Prospects of Improving the Indoor Air Quality in Classrooms by Reactivating Historic Ventilation Stacks

被引:0
|
作者
Hellwig, Runa T. [1 ,2 ]
Sedlmeier, Michael [1 ]
Tanzer, Christian [1 ]
机构
[1] Augsburg Univ Appl Sci, Unit E2D Energy Efficiency Design, Augsburg, Germany
[2] Natl Univ Singapore, Dept Bldg, Sch Design & Environm, Cluster Solar & Energy Efficient Bldg,Solar Energ, Singapore 11757, Singapore
关键词
school building; ventilation stack; indoor air quality; historic ventilation system;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Stack ventilation systems were installed in German schools constructed around 1900 and are no longer in operation. The aim of this study was to show how reactivating these systems could improve the indoor air quality in classrooms. Ventilation stacks were reactivated in three classrooms in a school while a fourth classroom, which was naturally ventilated via openable windows, served as the reference case. All classrooms were measured for carbon dioxide levels, air temperature and relative humidity. During winter, 50% of all measured carbon dioxide values in the classroom with natural ventilation using windows were higher than 1800 ppm. All classrooms with stack ventilation showed median values of 1600 and 1350 ppm. In these classrooms, the volumetric flow rate per person in winter (14 m(3)/(h.pers)) was approximately seven times higher compared to the classroom with window ventilation (2 m(3)/(h.pers)). The supply stacks provided a preheating effect of 0.5 to 0.7 K/m. Effects of summer flow reversal were found in both of the classrooms with exhaust and supply ventilation stacks. Reactivating ventilation stacks provides the potential to improve indoor air quality in classrooms. Some adjustment of the systems, such as adding automated dampers to close the stacks at night and during flow reversal in summer, could allow the systems to meet today's hygienic and comfort requirements and turn them into modern low energy consuming systems.
引用
收藏
页码:141 / 152
页数:12
相关论文
共 50 条
  • [31] VENTILATION AND INDOOR AIR-QUALITY
    SEPPANEN, OA
    KUKKONEN, E
    INTERNATIONAL SYMPOSIUM - ENERGY OPTIONS FOR THE YEAR 2000 : CONTEMPORARY CONCEPTS IN TECHNOLOGY AND POLICY, VOLS 1-4: ENERGY SYSTEM ; TECHNOLOGY FUTURES : ENERGY BUILDINGS ; INTERNATIONAL COOPERATION, 1988, : C33 - C39
  • [32] Ventilation for acceptable indoor air quality
    ASHRAE Standard, 2004, (62.1):
  • [33] Higher Attention Capacity After Improving Indoor Air Quality by Indoor Plant Placement in Elementary School Classrooms
    Kim, Ho-Hyun
    Yeo, In-Young
    Lee, Jae-Young
    HORTICULTURE JOURNAL, 2020, 89 (03): : 319 - 327
  • [34] Indoor air quality in classrooms: Environmental measures and effective ventilation rate modeling in urban elementary schools
    Johnson, David L.
    Lynch, Robert A.
    Floyd, Evan L.
    Wang, Jun
    Bartels, Jacob N.
    BUILDING AND ENVIRONMENT, 2018, 136 : 185 - 197
  • [35] Indoor Air Quality and Bioaerosols in Spanish University Classrooms
    Fuentes-Ferragud, Esther
    Lopez, Antonio
    Piera, Juan Miguel
    Yusa, Vicent
    Garrigues, Salvador
    de la Guardia, Miguel
    Labrador, F. Xavier Lopez
    Camaro, Marisa
    Ibanez, Maria
    Coscolla, Clara
    TOXICS, 2024, 12 (03)
  • [36] Investigation of Indoor Air Quality in Primary School Classrooms
    Hou, Yuefei
    Liu, Junjie
    Li, Jiayu
    9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 830 - 837
  • [37] Indoor Air Quality in Naturally Ventilated Italian Classrooms
    Fuoco, Fernanda Carmen
    Stabile, Luca
    Buonanno, Giorgio
    Trassiera, Concepcion Vargas
    Massimo, Angelamaria
    Russi, Aldo
    Mazaheri, Mandana
    Morawska, Lidia
    Andrade, Alexandro
    ATMOSPHERE, 2015, 6 (11) : 1652 - 1675
  • [38] WSN Based Indoor Air Quality Monitoring In Classrooms
    Wang, S. K.
    Chew, S. P.
    Jusoh, M. T.
    Khairunissa, A.
    Leong, K. Y.
    Azid, A. A.
    11TH ASIAN CONFERENCE ON CHEMICAL SENSORS (ACCS2015), 2017, 1808
  • [39] Effect of quality and maintenance of the ventilation to the indoor air quality
    Niskanen, J
    Valkeapää, A
    Anttonen, H
    PROGRESS IN MODERN VENTILATION, VOL 2, PROCEEDINGS, 2000, : 168 - 171
  • [40] Improving indoor air quality and thermal comfort in residential kitchens with a new ventilation system
    Liu, Sumei
    Cao, Qing
    Zhao, Xingwang
    Lu, Zechao
    Deng, Zhipeng
    Dong, Jiankai
    Lin, Xiaorui
    Qing, Ke
    Zhang, Weizhen
    Chen, Qingyan
    BUILDING AND ENVIRONMENT, 2020, 180