Energy and exergy analysis of a ground source heat pump system with a slinky ground heat exchanger supported by nanofluid

被引:15
|
作者
Kapicioglu, Abdullah [1 ]
机构
[1] Sivas Cumhuriyet Univ, Fac Technol, Dept Mfg Engn, Sivas, Turkey
关键词
Aluminum oxide nanofluid; Horizontal ground source heat pump; Slinky ground heat exchanger; Energy analysis; Exergy analysis; AL2O3; NANOFLUID; TRANSFER ENHANCEMENT; THERMAL PERFORMANCE; BUILDINGS;
D O I
10.1007/s10973-020-10498-0
中图分类号
O414.1 [热力学];
学科分类号
摘要
This work contains the experimental analysis results in real environment conditions of the use of Al2O3-based nanofluid (NF) at different concentration ratios (0.1% and 0.2%) in a ground source heat pump (GSHP) system with a slinky ground heat exchanger (GHE). The energetic and exergic efficiencies of the system were investigated with the data obtained from the experimental results of base fluid (ethylene glycol (EG)-water) (EG volumetric ratio 25%) and NF with Al2O3 concentration ratios of 0.1% and 0.2%. The exergetic model is obtained by applying energy and exergy equations for each system component. Exergetic efficiencies of the system components are evaluated separately and their potential for improvement is presented. According to the results of the energetic analysis, the overall system's coefficient of performance (COP) values for the base fluid and NF with concentration ratios of 0.1% and 0.2% were 4.30, 4.38 and 4.34, respectively. These results show that NF contributes to system performance. However, an increase in system performance was not achieved due to the increase in NF concentration; on the contrary, a decrease in performance was observed. Exergetic efficiencies of the system for base fluid and NF with concentration ratios of 0.1% and 0.2% were 88.3%, 89.7% and 89.0%, respectively, for the heat pump unit, while these values were 78.7%, 79.3% and 79.0% for the entire system, respectively. The results show that the usage of NF with low concentration ratios increases the energetic and exergic efficiency of the system.
引用
收藏
页码:1455 / 1468
页数:14
相关论文
共 50 条
  • [21] Influence of hydration heat on heat transfer effect of ground heat exchanger of ground source heat pump in summer
    Xia, Caichu
    Liu, Zhifang
    Xiao, Suguang
    Huang, Man
    Tongji Daxue Xuebao/Journal of Tongji University, 2015, 43 (09): : 1332 - 1338
  • [22] Using a capillary mat as a shallow heat exchanger for a ground source heat pump system
    Widiatmojo, Arif
    Gaurav, Shrestha
    Ishihara, Takeshi
    Yasukawa, Kasumi
    Uchida, Youhei
    Yoshioka, Mayumi
    Tomigashi, Akira
    ENERGY AND BUILDINGS, 2020, 209
  • [23] Determination of the ground source heat pump system capacity that ensures the longevity of a specified ground heat exchanger field
    Nguyen, A.
    RENEWABLE ENERGY, 2021, 169 : 799 - 808
  • [24] Development of a Horizontal Slinky Ground Heat Exchanger Model
    Xiong, Zeyu
    Lee, Edwin S.
    Fisher, Daniel E.
    2013 ASHRAE ANNUAL CONFERENCE, 2013,
  • [25] Performance study of heat pipe heat exchanger for ground source heat pump
    Hsieh, Jui Ching
    Lin, David T.W.
    Shin, Long Der
    1600, Chinese Mechanical Engineering Society (35): : 165 - 170
  • [26] TEMPERATURE PROCESS OF GROUND MASSIF WITH SLINKY HEAT EXCHANGER
    Sed'ova, Michaela
    Sterbova, Zuzana
    TRENDS IN AGRICULTURAL ENGINEERING 2013, 2013, : 577 - 580
  • [27] Comparison of energy and exergy analysis of fossil plant, ground and air source heat pump building heating system
    Lohani, S. P.
    Schmidt, D.
    RENEWABLE ENERGY, 2010, 35 (06) : 1275 - 1282
  • [28] Energy performance of a dual air and ground source heat pump coupled with a Flat-Panel ground heat exchanger
    Bottarelli, Michele
    Zhang, Li
    Bortoloni, Marco
    Su, Yuehong
    BULGARIAN CHEMICAL COMMUNICATIONS, 2016, 48 : 64 - 70
  • [29] INFLUENCE FACTORS ANALYSIS ON HEAT TRANSFER PERFORMANCE OF UNDERGROUND HEAT EXCHANGER IN GROUND-SOURCE HEAT PUMP SYSTEM
    Wu, X. Y.
    Dai, X. L.
    Yang, J. C.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 811 - 817
  • [30] Theoretical analysis on ground source heat pump and air source heat pump systems by the concepts of cool and warm exergy
    Li, Rongling
    Ooka, Ryozo
    Shukuya, Masanori
    ENERGY AND BUILDINGS, 2014, 75 : 447 - 455