Conventional and advanced exergy analyses of an air-conditioning system in a subway station

被引:7
|
作者
Yin, Hua [1 ,2 ]
Guo, Huafang [1 ,2 ]
Tang, Zhihua [1 ,2 ]
Yu, Junyan [3 ]
Lu, Haiyang [4 ]
机构
[1] Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
[2] Guangdong Key Lab New & Renewable Energy Res & De, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
[3] Guangzhou Metro Grp Co Ltd, Tower A,Wansheng Sq,1238 Xingang East Rd, Guangzhou 510330, Guangdong, Peoples R China
[4] Guangdong Univ Technol, Sch Automated Inst, Waihuan West Rd, Guangzhou 5100006, Guangdong, Peoples R China
关键词
conventional and advanced exergy analyses; air-conditioning system; subway station; CARBON-DIOXIDE; ENERGY; DESTRUCTIONS; OPTIMIZATION; PLANT; CYCLE; HVAC;
D O I
10.1504/IJEX.2019.100365
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air-conditioning systems in subway stations consume a large amount of energy. In this study, conventional and advanced exergy analyses were carried out to determine the energy-saving potential of an air-conditioning system in a subway station. Results show that air handling unit (AHU) should be improved for the highest values of relative irreversibility (RI) with conventional exergy analysis, whereas the compressor should have the highest improvement priority for the largest avoidable exergy destruction with advanced exergy analysis. Moreover, influences of compressor efficiency, condensation temperature, and evaporation temperature on avoidable exergy destruction of the air-conditioning system were also investigated. According to the findings, compressor efficiency significantly influences the system's total avoidable exergy destruction. The lower the compressor efficiency, the more rapidly the avoidable exergy destruction of the compressor increases. Furthermore, the avoidable exergy destruction of condenser, compressor, cooling tower (CT), and cooling water pump (CWP) increases with the rise of the condensation temperature, whereas that of the evaporator, throttling valve (TV), condenser, compressor, CT, and CWP decreases with the rise of the evaporation temperature.
引用
收藏
页码:236 / 262
页数:27
相关论文
共 50 条
  • [41] Nonlinear predictive control for subway station air conditioning systems
    Wei D.
    Xiao Z.-M.
    An S.
    Xiong Y.-X.
    Kongzhi yu Juece/Control and Decision, 2024, 39 (02): : 509 - 518
  • [42] Load forecast and fuzzy control of the air-conditioning systems at the subway stations
    Bi, Haiquan
    Zhou, Yuanlong
    Liu, Jin
    Wang, Honglin
    Yu, Tao
    Journal of Building Engineering, 2022, 49
  • [43] Load forecast and fuzzy control of the air-conditioning systems at the subway stations
    Bi, Haiquan
    Zhou, Yuanlong
    Liu, Jin
    Wang, Honglin
    Yu, Tao
    JOURNAL OF BUILDING ENGINEERING, 2022, 49
  • [44] Conventional and Advanced Exergy Analyses of an Integrated LNG Regasification-Air Separation Process
    Hamayun, Muhammad Haris
    Ramzan, Naveed
    Hussain, Murid
    Faheem, Muhammad
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2022, 61 (07) : 2843 - 2853
  • [45] Exergy analysis of ice storage air-conditioning system with heat pipe during charging period
    Fang, Guiyin
    Liu, Xu
    ENERGY FOR SUSTAINABLE DEVELOPMENT, 2010, 14 (02) : 149 - 153
  • [46] Exergy analysis of a solar-assisted air-conditioning system: Case study in southern Spain
    Rosiek, S.
    APPLIED THERMAL ENGINEERING, 2019, 148 : 806 - 816
  • [47] Research on frequency conversion technology of metro station's ventilation and air-conditioning system
    Yang, Zhao
    Yu, Zhuangzhuang
    Yu, Longqing
    Ma, Feng
    APPLIED THERMAL ENGINEERING, 2014, 69 (1-2) : 123 - 129
  • [48] Exergonomic optimization of an air-conditioning system
    Cammarata, G
    Fichera, A
    Mammino, L
    Marletta, L
    JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 1997, 119 (01): : 62 - 69
  • [49] Exergy analysis of two humidification process methods in air-conditioning systems
    Ghazikhani, M.
    Khazaee, I.
    Vahidifar, S.
    ENERGY AND BUILDINGS, 2016, 124 : 129 - 140
  • [50] HYBRID SOLAR AIR-CONDITIONING SYSTEM
    COSTELLO, FA
    SOLAR ENERGY, 1976, 18 (02) : 149 - 152