Ventilation and energy performance of partitioned indoor spaces under mixing and displacement ventilation

被引:55
|
作者
Ahn, Hyeunguk [1 ]
Rim, Donghyun [1 ]
Lo, L. James [2 ]
机构
[1] Penn State Univ, Dept Architectural Engn, University Pk, PA 16802 USA
[2] Drexel Univ, Dept Civil Architectural & Environm Engn, Philadelphia, PA 19104 USA
关键词
computational fluid dynamics; indoor partition; ventilation effectiveness; energy consumption; thermal comfort; draft risk; COMPUTATIONAL FLUID-DYNAMICS; AIR-DISTRIBUTION SYSTEMS; ROOM AIR; OFFICE ENVIRONMENT; TURBULENCE; LOCATION; QUALITY; FLOW; CFD; EFFICIENCY;
D O I
10.1007/s12273-017-0410-z
中图分类号
O414.1 [热力学];
学科分类号
摘要
Large variation in indoor air quality (IAQ) and thermal comfort can occur in partitioned office spaces due to heterogeneous air mixing. However, few published studies examined IAQ, thermal comfort, and energy performance of partitioned occupied spaces, which are commonly found in today's buildings. The objective of this study is to evaluate indoor environmental quality and air conditioning performance of a partitioned room under two typical ventilation modes: (1) mixing ventilation and (2) displacement ventilation. For a total of six representative air-conditioning scenarios, three-dimensional computational fluid dynamics (CFD) simulations are performed to examine temperature distribution, ventilation effectiveness, energy consumption, and local thermal comfort for two partitioned spaces. Simulation results indicate that temperature distribution in a partitioned room is a strong function of ventilation strategy (mixing vs. displacement), but marginally affected by diffuser arrangements. Local age-of-air (air freshness) significantly varies with both diffuser arrangement and ventilation strategy. Regarding energy consumption, displacement ventilation can achieve an indoor set-point temperature in the partitioned spaces about two times faster than mixing ventilation. Under mixing ventilation, the time to achieve a set-point temperature was notably reduced when each partitioned space is served by its own diffuser. For the same supply airflow rate, displacement ventilation can generate local draft risk at ankle level, while mixing ventilation may result in a draft sensation in wider areas around an occupant. Overall, the results suggest that mixing ventilation system can save energy if each partitioned zone is served by its own diffuser such as a multi-split air conditioning. However, when multiple partitioned zones are served by only one diffuser, displacement ventilation is more energy-efficient and can achieve higher ventilation effectiveness than mixing ventilation.
引用
收藏
页码:561 / 574
页数:14
相关论文
共 50 条
  • [41] Effect of air supply temperature on the performance of displacement ventilation (Part II) - Indoor air quality
    Lin, Z
    Chow, TT
    Tsang, CF
    Fong, KF
    Chan, LS
    INDOOR AND BUILT ENVIRONMENT, 2005, 14 (02) : 117 - 131
  • [42] On the transition from displacement to mixing ventilation with a localized heat source
    Fitzgerald, Shaun D.
    Woods, Andrew W.
    BUILDING AND ENVIRONMENT, 2007, 42 (06) : 2210 - 2217
  • [43] Experimental Study on Displacement and Mixing Ventilation Systems for a Patient Ward
    Yin, Yonggao
    Xu, Weiran
    Gupta, Jitendra K.
    Guity, Arash
    Marmion, Paul
    Manning, Andy
    Gulick, Bob
    Zhang, Xiaosong
    Chen, Qingyan
    HVAC&R RESEARCH, 2009, 15 (06): : 1175 - 1191
  • [44] Comparing mixing and displacement ventilation in classrooms: pupils' perception and health
    Smedje, G.
    Mattsson, M.
    Walinder, R.
    INDOOR AIR, 2011, 21 (06) : 454 - 461
  • [45] Investigation of airborne particle exposure in an office with mixing and displacement ventilation
    Liu, Sumei
    Koupriyanov, Mike
    Paskaruk, Dale
    Fediuk, Graham
    Chen, Qingyan
    SUSTAINABLE CITIES AND SOCIETY, 2022, 79
  • [46] COMPARATIVE STUDY ON DISPLACEMENT AND MIXING VENTILATION SYSTEMS FOR A PATIENT WARD
    Yin, Yonggao
    Xu, Weiran
    Gupta, Jitendra K.
    Guity, Arash
    Marmion, Paul
    Manning, Andy
    Gulick, Bob
    Zhang, Xiaosong
    Chen, Qingyan
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 1007 - 1014
  • [47] Comparison of Mixing and Displacement Ventilation under Limited Space Air Stability Conditions in a Space Capsule
    Deng, Xiaorui
    Gong, Guangcai
    MICROGRAVITY SCIENCE AND TECHNOLOGY, 2020, 32 (04) : 749 - 759
  • [48] A comparative experimental study on the performance of mixing ventilation and stratum ventilation for space heating
    Kong, Xiangfei
    Xi, Chang
    Li, Han
    Lin, Zhang
    BUILDING AND ENVIRONMENT, 2019, 157 : 34 - 46
  • [49] Comparison of Mixing and Displacement Ventilation under Limited Space Air Stability Conditions in a Space Capsule
    Xiaorui Deng
    Guangcai Gong
    Microgravity Science and Technology, 2020, 32 : 749 - 759
  • [50] Dynamic performance of displacement ventilation in a lecture hall
    Lastovets, Natalia
    Kai Siren
    Kosonen, Risto
    Jokisalo, Juha
    Kilpelainen, Simo
    INTERNATIONAL JOURNAL OF VENTILATION, 2021, 20 (3-4) : 204 - 214