Circuit Breaker Transient Recovery Voltage in Presence of Source Side Shunt Capacitor Bank

被引:0
|
作者
Kandakatla, Murali [1 ]
Rao, B. Kondala [1 ]
Gajjar, Gopal [1 ]
机构
[1] ABB Ltd, Vadodara, India
关键词
Arcing time; High frequency discharge current; Initial Transient Recovery Voltage (ITRV); Rate of Rise of Recovery Voltage (RRRV); Re-ignition; Restrike; Shunt capacitor bank; Transient Recovery Voltage (TRV);
D O I
暂无
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
Reactive power compensation through connection of shunt capacitor banks is a common practice in medium voltage systems. But the presence of capacitor bank leads to some interesting phenomena in switching transients. Clearing of a fault on line side of breaker in the presence of a source side capacitor bank is one such phenomenon. While clearing the fault if there is any re-ignition, presence of capacitor bank will develop high frequency discharge current that is superimposed on the power frequency fault current. Interruption of this high frequency current would cause considerable increase in the TRV magnitude. This paper describes the above phenomenon with PSCAD simulation results of a practical system. It also explains the effect of various parameters on the breaker TRV magnitude.
引用
收藏
页码:606 / 611
页数:6
相关论文
共 50 条
  • [31] A METHOD OF EVALUATING A CIRCUIT-BREAKER FOR A CAPACITOR BANK AND SUPPRESSION OF RESTRIKING OVERVOLTAGE
    NISHIKAWA, H
    YOKOKURA, K
    MASUDA, S
    OKAWA, M
    KOIKE, H
    KATO, T
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (06): : 1574 - 1581
  • [32] Effect of Circuit Breaker Shunt Resistance on Chaotic Ferroresonance in Voltage Transformer
    Radmanesh, Hamid
    Rostami, Mehrdad
    ADVANCES IN ELECTRICAL AND COMPUTER ENGINEERING, 2010, 10 (03) : 71 - 77
  • [33] Voltage ripple across the capacitor in DC side of shunt APF
    Yan, Zhaoyang
    Zhu, Guiping
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2012,
  • [34] AUTOTRANSFORMER CIRCUIT BREAKER TRANSIENT RECOVERY VOLTAGES ASSOCIATED WITH INTERRUPTING LOW VOLTAGE BUS FAULTS.
    Vietor, G.C.
    Ahrens, P.R.
    Harper, W.E.
    Engineering News-Record, 1981,
  • [35] EHV Shunt Capacitor Bank Design and Transient Analysis - A Case Study
    Wu, Xuan
    Andov, Kiril
    Leece, Benjamin B.
    Skidmore, Michael L.
    Louderback, Matthew R.
    Meisner, David J.
    Momme, Thomas E.
    Posey, Kenneth R.
    2021 IEEE/IAS 57TH INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE (I&CPS), 2021,
  • [36] Effect of Series Reactors on Circuit Breaker Transient Recovery Voltages
    Peelo, D. F.
    2014 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (IEEE PES APPEEC), 2014,
  • [37] Restrike Modeling of Vacuum Circuit Breaker switching off Shunt Capacitor Banks with EMTP
    Wang, Yongyuan
    Liu, Shenghui
    Liu, Wenze
    Wang, Keying
    MANUFACTURING SCIENCE AND TECHNOLOGY, PTS 1-8, 2012, 383-390 : 2287 - +
  • [38] An investigation of transient overvoltage generation when switching high voltage shunt reactors by SF6 circuit breaker
    Ma, Z
    Bliss, CA
    Penfold, AR
    Harris, AFW
    Tennakoon, SB
    IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) : 472 - 479
  • [39] Diagnostics of Low Voltage Circuit Breaker with Impulse Current Source
    Kacor, Petr
    PROCEEDINGS OF THE 10TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2009, 2009, : 328 - 331
  • [40] Application of Circuit Breaker Switching Capacitor Bank with Phase Selection in UHV Transmission Project
    Li, Zhibing
    Yan, Xianglian
    Liu, Beiyang
    Wang, Hao
    Han, Bin
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014, : 1178 - 1181