Numerical investigation of hot air recirculation of air-cooled condensers at a large power plant

被引:69
|
作者
Liu, Peiqing [1 ]
Duan, Huishen [1 ]
Zhao, Wanli [1 ]
机构
[1] Beijing Univ Aeronaut & Astronaut, Dept Aviat Sci & Engn, Key Lab Fluid Mech Educ Minist, Beijing 100191, Peoples R China
关键词
Hot air recirculation; Air-cooled condenser; Hot recirculation rate; WIND-TUNNEL SIMULATION; FAN PERFORMANCE; HEAT-EXCHANGERS;
D O I
10.1016/j.applthermaleng.2008.09.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to minimize the hot air recirculation (HAR) to ensure normal operation of the air-cooled condensers (ACC) system, the hot air recirculation phenomenon and its dependence on ambient winds are numerically simulated by using the computational fluid dynamics code, FLUENT. Under the constant ambient temperature, the effects of different wind speed and wind direction on the HAR are qualitatively considered by applying the concept of the hot recirculation rate (HRR). The mechanism of occurrence of hot air recirculation are presented and analyzed. It was found that when considering about the existing and normally operating power plants, the HAR is more sensitive to wind direction and wind speed. Based on the above results, two improved measures increasing the wind-wall height and accelerating the rotational speed of the fans near the edge of the ACC platform are developed to effectively reduce the hot air recirculation. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1927 / 1934
页数:8
相关论文
共 50 条
  • [41] Numerical Investigation on Performance of Air-cooled BLDC Motor
    Kwon, Hwabhin
    Lee, Won-Sik
    Kim, Gyu-Tak
    Park, Heesung
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2018, 42 (10) : 681 - 687
  • [42] PROFIT FROM LATEST EXPERIENCE WITH AIR-COOLED CONDENSERS
    SWANEKAMP, R
    POWER, 1994, 138 (06) : 78 - &
  • [43] COMPARISON WITH RESPECT TO ECONOMY AND TECHNIQUE OF AIR-COOLED CONDENSERS
    CLEVE, HHV
    KALTE UND KLIMATECHNIK, 1977, 30 (06): : 218 - &
  • [44] Effect of circuit arrangement on the performance of air-cooled condensers
    Wang, CC
    Jang, JY
    Lai, CC
    Chang, YJ
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (04): : 275 - 282
  • [45] Mathematical models of air-cooled condensers for thermoelectric units
    Bracco, S.
    Caligaris, O.
    Trucco, A.
    ENERGY AND SUSTAINABILITY II, 2009, 121 : 389 - +
  • [46] Experimental investigation on thermal flow field characteristics of a direct air-cooled system for a large power plant
    Zhao, Wanli
    Liu, Peiqing
    Yingyong Jichu yu Gongcheng Kexue Xuebao/Journal of Basic Science and Engineering, 2009, 17 (04): : 605 - 613
  • [47] Impact of shading air-cooled condensers on the efficiency of air-conditioning systems
    ElSherbini, A. I.
    Maheshwari, G. P.
    ENERGY AND BUILDINGS, 2010, 42 (10) : 1948 - 1951
  • [48] Challenges in predicting steam-side pressure drop and heat transfer in air-cooled power plant condensers
    Mahvi, Allison J.
    Rattner, Alexander S.
    Lin, Jennifer
    Garimella, Srinivas
    APPLIED THERMAL ENGINEERING, 2018, 133 : 396 - 406
  • [49] Numerical and and wind tunnel investigation of Hot Air Recirculation across Liquefied Natural Gas Air Cooled Heat Exchangers
    Ghani, Saud
    Gamaledin, Seifelislam Mahmoud Ahmad
    Bakochristou, Foteini
    El-Bialy, Esmail
    Mohamed, Mohamed Mostafa
    Elsawi, Rodina Mohamed El Hassan
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2018, 172 : 409 - 422
  • [50] Wind effect on the thermo-flow performances and its decay characteristics for air-cooled condensers in a power plant
    Yang, L. J.
    Du, X. Z.
    Yang, Y. P.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2012, 53 : 175 - 187