Optimization of geothermal interaction of a double U-tube borehole heat exchanger for space heating and cooling applications using Taguchi method and utility concept

被引:45
|
作者
Kumar, Satish [1 ]
Murugesan, K. [1 ]
机构
[1] Indian Inst Technol Roorkee, Dept Mech & Ind Engn, Roorkee 247667, Uttar Pradesh, India
关键词
Double U-tube borehole heat exchanger; Ground source heat pump system; Optimization of heat transfer; Space cooling and heating applications; Taguchi method; Utility concept; THERMAL PERFORMANCE; MULTIRESPONSE OPTIMIZATION; PUMP SYSTEM; INTERFERENCE;
D O I
10.1016/j.geothermics.2019.101723
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Optimization results for thermal interaction of a double U-tube borehole heat exchanger (BHE) used along with a 5 ton capacity ground source heat pump system (GSHP), are discussed in this paper. Heat transfer from the BHE is computed using thermal resistance concept for space cooling and heating mode operations. The main objective of optimization is to achieve maximum heat extraction during space heating and maximum heat rejection during space cooling operations. For the purpose of optimization, eight control variables consisting of geometric parameters, thermo-physical parameters and mass flow rate are considered at three levels for a series connected double U-tube BHE of 120 m depth. For Taguchi method L-27 orthogonal array has been employed for the computation of heat transfer and S/N ratios for both modes of operations. Results obtained show that optimum values of 9270 W and 7210 W heat can be rejected to and extracted from the ground. Taguchi results are combined to obtain a single set of optimum levels of control variables using the utility concept. Mass flow rate of water in the BHE is found to be the most influential variable. For variation in the duration of cooling and heating mode operations, the optimum heat that could be rejected and absorbed becomes the same and equal to 6180 W for equal duration. It is observed that the heat transfer calculated from the utility concept is 11.11% and 42.86% less than those values calculated by Taguchi method for cooling and heating mode of operations respectively.
引用
收藏
页数:17
相关论文
共 45 条
  • [41] Optimization of double diffusive mixed convection in a BFS channel filled with Alumina nanoparticle using Taguchi method and utility concept
    Nath, Ratnadeep
    Krishnan, Murugesan
    SCIENTIFIC REPORTS, 2019, 9 (1)
  • [42] Design optimization of a shell-and-tube heat exchanger with novel three-zonal baffle by using CFD and taguchi method
    Bicer, Nihat
    Engin, Tahsin
    Yasar, Halit
    Buyukkaya, Ekrem
    Aydin, Ahmet
    Topuz, Adnan
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2020, 155
  • [43] Analysis, prediction and multi-objective optimization of helically coiled tube-in-tube heat exchanger with double cooling source using RSM
    Liu, Shaobei
    Huang, Weixing
    Bao, Zewei
    Zeng, Tao
    Qiao, Min
    Meng, Jiancheng
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2021, 159
  • [44] Multi-objective shape optimization of double pipe heat exchanger with inner corrugated tube using RSM method
    Han, Huai-Zhi
    Li, Bing-Xi
    Wu, Hao
    Shao, Wei
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2015, 90 : 173 - 186
  • [45] Investigation of Trapezoidal-Cut Twisted Tape Insert in a Double Pipe U-Tube Heat Exchanger using Al2O3/Water Nanofluid
    Prasad, P. V. Durga
    Gupta, A. V. S. S. K. S.
    Deepak, K.
    2ND INTERNATIONAL CONFERENCE ON NANOMATERIALS AND TECHNOLOGIES (CNT 2014), 2015, 10 : 50 - 63