New Approach for Upgrading an Existing 115 kV Transmission Line

被引:0
|
作者
Callery, Karen [1 ]
Hathout, Ibrahim [1 ]
机构
[1] Hydro One Inc, Transmiss Lines Dept, 483 Bay St, Toronto, ON M5G 2P5, Canada
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces pioneering solution for upgrading 45 km, 115 kV double circuit line, built in 1922, in Ontario. To double the circuits' power transfer, the existing 605 kcmil ACSR was replaced with 997.2 kcmil ACSR/WT conductor and the thermal rating was increased from 85 degrees C to 150 degrees C. Visual inspection and probabilistic corrosion model were used to determine the severity of corrosion and to incorporate corrosion damages into analysis of the steel towers. Relocating the bottom phases to modified middle arms did not provide sufficient ground clearance and using conventional vertical extensions on existing grillage footings were impractical because it require large crane to lift the fully dressed tower, which was impossible in populated areas. Innovative solution using lighter shaft extension inserted above the tower's bend line was designed allowing the use of smaller crane thus considerably lowered material and construction costs. Further, galloping performance was improved by installing inter-phase spacers.
引用
收藏
页码:538 / 549
页数:12
相关论文
共 50 条
  • [31] Research on Upgrading Plan of Transmission Line for Voltage Sag Treatment
    Wang, Xue
    Liu, Changrong
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2022, 17 (03) : 1509 - 1516
  • [32] COMPACTION TECHNIQUES APPLIED TO SUBTRANSMISSION LINE UPRATING 41. 6 KV TO 115 KV.
    Broschat, Myron
    Clayton, Roger
    Radiophysics and Quantum Electronics (English Translation of Izvestiya Vysshikh Uchebnykh Zavedenii, Radiofizika), 1980,
  • [33] PERFORMANCE OF 115 KV FIBERGLASS TRANSMISSION CROSSARMS IN WET AND SALT FOG ENVIRONMENTS
    SHAH, KR
    SARKINEN, CF
    VERMA, V
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (04): : 805 - 811
  • [34] SVC for Reliability Improvement in the NSTAR 115 kV Cape Cod Transmission System
    Bostrom, Anders
    Grunbaum, Rolf
    Dahlblom, Marie
    Oheim, Henry V.
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [35] Upgrading of Ge-Hu DC transmission line completed
    Liu Chunsheng
    Electricity, 2010, 21 (02) : 1 - 1
  • [36] Electrical performance of 115 kV transmission lines fiberglass crossarms aged in field
    Grzybowski, S
    PROCEEDINGS OF THE 5TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 1997, : 774 - 777
  • [37] ELECTRICAL DESIGN OF 115-138 KV COMPACT TRANSMISSION-LINES
    CLAYTON, RE
    GRANT, IS
    STEWART, JR
    WILSON, DD
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (02): : 323 - 323
  • [38] A new approach of Mho distance relay for Transmission line protection
    Ahmed, Abdullah Hamed
    Sultan, Ahmed Jasim
    2ND INTERNATIONAL CONFERENCE ON SUSTAINABLE ENGINEERING TECHNIQUES (ICSET 2019), 2019, 518
  • [39] Transmission Line Arresters Application for Control of Switching Overvoltages on 500-kV Transmission Line
    Bunov, P.
    Klingbeil, L.
    Schubert, M.
    Gossler, B.
    Biswas, D.
    Hunt, James
    Thallam, R.
    Keri, A. J. F.
    2014 IEEE PES T&D CONFERENCE AND EXPOSITION, 2014,
  • [40] Line Surge Arrester Application for a 380 kV Power Transmission Line
    Font, Aytug
    Ilhan, Suat
    Ozdemir, Aydogan
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,