Partial discharge, dissipation factor, and corona aspects for high voltage electric generator stator bars and windings

被引:20
|
作者
Emery, FT [1 ]
机构
[1] Siemens Westinghouse Power Corp, Charlotte, NC 28273 USA
关键词
partial discharge; corona; high voltage generators; power factor; electrical insulation;
D O I
10.1109/TDEI.2005.1430403
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High voltage stator windings in modern electric generators are subject to high electrical, mechanical, and thermal stress. Operation of these machines in both air and high pressure hydrogen results in different considerations. Operation in the air environment does not offer the dielectric advantages of operating in high-pressure hydrogen. The two major design factors that are significant for the design of high voltage stator bars to be operated in air, are corona activity and PD activity. These of course are closely related. With the movement to increasing the power density of generators, which means operation at higher voltages and higher insulation stress levels, it has become more critical to be sure the design constraints are met in the stator bar design to minimize both partial discharge activity and corona activity involving the stator bars. The stator bar insulation system must be designed for minimum partial discharge activity and ideally is corona free at the stator winding operating stress levels, and at the operating conditions (temperature and pressure) the generator is subject to. This paper will present the findings associated with the development work in designing, testing and implementing a PD reduced and corona free design.
引用
收藏
页码:347 / 361
页数:15
相关论文
共 50 条
  • [31] Locating Partial Discharge Sources in High Voltage Transformer Windings
    Lewin, P. L.
    Golosnoy, I. O.
    Mohamed, R.
    2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 196 - 200
  • [32] Partial discharge detection in generator stator insulation using oscillating voltage waves
    Gulski, E
    van Breen, HJ
    Smit, JJ
    Seitz, PN
    Schikarski, P
    ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING & COIL WINDING CONFERENCE, PROCEEDINGS, 2001, : 331 - 334
  • [33] Analysis of localized dissipation factor measurements on the insulation system of mechanically aged generator stator bars
    Cimino, Alessandro
    Foelting, Christian
    Jenau, Frank
    Staubach, Christian
    2016 IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD), VOLS 1-2, 2016, : 674 - 677
  • [34] Partial Discharge Detection with High-Frequency Band through Resistance-Temperature Sensor of Hydropower Generator Stator Windings
    Kanegami, Masaki
    Miyazaki, Satoru
    Miyake, Katsuyuki
    ELECTRICAL ENGINEERING IN JAPAN, 2016, 195 (04) : 9 - 15
  • [35] Investigation Regarding Corona Free Endwinding Design of Form Wound High Voltage Stator Windings
    Lerchbacher, M.
    Imamovic, D.
    Lemesch, G.
    Ramsauer, F.
    Muhr, M.
    2010 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTIC PHENOMENA, 2010,
  • [36] Investigation regarding corona free endwinding design of form wound high voltage stator windings
    Graz University of Technology, Institute of High Voltage Engineering and System Management, Austria
    不详
    Annu. Rep. Conf. Electr. Insul. Dielectr. Phenom. CEIDP, 2010,
  • [37] Identification of Multiple Partial Discharge Sources in High Voltage Transformer Windings
    Ali, N. H. Nik
    Hunter, J. A.
    Rapisarda, P.
    Lewint, P. L.
    2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 188 - 191
  • [38] Investigation of Partial Discharges at the High Voltage Electric Motor Bars
    Dauksys, Gediminas
    Jonaitis, Audrius
    Gudzius, Saulius
    Morkvenas, Alfonsas
    ELEKTRONIKA IR ELEKTROTECHNIKA, 2016, 22 (02) : 9 - 12
  • [39] Relative Ability of UHF Antenna and VHF Capacitor Methods to Detect Partial Discharge in Turbine Generator Stator Windings
    Stone, G. C.
    Chan, C.
    Sedding, H. G.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (06) : 3069 - 3078
  • [40] Partial Discharge Influence on Dissipation Factor Values During Stator-Bar Testing
    Contin, Alfredo
    Zhu, Hugh
    IEEE ELECTRICAL INSULATION MAGAZINE, 2011, 27 (06) : 8 - 14