New standard for electrical grid reliability and energy efficiency. Commercially available Fault Current Limiters enable cost-effective connection of generation and distributed renewable energy sources to transmission, distribution and industrial networks
被引:0
|
作者:
Garbi, Uri
论文数: 0引用数: 0
h-index: 0
机构:
GridON Ltd, Giv'atayim, IsraelGridON Ltd, Giv'atayim, Israel
Garbi, Uri
[1
]
Pannu, Mohinder
论文数: 0引用数: 0
h-index: 0
机构:
Wilson Transformer Co, Glen Waverley, AustraliaGridON Ltd, Giv'atayim, Israel
Pannu, Mohinder
[2
]
机构:
[1] GridON Ltd, Giv'atayim, Israel
[2] Wilson Transformer Co, Glen Waverley, Australia
fault current limiter;
recovery;
saturated core;
failsafe;
FCL;
transmission and distribution;
D O I:
暂无
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
GridON's saturated core fault current limiters have been installed in live networks for more than two years. Field performance and test results of 10MVA and 30MVA devices are described in this paper. These saturated core fault current limiters (FCLs) are passive failsafe devices, which limit the fault current from the first peak and have immediate recovery capability. They present a large ratio between fault impedance and normal impedance, based solely on the current level through them. These FCLs are now well-established field proven devices and commercially available products. The paper reviews the performance of these devices through long duration and high power fault events. Their uninterrupted operation in transformer feeders is demonstrated. These FCLs are based on standard power transformer technology and are scalable to all voltage levels up to EHV transmission networks.