism
    Yu, Li
    Geng, Yingsan
    Liu, Zhiyuan
    Sun, Liqiong
    Yao, Jianjun
    ISDEIV 2008: PROCEEDINGS OF THE XXIIIRD INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, 2008, : 137 - +
  • [28] Development of Axial Magnetic Field Type Vacuum Interrupter for 170kV Circuit Breaker
    Ryu, Jaeseop
    Joo, Hyun-Woo
    Tak, Sungjun
    Kim, Young-Geun
    Park, Seokweon
    COMPUTER FIELD MODELS OF ELECTROMAGNETIC DEVICES, 2010, 34 : 558 - 564
  • [29] Simulation Analysis of the 126kV Three-break Vacuum Circuit Breaker with Phase-control Method Used in Capacitive Interrupting
    Liu Bo
    Zhang Chao-hai
    Xiu Shi-xin
    PROCEEDINGS OF THE 27TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV), VOL 1, 2016, : 185 - 188
  • [30] FACTORS INFLUENCING THE INTERRUPTING ABILITY OF SF6 PUFFER BREAKER AND DEVELOPMENT OF 300kV-50kA ONE-BREAK CIRCUIT BREAKER.
    Yanabu, S.
    Mizoguchi, H.
    Kobayashi, A.
    Ozaki, Y.
    Murakami, Y.
    SAE Preprints, 1981,