Design, fabrication, investigation and analysis of a novel flat evaporator loop heat pipe for cooling high heat flux server chips

被引:36
|
作者
Xiong, Kangning [1 ]
Meng, Like [1 ]
Wang, Shuangfeng [1 ]
机构
[1] South China Univ Technol, Sch Chem & Chem Engn, Key Lab Heat Transfer Enhancement & Energy Conser, Minist Educ, Guangzhou 510640, Peoples R China
基金
中国国家自然科学基金;
关键词
Loop heat pipe; Flat evaporator; Filling ratios; Capillary performance; Thermal characteristics; Water block; FIBER SINTERED SHEET; THERMAL PERFORMANCE; DATA CENTERS; MANAGEMENT; SYSTEMS; WICK; FLOW;
D O I
10.1016/j.applthermaleng.2021.117775
中图分类号
O414.1 [热力学];
学科分类号
摘要
A novel loop heat pipe (LHP) with a flat evaporator has been proposed to meet the heat dissipation requirement of high heat flux server CPU. The sintered porous copper wick was provided with a double arrayed vapor channels to increase the evaporation area. And a 1 mm thick smaller particle size copper powder embedded with two 0.5 mm thick stainless steel rings was sintered on the inner surface of the compensation chamber to enhance the strength, and increase the working fluid into the porous wick such that the liquid saturation was enhanced and the dry zone was reduced at high heat flux. Additionally, a dual layer structure condenser was presented to increase the cooling area of the condenser. In this study, the systematic experimental studies were carried out mainly focusing on the optimization of powder size, heat transfer performance of the novel LHP and performance comparison of the novel LHP. The results demonstrated that the sintered copper powder of the 106-150 mu m particle size shown the best capillary performance in comparison with other powder sizes. More importantly, in the heat load range of 500-750 W, the novel LHP of filling ratio of 46.1% exhibited better operating thermal characteristics. The minimum values of the LHP thermal resistance and the total system thermal resistance at the heat load of 750 W were 0.040 degrees C/W and 0.090 degrees C/W, respectively. Compared with the conventional LHP and the simple water block, the novel flat evaporator LHP was a more promising option when the heat load was higher than 250 W.
引用
收藏
页数:18
相关论文
共 50 条
  • [41] AN EXPERIMENTAL INVESTIGATION OF THE MINIATURE LOOP HEAT PIPE COOLING SYSTEMS FOR HIGH POWER DENSITY COMPUTER CHIPS
    Choi, Jeehoon
    Yoo, Junghyun
    Sung, Byungho
    Kim, Chulju
    Borca-Tasciuc, Diana-Andra
    PROCEEDINGS IF THE ASME 9TH INTERNATIONAL CONFERENCE ON NANOCHANNELS, MICROCHANNELS AND MINICHANNELS 2011, VOL 1, 2012, : 421 - +
  • [42] Experimental study of heat transfer capacity for loop heat pipe with flat disk evaporator
    Zhang, Zikang
    Zhang, Hao
    Ma, Zhenyuan
    Liu, Zhichun
    Liu, Wei
    APPLIED THERMAL ENGINEERING, 2020, 173
  • [43] Peculiarities of heat transfer in a flat disk-shaped evaporator of a loop heat pipe
    Chernysheva, M. A.
    Maydanik, Yu. F.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 92 : 1026 - 1033
  • [44] Experimental studies on a high performance compact loop heat pipe with a square flat evaporator
    Li, Ji
    Wang, Daming
    Peterson, G. P.
    APPLIED THERMAL ENGINEERING, 2010, 30 (6-7) : 741 - 752
  • [45] Flat Loop Heat Pipe for Cooling Graphics Card
    Mo, Dong-chuan
    Zou, Guan-sheng
    Lu, Shu-shen
    PROCEEDINGS OF ISHTEC2012, 4TH INTERNATIONAL SYMPOSIUM ON HEAT TRANSFER AND ENERGY CONSERVATION, 2011, : 147 - 149
  • [46] Investigation of a novel flat heat pipe
    Wang, YX
    Peterson, GP
    JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2005, 127 (02): : 165 - 170
  • [47] Multi-evaporator hybrid loop heat pipe for cooling high performance servers
    Zimbeck, W.
    Yun, J.
    Cennamo, J.
    Kroliczek, E.
    THERMES 2007: THERMAL CHALLENGES IN NEXT GENERATION ELECTRONIC SYSTEMS, 2007, : 249 - +
  • [48] Analysis of the evaporation process in a high heat flux flat plate heat pipe
    Carbaja, Gerardo
    Sobhan, C. B.
    Peterson, G. P.
    Proceedings of the ASME Heat Transfer Division 2005, Vol 1, 2005, 376-1 : 27 - 33
  • [49] Experimental study on flat type loop heat pipe with parallel evaporator
    Liu, Z.-C. (zcliu@hust.edu.cn), 1939, Science Press (34):
  • [50] Experimental investigation of a loop heat pipe with a flat evaporator and cupric oxide nanofluids as working fluid
    Zhao, Tianyuan
    Ma, Zhengyuan
    Zhang, Zikang
    Deng, Weizhong
    Long, Rui
    Liu, Wei
    Ma, Lei
    Liu, Zhichun
    Energy Reports, 2021, 7 : 7693 - 7703