A frost-free dedicated outdoor air system with exhaust air heat recovery

被引:41
|
作者
Zhang, Zi-Yang [1 ]
Zhang, Chun-Lu [1 ]
Ge, Mei-Cai [2 ]
Yu, Yue [2 ]
机构
[1] Tongji Univ, Sch Mech Engn, Inst Refrigerat & Cryogen, Shanghai 201804, Peoples R China
[2] Nantong Huaxin Cent Air Conditioning CO LTD, Nantong 226014, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
Dedicated outdoor air system; Heat pump; Exhaust air heat recovery; Frost-free; PERFORMANCE EVALUATION; ENERGY PERFORMANCE; LIQUID DESICCANT; OFFICE BUILDINGS; COOLING SYSTEM; EXCHANGERS; FLOW; PUMP; EFFICIENCY; TUBES;
D O I
10.1016/j.applthermaleng.2017.09.091
中图分类号
O414.1 [热力学];
学科分类号
摘要
DOAS (dedicated outdoor air system) has drawn much attention recently. However, it is quite energy intensive resulted from the big temperature and/or humidity difference between outdoor air and supply air. This paper proposed a new DOAS with exhaust air heat recovery. In cooling mode, there are one evaporator and three condensers in parallel. The outdoor air is cooled and dehumidified by the evaporator. Besides the outdoor condenser, another two are used for supply air reheat and exhaust air heat recovery. In heating mode, the reheat coil is off and two evaporators work for exhaust air heat recovery and ambient heat absorption, respectively. A pressure regulating valve equipped on the indoor evaporator keeps proper evaporating temperature for a frost-free operation. A validated model is applied to fulfill the system design and performance prediction. The results showed that the system cooling COP reaches 3.3 at ambient temperature 35 degrees C/28 degrees C and the heating COP achieves 4.8 at ambient temperature 7 degrees C/6 degrees C, respectively. In winter the proposed system can maintain the desired supply temperature and keep both evaporators frost-free (ambient temperature -20 degrees C to 10 degrees C). The proposed system can efficiently recover waste energy from exhaust air in the whole year and has the extensive applicability, especially in the cold climate where considerable energy savings can be found. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1041 / 1050
页数:10
相关论文
共 50 条
  • [22] Heat recovery from dryer exhaust air
    Krokida, MK
    Bisharat, GI
    DRYING TECHNOLOGY, 2004, 22 (07) : 1661 - 1674
  • [23] EXHAUST AIR HEAT RECOVERY IN PRACTICE.
    Railio, Jorma
    Batiment international, Building research & practice, 1984, 12 (05): : 294 - 298
  • [24] Research on exhaust air heat recovery mode of air conditioning system in different types of buildings
    Chen Aoxue
    PROCEEDINGS OF THE 2017 6TH INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENTAL PROTECTION (ICEEP 2017), 2017, 143 : 1469 - 1473
  • [25] Trends in the frost-free season with parallel circulation and air mass statistics in Poland
    Bielec-Bakowska, Zuzanna
    Piotrowicz, Katarzyna
    Krepa-Adolf, Ewa
    IDOJARAS, 2018, 122 (04): : 375 - 392
  • [26] ANALYSIS OF THE EFFECTIVENESS OF A THERMOSIPHON SYSTEM IN RECOVERY OF THE HEAT OF EXHAUST AIR.
    Fert, A.R.
    Chekhovskaya, N.I.
    Grebenyuk, A.V.
    Heat transfer. Soviet research, 1988, 20 (01): : 112 - 118
  • [27] Performance analysis and comparison of five solution regeneration methods for frost-free air-source heat pump
    Zhu, Liutao
    Wang, Libo
    Ling, Yunzhi
    Gao, Enyuan
    Ma, Yuxin
    Qu, Hongshuo
    Chen, Meng
    Zhang, Xiaosong
    Huang, Shifang
    JOURNAL OF BUILDING ENGINEERING, 2025, 99
  • [28] Dedicated outdoor air systems
    Dieckmann, J
    Roth, KW
    Brodrick, J
    ASHRAE JOURNAL, 2003, 45 (03) : 58 - 59
  • [29] Modelica-based modeling and simulation of a novel dedicated outdoor air-conditioning system with double heat recovery
    Chen, Sihao
    Zhou, Xiaoqing
    Yang, Yi
    Li, Jing
    Zhao, Shiqi
    Li, Jiangbo
    JOURNAL OF BUILDING ENGINEERING, 2025, 99
  • [30] A novel packaged outdoor air dehumidifier with exhaust air heat pump Experiment and simulation
    Cao, Xiang
    Yang, Chen
    Sun, Zhao
    Lu, Yue-Ming
    Chang, Meng-Meng
    Shao, Liang-Liang
    Zhang, Chun-Lu
    APPLIED THERMAL ENGINEERING, 2020, 181