Experimental investigation of a novel multi-channel flat plate liquid desiccant dehumidification system

被引:7
|
作者
Sharma, Akash [1 ]
Kaushal, Rajneesh [1 ]
机构
[1] Natl Inst Technol, Dept Mech Engn, Kurukshetra 136119, Haryana, India
关键词
Liquid desiccant; dehumidification; regeneration; effectiveness; moisture absorption rates; AIR-CONDITIONING SYSTEM; NATURAL-GAS DEHYDRATION; MASS-TRANSFER; PERFORMANCE ANALYSIS; PARAMETRIC ANALYSIS; DEHUMIDIFIER/REGENERATOR; LITHIUM;
D O I
10.1080/15567036.2020.1789243
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The continuously growing energy demands for space air conditioning and depletion of conventional energy resources at a fast rate have propagated the need for producing a new and wide range of renewable and sustainable energy technologies. Liquid desiccant dehumidification technologies are the most optimistic approach due to their lower regeneration temperature required, a higher coefficient of performance, and the ability to be used during night hours. The factors responsible for the limited application of these systems are desiccant leakage, corrosion to the fabricating material, and carryover of desiccant droplets with the process air. To overcome these issues, a new multi-channel flat plate liquid desiccant air conditioning system has been developed and experimentally investigated. The performance of the system has been analyzed for the dehumidification and regeneration process. Calcium chloride has been used as a desiccant material with 40% and 35% by wt. concentration. Three sets of velocities of process air have been utilized, i.e., 0.9, 0.7, 0.5 m/s to investigate the system performance. Performance parameters, such as dehumidification rate, regeneration rate, dehumidification, and regeneration effectiveness, have been investigated in the present study. The liquid desiccant dehumidification system investigated in the present study includes a flat plate energy exchanger for heat and mass transfer between ambient moist air and liquid desiccant solution. This system conveys a large interfacial surface area between liquid desiccant solution and process air. Experimental results indicate that, in the dehumidification process, the ambient moist air has been dehumidified and cooled by 5.90 g kg(-1)and 1.4 degrees C, respectively, and dehumidification effectiveness of 0.239 has been achieved for the air velocity of 5 m/s at 40% concentration of the desiccant solution. Regeneration rate and effectiveness have been observed to be 0.014 g s(-1)and 0.323, respectively, for the air velocity of 5 m/s at 35% concentration. The work presented in this study demonstrates the feasibility of the novel multi-layer flat plat liquid desiccant concept and provide growth and development to the liquid desiccant technologies for space air conditioning. Certain issues regarding the mass imbalance in the dehumidification and regeneration processes have been identified to be considered as future scope.
引用
收藏
页码:11148 / 11166
页数:19
相关论文
共 50 条
  • [21] The experimental study of dehumidification and regeneration processes in a fin and tube liquid desiccant system
    Indrawan, Wisnu
    Lubis, Arnas
    Nasruddin
    Alhamid, M. I.
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 39
  • [22] A proposed hyper-gravity liquid desiccant dehumidification system and experimental verification
    Gu, Yangyang
    Zhang, Xiaosong
    APPLIED THERMAL ENGINEERING, 2019, 159
  • [23] Numerical analysis of liquid desiccant dehumidification system with novel trapezoidal baffled surface
    Das, Aabir
    Das, Rajat Subhra
    Das, Koushik
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 145 : 457 - 466
  • [24] An Experimental Study on Dehumidification Characteristics according to Operating Conditions of Liquid Desiccant System
    Jeon, Dong-Soon
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2024, 48 (11) : 737 - 744
  • [25] Experimental Investigation of Desiccant Dehumidification Cooling System for Climatic Conditions of Multan (Pakistan)
    Aleem, Muhammad
    Hussain, Ghulam
    Sultan, Muhammad
    Miyazaki, Takahiko
    Mahmood, Muhammad H.
    Sabir, Muhammad, I
    Nasir, Abdul
    Shabir, Faizan
    Khan, Zahid M.
    ENERGIES, 2020, 13 (21)
  • [26] Experimental investigation and analytical prediction of a multi-channel flat heat pipe thermal performance
    Guichet V.
    Khordehgah N.
    Jouhara H.
    International Journal of Thermofluids, 2020, 5-6
  • [27] Experimental investigation of a polymer hollow fibre integrated liquid desiccant dehumidification system with aqueous potassium formate solution
    Chen, Xiangjie
    Su, Yuehong
    Aydin, Devrim
    Bai, Hongyu
    Jarimi, Hasila
    Zhang, Xingxing
    Riffat, Saffa
    APPLIED THERMAL ENGINEERING, 2018, 142 : 632 - 643
  • [28] Experimental investigation of a novel desiccant cooling system
    Hurdogan, Ertac
    Buyukalaca, Orhan
    Yilmaz, Tuncay
    Hepbasli, Arif
    ENERGY AND BUILDINGS, 2010, 42 (11) : 2049 - 2060
  • [29] INVESTIGATION OF THE MULTIPLICATION ELECTRON PROCESS IN MULTI-CHANNEL PLATE
    APANASOVICH, VV
    NOVIKOV, EG
    RADIOTEKHNIKA I ELEKTRONIKA, 1989, 34 (07): : 1469 - 1474
  • [30] ANALYSIS OF AIR DEHUMIDIFICATION USING LIQUID DESICCANT SYSTEM
    ELSAYED, MM
    RENEWABLE ENERGY, 1994, 4 (05) : 519 - 528