Numerical investigation of hot air recirculation of air-cooled condensers at a large power plant

被引:69
|
作者
Liu, Peiqing [1 ]
Duan, Huishen [1 ]
Zhao, Wanli [1 ]
机构
[1] Beijing Univ Aeronaut & Astronaut, Dept Aviat Sci & Engn, Key Lab Fluid Mech Educ Minist, Beijing 100191, Peoples R China
关键词
Hot air recirculation; Air-cooled condenser; Hot recirculation rate; WIND-TUNNEL SIMULATION; FAN PERFORMANCE; HEAT-EXCHANGERS;
D O I
10.1016/j.applthermaleng.2008.09.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to minimize the hot air recirculation (HAR) to ensure normal operation of the air-cooled condensers (ACC) system, the hot air recirculation phenomenon and its dependence on ambient winds are numerically simulated by using the computational fluid dynamics code, FLUENT. Under the constant ambient temperature, the effects of different wind speed and wind direction on the HAR are qualitatively considered by applying the concept of the hot recirculation rate (HRR). The mechanism of occurrence of hot air recirculation are presented and analyzed. It was found that when considering about the existing and normally operating power plants, the HAR is more sensitive to wind direction and wind speed. Based on the above results, two improved measures increasing the wind-wall height and accelerating the rotational speed of the fans near the edge of the ACC platform are developed to effectively reduce the hot air recirculation. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1927 / 1934
页数:8
相关论文
共 50 条
  • [31] Porous Medium Modeling of Air-Cooled Condensers
    K. Hooman
    H. Gurgenci
    Transport in Porous Media, 2010, 84 : 257 - 273
  • [32] Research on the structure optimization of air-cooled condensers
    Zhou, Yu
    Dong, Xiaorui
    Cheng, Youliang
    Hu, Hongkuan
    ENERGY SCIENCE AND APPLIED TECHNOLOGY (ESAT 2016), 2016, : 397 - 400
  • [33] DESIGN AND SPECIFICATION OF AIR-COOLED STEAM CONDENSERS
    LARINOFF, MW
    MOLES, WE
    REICHHELM, R
    CHEMICAL ENGINEERING, 1978, 85 (12) : 86 - 94
  • [34] FAN PERFORMANCE IN AIR-COOLED STEAM CONDENSERS
    KROGER, DG
    HEAT RECOVERY SYSTEMS & CHP, 1994, 14 (04): : 391 - 399
  • [35] Porous Medium Modeling of Air-Cooled Condensers
    Hooman, K.
    Gurgenci, H.
    TRANSPORT IN POROUS MEDIA, 2010, 84 (02) : 257 - 273
  • [36] Trapezoidal array of air-cooled condensers to restrain the adverse impacts of ambient winds in a power plant
    Yang, L. J.
    Wang, M. H.
    Du, X. Z.
    Yang, Y. P.
    APPLIED ENERGY, 2012, 99 : 402 - 413
  • [37] Cooling Performance Enhancement of Air-Cooled Condensers by Guiding Air Flow
    Huang, Xianwei
    Chen, Lin
    Yang, Lijun
    Du, Xiaoze
    Yang, Yongping
    ENERGIES, 2019, 12 (18)
  • [38] A favorable face velocity distribution and a V-frame cell for power plant air-cooled condensers
    Zhang, Zhaoying
    Yang, Jianguo
    Wang, Yanyan
    APPLIED THERMAL ENGINEERING, 2015, 87 : 1 - 9
  • [39] Air-cooled condensers cut tower water plume
    Chambers, A
    POWER ENGINEERING, 1998, 102 (08) : 58 - 58
  • [40] SPECIFYING BETTER-PERFORMING AIR-COOLED CONDENSERS
    LARINOFF, MW
    POWER ENGINEERING, 1994, 98 (10) : 37 - 39