New Approach for Upgrading an Existing 115 kV Transmission Line

被引:0
|
作者
Callery, Karen [1 ]
Hathout, Ibrahim [1 ]
机构
[1] Hydro One Inc, Transmiss Lines Dept, 483 Bay St, Toronto, ON M5G 2P5, Canada
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces pioneering solution for upgrading 45 km, 115 kV double circuit line, built in 1922, in Ontario. To double the circuits' power transfer, the existing 605 kcmil ACSR was replaced with 997.2 kcmil ACSR/WT conductor and the thermal rating was increased from 85 degrees C to 150 degrees C. Visual inspection and probabilistic corrosion model were used to determine the severity of corrosion and to incorporate corrosion damages into analysis of the steel towers. Relocating the bottom phases to modified middle arms did not provide sufficient ground clearance and using conventional vertical extensions on existing grillage footings were impractical because it require large crane to lift the fully dressed tower, which was impossible in populated areas. Innovative solution using lighter shaft extension inserted above the tower's bend line was designed allowing the use of smaller crane thus considerably lowered material and construction costs. Further, galloping performance was improved by installing inter-phase spacers.
引用
收藏
页码:538 / 549
页数:12
相关论文
共 50 条
  • [1] Upgrading an existing 138 kV transmission line in Manitoba
    Lu, M. L.
    Pfrimmer, G.
    Kieloch, Z.
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 964 - +
  • [2] An approach to improve grounding resistance characteristic in existing 115 KV transmission towers
    Pothisarn, Chaichan
    Kulwongwit, Wiwat
    Lertwanitrot, Praikanok
    Bunjongjit, Sulee
    Ngaopitakkul, Atthapol
    RESULTS IN ENGINEERING, 2024, 24
  • [3] Upgrading of a 230 kV steel transmission line system using probabilistic approach
    Haldar, Asim
    2006 International Conference on Probabilistic Methods Applied to Power Systems, Vols 1 and 2, 2006, : 1133 - 1139
  • [4] TRANSMISSION-LINE UPRATING 115 KV TO 230 KV REPORT ON OPERATING PERFORMANCE
    BROSCHAT, M
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (02): : 545 - &
  • [5] The security precautions in the 500 kV transmission line protection upgrading and replacing
    Yao, Li-Na
    Liu, Hua
    Zhang, Bin
    Zhou, Ya-Hui
    Jia, Wei
    Zhang, Xin-Wang
    Zhang, Qiang
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (22): : 220 - 223
  • [6] TRANSMISSION LINE UPRATING 115-KV TO 230-KV ELECTRICAL AND STRUCTURAL DESIGN
    LARSON, ELC
    BROSCHAT, M
    THOMPSON, RL
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1967, PA86 (05): : 539 - &
  • [7] Lightning Location on 115-kV Transmission Line using Travelling Waves
    Bunjongjit, Sulee
    Ngaopitakkul, Atthapol
    Leelajindakrairerk, Monthon
    2018 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2018,
  • [8] A Comparative Study of Magnetic Fields in 115 kV Single Circuit Transmission Line of Thailand
    Isaramongkolrak, A.
    Srikun, I.
    Sumpavakup, C.
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [9] AC AND LIGHTNING PERFORMANCE OF FIBERGLASS CROSSARMS AGED IN 115 KV TRANSMISSION-LINE
    GRZYBOWSKI, S
    JENKINS, EB
    IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (04) : 1914 - 1920
  • [10] SENSITIVITY ANALYSIS OF 115-138KV COMPACT TRANSMISSION-LINE COSTS
    LONGO, VJ
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (02): : 324 - 324