Dehumidification performance of a variable speed heat pump and a single speed heat pump with and without dehumidification capabilities in a warm and humid climate

被引:9
|
作者
Kone, Koukouni P. [1 ]
Fumo, Nelson [1 ]
机构
[1] Univ Texas Tyler, Mech Engn Dept, Tyler, TX 75799 USA
关键词
Air humidity control; Residential air conditioning; Air dehumidification; Thermal comfort;
D O I
10.1016/j.egyr.2020.06.024
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Conventional air conditioning systems in houses respond to thermal loads by means of controlling dry-bulb temperature through the thermostat. As part of the process to control temperature, dehumidification is also provided. However, as houses are becoming more efficient, supplemental dehumidification is often necessary for homes located in hot and humid climates to control relative humidity intentionally. This study compared the dehumidification performance of a residential air conditioning system working in three operations modes to emulate three different systems: a system with a variable speed mode, a single-speed system with an enhanced dehumidification mode, and a single-speed system operating in a traditional or normal cooling mode. With operation mode changes achieved through software, this study constituted a novelty in the topic of humidity control by using a single machine, with the same exact physical set-up to directly compare the dehumidification performance of three types of systems. Two types of days were of interest in the study, hot and humid days (summer season) and mild and humid days (Fall shoulder season). After assessment of the dehumidification performance, the variable speed mode was able to maintain relative humidity between 50% to 52% on summer days. In the single-speed with enhanced dehumidification, a slightly less effective humidity control was achieved on summer days with the mode keeping the relative humidity between 53% to 55%. In the normal cooling mode, which resembles a conventional system, the humidity levels were controlled between 55% to 60%. In the shoulder season, the variable speed and enhanced dehumidification modes maintained the relative humidity between 55% to 58% and 53% to 56% respectively. In the shoulder season, the normal cooling mode kept the indoor relative humidity near or above 60%. In terms of dehumidification efficiency expressed as a function of the amount of water condensate per unit of energy, the variable speed was determined to be more efficient than the other modes. (C) 2020 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:1696 / 1701
页数:6
相关论文
共 50 条
  • [21] Investigating dehumidification and heating performance in a dual evaporator heat pump system for electric vehicles
    Li, Kang
    Tan, Mingfei
    Man, Yuan
    Zhang, Hua
    Dou, Binlin
    Liu, Ni
    Zhang, Tianjiao
    He, Qize
    Su, Lin
    Mohtaram, Soheil
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 168 : 620 - 631
  • [22] Research on Energy-Saving Experimental of Critical Dehumidification of Combined Drying by Dehumidification Wheel and Heat Pump
    Wang, Jiaoling
    Song, Weidong
    Jin, Chengqian
    Ding, Tianhang
    Wang, Mingyou
    Wu, Jinji
    JOURNAL OF FOOD QUALITY, 2021, 2021
  • [23] THE POTENTIAL FOR HEAT-PUMPS IN DRYING AND DEHUMIDIFICATION SYSTEMS .2. AN EXPERIMENTAL ASSESSMENT OF THE HEAT-PUMP CHARACTERISTICS OF A HEAT-PUMP DEHUMIDIFICATION SYSTEM USING R114
    TAI, KW
    ZYLLA, R
    DEVOTTA, S
    DIGGORY, PJ
    WATSON, FA
    HOLLAND, FA
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1982, 6 (04) : 323 - 331
  • [24] Modeling of a heat pump with evaporator air dehumidification for reduced frost formation
    Martínez-Frías, J
    Aceves, SM
    JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 1999, 121 (03): : 189 - 195
  • [25] COEFFICIENT OF PERFORMANCE FOR FINITE SPEED HEAT-PUMP
    BLANCHARD, CH
    JOURNAL OF APPLIED PHYSICS, 1980, 51 (05) : 2471 - 2472
  • [26] An investigation on dehumidification and heat transfer characteristics of a minichannel heat exchanger for heat pump system of electric vehicles
    Yu, Jun
    Su, Lin
    Li, Kang
    Fang, Yidong
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2022, 46 (13) : 18294 - 18311
  • [27] Experimental studies of semi hermetic single screw compressor with variable speed in heat pump
    Wen, Qiangyu
    Zhi, Ruiping
    Wu, Yuting
    Lei, Biao
    Ban, Guohong
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 58
  • [28] THE POTENTIAL FOR HEAT-PUMPS IN DRYING AND DEHUMIDIFICATION SYSTEMS .3. AN EXPERIMENTAL ASSESSMENT OF THE DEHUMIDIFICATION CHARACTERISTICS OF A HEAT-PUMP DEHUMIDIFICATION SYSTEM USING R114
    TAI, KW
    DEVOTTA, S
    WATSON, FA
    HOLLAND, FA
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1982, 6 (04) : 333 - 340
  • [29] Cooling Efficiency Comparison between Residential Variable Capacity and Single Speed Heat Pump
    Hunt, Walter
    Domitrovic, Ron
    Amarnath, Ammi
    2013 ASHRAE ANNUAL CONFERENCE, 2013,
  • [30] Performance evaluation of a heat pump-driven vacuum humidification-dehumidification desalination system
    Ayati, Emad
    Rahimi-Ahar, Zohreh
    Hatamipour, Mohammad Sadegh
    Ghalavand, Younes
    APPLIED THERMAL ENGINEERING, 2020, 180