An Experimental Study on Dehumidification Characteristics according to Operating Conditions of Liquid Desiccant System

被引:0
|
作者
Jeon, Dong-Soon [1 ]
机构
[1] Korea Inst Ind Technol, Ind Energy R&D Dept, Cheonan Si, South Korea
关键词
Dehumidification Rate; Dehumidification Effectiveness; LiCl Aqueous Solution; MASS-TRANSFER; PERFORMANCE;
D O I
10.3795/KSME-B.2024.48.11.737
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Liquid desiccant based dehumidification system have been widely used to remove moisture from humid air. And this system has the advantage of being able to effectively remove latent heat from humid air, as well as use low grade energy sources such as solar heat and waste heat. Because of these advantages, liquid desiccant dehumidification systems have attracted increasing attention in recent years as a potential alternative to the conventional dehumidification methods. Therefore in this paper, a experimental study on the dehumidification characteristics of the dehumidification system according to the operating conditions was performed. Packing material(Celdek 7090(munter's)) of 150 mm in width, 300 mm depth and 400 mm in height was used for experiment. A correlation of main performance indexes(Q(a), (m) over dot(deh), eta(deh)) was propose by experimental study. The proposed correlation is expected to be useful in dehumidification system designs.
引用
收藏
页码:737 / 744
页数:8
相关论文
共 50 条
  • [1] Experimental study of dynamic characteristics of liquid desiccant dehumidification processes
    Wang, Lingshi
    Xiao, Fu
    Niu, Xiaofeng
    Gao, Dian-Ce
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (01) : 91 - 104
  • [2] On Effective Design and Operating Conditions of Desiccant Dehumidification System
    Chu, Yu-Cheng
    Weng, Ling-Chia
    Tseng, Pen-Chang
    Kang, Yu-Hao
    Wang, Chi-Chuan
    HEAT TRANSFER ENGINEERING, 2018, 39 (7-8) : 598 - 607
  • [3] EXPERIMENTAL ANALYSIS OF AIR DEHUMIDIFICATION SYSTEM WITH LIQUID DESICCANT
    Zhang, Li
    Chitose, Tanaka
    Hihara, Eiji
    PROCEEDINGS OF THE ASME INTERNATIONAL HEAT TRANSFER CONFERENCE - 2010, VOL 8, 2010, : 169 - 177
  • [4] The experimental study of dehumidification and regeneration processes in a fin and tube liquid desiccant system
    Indrawan, Wisnu
    Lubis, Arnas
    Nasruddin
    Alhamid, M. I.
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 39
  • [5] Dehumidifier desiccant concentration soft-sensor for a distributed operating Liquid Desiccant Dehumidification System
    Wu, Qiong
    Cai, WenJian
    Wang, Xinli
    Chakraborty, Anutosh
    ENERGY AND BUILDINGS, 2016, 129 : 215 - 226
  • [6] EXPERIMENTAL STUDY ON A TWO-STAGE LIQUID DESICCANT DEHUMIDIFICATION SYSTEM USING DUAL DESICCANT SOLUTIONS
    Xiong, Z. Q.
    Wang, R. Z.
    Dai, Y. J.
    HEAT TRANSFER RESEARCH, 2015, 46 (04) : 383 - 397
  • [7] Experimental investigation of a liquid desiccant system for solar cooling and dehumidification
    Gommed, K.
    Grossman, G.
    SOLAR ENERGY, 2007, 81 (01) : 131 - 138
  • [8] Dehumidification characteristics of recirculated desiccant wheel dehumidification system under variable working conditions
    Wu W.
    Han X.
    Zhou Z.
    Wang Y.
    Chong D.
    Huagong Xuebao/CIESC Journal, 2020, 71 : 355 - 360
  • [9] Experimental study on dehumidification/regeneration of liquid desiccant: LiBr solution
    Bouzenada, S.
    Kaabi, A. N.
    Fraikin, L.
    Leonard, A.
    5TH INTERNATIONAL CONFERENCE ON AMBIENT SYSTEMS, NETWORKS AND TECHNOLOGIES (ANT-2014), THE 4TH INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY INFORMATION TECHNOLOGY (SEIT-2014), 2014, 32 : 673 - 680
  • [10] Experimental study on partially internally cooled dehumidification in liquid desiccant air conditioning system
    Gao, W. Z.
    Shi, Y. R.
    Cheng, Y. P.
    Sun, W. Z.
    ENERGY AND BUILDINGS, 2013, 61 : 202 - 209