Electrical distribution networks with isolated neutral point - the value of the capacitive earth-fault current and impact on the operation of these networks

被引:0
|
作者
Nohacova, Lucie [1 ]
Vykuka, Roman [1 ]
Zak, Frantisek [2 ]
Kropacek, Vaclav [3 ]
机构
[1] Univ W Bohemia, Dept Elect Engn & Environm Engn, Plzen 30614, Czech Republic
[2] EGE Sro, Sect Elect Power Engn, Dept Distribut Network Operat, Ceske Budejovice, Czech Republic
[3] CEZ As, Div Distribut & Foreign, Plzen, Czech Republic
关键词
renewable energy sources; electrical network operation;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Distribution networks operated with isolated neutral point the capacitive earth-fault current flows through the point of fault in the case of a single-phase-to-earth fault. The magnitude of the current depends on the used type of line and the scope of network. There are many reasons for determining values of the capacitive earth-fault current. One of the most important reasons is the distribution networks operation safety. During a single phase earth fault, it is necessary to adhere to the allowed values of the touch voltage. This article has been written based on own knowledge and long-time experience acquired by the processing of measurements in the distribution network. The described method has been verified in real operation and based on the results a special-purpose automatic system for the measurement of the capacitive earth-fault current in a network with isolated neutral point has been developed.