Analysis of localized dissipation factor measurements on the insulation system of mechanically aged generator stator bars

被引:0
|
作者
Cimino, Alessandro [1 ]
Foelting, Christian [1 ]
Jenau, Frank [1 ]
Staubach, Christian [2 ]
机构
[1] TU Dortmund Univ, Inst High Voltage Engn, Dortmund, Germany
[2] Siemens AG, Siemens AG Power & Gas, Mulheim, Germany
关键词
generator stator bar; insulation; multifactor aging; cracking; dissipation factor;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Integration of decentralised renewable energy sources lead to an increasingly fluctuating load profile of power engineering equipment. In particular, on large rotating machines this changing load profiles continuously stress the insulation in form of mechanical and thermo-mechanical forces. Eventually, a mechanical overstressing can ultimately result in an electrical breakdown of the insulation. To evaluate the condition of electrical insulation systems the knowledge of predominant aging mechanisms is of particular importance. This paper presents accelerated multi-factor aging tests with simultaneous mechanical and thermal loads on generator stator bars. Localized dissipation factor measurements as well as partial discharge detection are performed between aging cycles. An interrelationship between mechanical stress and the results of experimental examinations is indicated and analyzed. It can be shown, that mechanical stress can lead to cracking of the insulation, which is verified by the use of computer tomography.
引用
收藏
页码:674 / 677
页数:4
相关论文
共 50 条
  • [1] Diagnosis of Generator Stator Winding Insulation Based on Dissipation Factor Measurement
    Liu, Fei
    Huang, Xingyi
    Jiang, Pingkai
    PROCEEDINGS OF 2014 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM 2014), 2014, : 120 - 123
  • [2] Insulation resistance measurements versus temperature made on aged stator bars and coils
    Zhu, H.
    2007 ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING EXPO, 2007, : 215 - 218
  • [3] Unidirectional Accelerated Lifetime Investigations of Mechanically Dominated Aged Electrical Insulation System used in Generator Winding Bars
    Cimino, Alessandro
    Jenau, Frank
    Mashkin, Andrey
    Behnisch, Daniel
    Merte, Ralf
    Steins, Hendrik
    Pohlmann, Friedhelm
    2019 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2019, : 164 - 167
  • [4] Study on Insulation of Stator Bars from a Hydro Generator
    Garoarsdottir, Alexandra Dilja
    Edin, Hans
    2023 IEEE ELECTRICAL INSULATION CONFERENCE, EIC, 2023,
  • [5] Analysis of accelerated multi-factor aging tests on the winding insulation system of generator stator bars used in large rotating machines
    Cimino, Alessandro
    Staubach, Christian
    Jenau, Frank
    2018 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2018, : 110 - 113
  • [6] Dielectric Dissipation factor measurements on stator insulation - results from a global survey
    Krieg-Wezelenburg, M. G.
    2020 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2020, : 269 - 273
  • [7] Study of aging characteristics of generator stator insulation based on temperature spectrum of dielectric dissipation factor
    Ma, XQ
    Ma, XW
    You, B
    Lu, WS
    Xie, HK
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 294 - 297
  • [8] Temperature Dependence of Insulation Resistance and Current Components for Generator Stator Bars
    Suzuki, Kyohei
    Sako, Hiroshi
    Maeda, Susumu
    Mio, Koji
    2016 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2016, : 452 - 455
  • [9] Partial discharge, dissipation factor, and corona aspects for high voltage electric generator stator bars and windings
    Emery, FT
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2005, 12 (02) : 347 - 361
  • [10] Analysis of in-service aged stator bars
    Morin, R
    Novak, JP
    Bartnikas, R
    Ross, R
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 1995, 10 (04) : 645 - 654