On-line Turn-to-Turn Protection Method of the Synchronous Machines Field Winding

被引:0
|
作者
Tian, Pengfei [1 ]
Platero, Carlos A. [1 ]
Gyftakis, Konstantinos N. [2 ]
机构
[1] Univ Politecn Madrid, Dept Elect Engn, Escuela Tecn Super Ingn Ind, Madrid 28006, Spain
[2] Univ Edinburgh, Sch Engn, Edinburgh, Midlothian, Scotland
关键词
Condition monitoring; Power generation protection; Synchronous generator; Turn-to-turn fault;
D O I
10.1109/demped.2019.8864853
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Turn-to-turn faults are quite common in the synchronous generator field winding, especially in the turbo-generator types. This condition may be caused by either the double- ground fault of the winding or by a lack of insulation between adjacent turns. This paper presents a new on-line protection method for turn-to-turn faults in field windings of synchronous machines with static excitation system. The proposed method is based on the comparison of the measured excitation current with the theoretical excitation current calculated from the stator voltages and currents for the actual operation point. The method has been validated by experimental results using a special laboratory synchronous machine.
引用
收藏
页码:69 / 74
页数:6
相关论文
共 50 条
  • [31] Experience With Hydro-Generator Turn-to-Turn Insulation Fault, Investigation, and Recommendation for New Stator Winding Design and Protection
    Hong, Wenli
    Arshad, Muhammud
    2018 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2018, : 459 - 464
  • [33] Discussion on way of connection to neutral point and turn-to-turn fault protection for stator winding of large turbo-generator
    Fu, Ziqing
    Chen, Wenxue
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2000, 24 (09): : 63 - 66
  • [34] Analysis of Turn-to-Turn Fault on Split-Winding Transformer Using Coupled Field-Circuit Approach
    Yang, Cunxiang
    Ding, Yiwei
    Qiu, Hongbo
    Xiong, Bin
    PROCESSES, 2021, 9 (08)
  • [35] New Principle of Protection Scheme Based on Fundamental Component of Control Winding Currents Against Turn-to-turn Fault of MCSR
    Zheng T.
    Liu X.
    Dianwang Jishu/Power System Technology, 2019, 43 (08): : 3016 - 3024
  • [36] Turn-to-Turn Short Circuit Fault Localization in Transformer Winding via Image Processing and Deep Learning Method
    Moradzadeh, Arash
    Moayyed, Hamed
    Mohammadi-Ivatloo, Behnam
    Gharehpetian, G. B.
    Aguiar, A. Pedro
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2022, 18 (07) : 4417 - 4426
  • [37] Research on the Effect of Lightning Oscillatory Wave to Transformer Winding Turn-to-turn Insulation Fault
    Quan, Yusheng
    Yi, Bo
    Chen, Guang
    Ning, Zisen
    ENERGY AND POWER TECHNOLOGY, PTS 1 AND 2, 2013, 805-806 : 855 - +
  • [38] Effects of turn to turn stator winding faults in synchronous generators
    Klocke, Meinolf
    Rosendahl, Jens
    PROCEEDINGS OF THE 10TH INTERNATIONAL CONFERENCE ON OPTIMIZATION OF ELECTRICAL AND ELECTRONIC EQUIPMENT, VOL II: POWER ELECTRONICS, ELECTRICAL MACHINES & DRIVERS, 2006, : 55 - 62
  • [39] Flux-based turn-to-turn fault protection for power transformers
    Mostafaei, Mohsen
    Haghjoo, Farhad
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (05) : 1154 - 1163
  • [40] Novel Technique for Location Identification and Estimation of Extent of Turn-to-Turn Fault in Transformer Winding
    Kumar, Abhishek
    Bhalja, Bhavesh R.
    Kumbhar, Ganesh B.
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2023, 70 (07) : 7382 - 7392