Influence of Fault Locations on the Pipeline Induced Voltages Near to Power Transmission Lines

被引:0
|
作者
Abdel-Gawad, Nagat M. K. [1 ]
Shaalan, Essam M. [1 ]
Darwish, M. M. F. [1 ]
Basuny, Mahmoud A. M. [2 ]
机构
[1] Shoubra Benha Univ, Fac Engn, Dept Elect Power & Machines Engn, Cairo, Egypt
[2] Egyptian Cairo Metro, Dept Signaling & Maintenance, Cairo, Egypt
关键词
Electromagnetic Interference; Fault location; Induced voltage; Inductive coupling; Pipelines;
D O I
10.1109/mepcon47431.2019.9008020
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, the simulation induced voltages along the buried pipeline due to normal operating condition as well as symmetric and un-symmetric fault conditions of the power transmission lines are calculated. By using the ATP program and MATLAB software, to simulate the power line-pipeline system under all fault conditions, the simulation results of induced voltages are obtained then compared with the actual measurement values. Moreover, the influence of fault locations, either in the first quarter or in the middle place of the power line, on the pipeline induced voltages is studied. Furthermore, the variation of soil resistivity on the pipeline induced voltages under normal and fault conditions is analyzed. It is found that El-Kurimate power line is the most effective power line on the pipeline at normal operating condition. Also, it is seen that a good agreement between the experimental and simulation results of induced voltages, under normal condition, is achieved. Moreover, the simulation results show that the most serious type of abnormal conditions on the pipeline itself and its coating is the single line to ground fault when it occurs at the first quarter of the transmission line. Finally, it is concluded that soil resistivity variation has a great effect on the pipeline induced voltage under fault conditions.
引用
收藏
页码:761 / 767
页数:7
相关论文
共 50 条
  • [31] Transient induced voltages on aboveground pipelines parallel to overhead transmission lines
    Papadopoulos, T. A.
    Datsios, Z. G.
    Chrysochos, A. I.
    Martins-Britto, A. G.
    Papagiannis, G. K.
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 223
  • [32] New algorithm for fault location in power transmission lines
    Sadeh, J.
    Ranjbar, A.M.
    Proceedings of the American Power Conference, 61-1 : 458 - 462
  • [33] New algorithm for fault location in power transmission lines
    Sadeh, J.
    Ranjbar, A.M.
    Proceedings of the American Power Conference, 1999, 61
  • [34] A new algorithm for fault location in power transmission lines
    Sadeh, J
    Ranjbar, AM
    PROCEEDINGS OF THE AMERICAN POWER CONFERENCE, VOL 61 - I AND II, 1999, 61 : 458 - 462
  • [35] Accurate fault location algorithm for power transmission lines
    Sadeh, J
    Ranjbar, AM
    Hadjsaid, N
    Feuillet, R
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2000, 10 (05): : 313 - 318
  • [36] Enhancing fault location performance on power transmission lines
    Bockarjova, Marija
    Dolgicers, Aleksandrs
    Sauhats, Antans
    2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, : 1123 - +
  • [37] Fault diagnosis system for tapped power transmission lines
    Mohamed, E. A.
    Talaat, H. A.
    Khamis, E. A.
    ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (05) : 599 - 613
  • [38] Lightning-Induced Voltages on Overhead Power Lines with the Use of the Hybrid Method: Influence of the Shielding Wire
    M'Ziou, Nassima
    Mokhnache, Leila
    Boubakeur, Ahmed
    Kattan, Rafic
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (03): : 57 - 60
  • [39] Influence of Lossy Ground on High-Frequency Induced Voltages on Aboveground Pipelines by Nearby Overhead Transmission Lines
    Martins-Britto, Amauri G.
    Papadopoulos, Theofilos A.
    Datsios, Zacharias G.
    Chrysochos, Andreas, I
    Papagiannis, Grigoris K.
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2022, 64 (06) : 2273 - 2282
  • [40] A fault effect to induced voltage of gas pipeline in transmission systems
    Kim, Hyun-Soo
    Rhee, Sang-Bong
    Kim, Chul-Hwan
    Transactions of the Korean Institute of Electrical Engineers, 2008, 57 (10): : 1720 - 1725