Induced Voltages Ratio-Based Algorithm for Fault Detection, and Faulted Phase and Winding Identification of a Three-Winding Power Transformer

被引:15
|
作者
Lee, Byung Eun [1 ]
Park, Jung-Wook [2 ]
Crossley, Peter A. [3 ]
Kang, Yong Cheol [4 ]
机构
[1] Chonbuk Natl Univ, Wind Energy Grid Adapt Technol Res Ctr, Chonju 561756, South Korea
[2] Yonsei Univ, Sch Elect & Elect Engn, Seoul 120749, South Korea
[3] Univ Manchester, Sch Elect & Elect Engn, Manchester M13 9PL, Lancs, England
[4] Chonbuk Natl Univ, Dept Elect Engn, Wind Energy Grid Adapt Technol Res Ctr, Chonju 561756, South Korea
基金
新加坡国家研究基金会;
关键词
fault detection; faulted phase and winding identification; ratio of induced voltages; transformer protection; three-winding transformer; DIFFERENTIAL PROTECTION; CLASSIFICATION; RELAY;
D O I
10.3390/en7096031
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes an algorithm for fault detection, faulted phase and winding identification of a three-winding power transformer based on the induced voltages in the electrical power system. The ratio of the induced voltages of the primary-secondary, primary-tertiary and secondary-tertiary windings is the same as the corresponding turns ratio during normal operating conditions, magnetic inrush, and over-excitation. It differs from the turns ratio during an internal fault. For a single phase and a three-phase power transformer with wye-connected windings, the induced voltages of each pair of windings are estimated. For a three-phase power transformer with delta-connected windings, the induced voltage differences are estimated to use the line currents, because the delta winding currents are practically unavailable. Six detectors are suggested for fault detection. An additional three detectors and a rule for faulted phase and winding identification are presented as well. The proposed algorithm can not only detect an internal fault, but also identify the faulted phase and winding of a three-winding power transformer. The various test results with Electromagnetic Transients Program (EMTP)-generated data show that the proposed algorithm successfully discriminates internal faults from normal operating conditions including magnetic inrush and over-excitation. This paper concludes by implementing the algorithm into a prototype relay based on a digital signal processor.
引用
收藏
页码:6031 / 6049
页数:19
相关论文
共 50 条
  • [31] Distribution Transformer Winding Fault Detection Based on Hybrid Wavelet-CNN
    Afandi, Orkhan
    Najafi, Atabak
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2025, 2025 (01):
  • [32] The Fault Detection Method of Transformer Winding Oscillatory Wave Based on Discrete Wavelet
    Sun, Aoyang
    Xu, Xiaowei
    Liu, Hongwen
    Wang, Ke
    Zhou, Lijun
    Jiang, Feiming
    Lin, Tong
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1810 - 1814
  • [33] Performance and mathematical model of three-phase three-winding transformer used in 2 x 25 kV electric railway
    Mingli, W
    Chengshan, X
    Fan, Y
    Zheng, TQ
    IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 2006, 153 (02): : 271 - 281
  • [34] Decoupling Capacitor Minimization of an MMC-Based Photovoltaic System With Three-Winding Power Channel
    Pan, Xicai
    Pan, Shangzhi
    Jin, Pengxin
    Yao, Liangzhong
    Gong, Jinwu
    Liu, Fei
    Zha, Xiaoming
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (01) : 1012 - 1026
  • [35] A 0.2-V Three-Winding Transformer-Based DCO in 16-nm FinFET CMOS
    Li, Chao-Chieh
    Yuan, Min-Shueh
    Lin, Yu-Tso
    Liao, Chia-Chun
    Chang, Chih-Hsien
    Staszewski, Robert Bogdan
    IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS II-EXPRESS BRIEFS, 2020, 67 (12) : 2878 - 2882
  • [36] Transformer inter-turn winding fault detection based on no-load active power loss and reactive power
    Ehsanifar, Ali
    Allahbakhshi, Mehdi
    Tajdinian, Mohsen
    Dehghani, Mohammad
    Montazeri, Zeinab
    Malik, O. P.
    Guerrero, Josep M.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 130
  • [37] A Sensorless Control Algorithm for the Circular Winding Brushless DC Motor Based on Phase Voltages and DC Current Detection
    Jia, Zhewu
    Zhang, Qinghu
    Wang, Dong
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2021, 68 (10) : 9174 - 9184
  • [38] Study on Two-Winding Three-Phase Transformer Based on Matlab Sim Power System
    Wang Xin-jie
    Hu Ming-qin
    12TH ANNUAL MEETING OF CHINA ASSOCIATION FOR SCIENCE AND TECHNOLOGY ON INFORMATION AND COMMUNICATION TECHNOLOGY AND SMART GRID, 2010, : 108 - 110
  • [39] A Circulating Power Suppression Structure for Three-Winding-Transformer-Based Converter
    Yan, Zhixing
    Tang, Ting
    Yu, Zehui
    Chen, Run
    Lai, Zhen
    Ying, Gengning
    Yang, Ningrui
    Zeng, Jun
    Liu, Junfeng
    Hu, Renjun
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (08) : 8800 - 8804
  • [40] Stator Winding Fault Detection and Classification in Three-Phase Induction Motor
    Hussain, Majid
    Soother, Dileep Kumar
    Kalwar, Imtiaz Hussain
    Memon, Tayab Din
    Memon, Zubair Ahmed
    Nisar, Kashif
    Chowdhry, Bhawani Shankar
    INTELLIGENT AUTOMATION AND SOFT COMPUTING, 2021, 29 (03): : 869 - 883