Ventilation and energy performance of partitioned indoor spaces under mixing and displacement ventilation

被引:55
|
作者
Ahn, Hyeunguk [1 ]
Rim, Donghyun [1 ]
Lo, L. James [2 ]
机构
[1] Penn State Univ, Dept Architectural Engn, University Pk, PA 16802 USA
[2] Drexel Univ, Dept Civil Architectural & Environm Engn, Philadelphia, PA 19104 USA
关键词
computational fluid dynamics; indoor partition; ventilation effectiveness; energy consumption; thermal comfort; draft risk; COMPUTATIONAL FLUID-DYNAMICS; AIR-DISTRIBUTION SYSTEMS; ROOM AIR; OFFICE ENVIRONMENT; TURBULENCE; LOCATION; QUALITY; FLOW; CFD; EFFICIENCY;
D O I
10.1007/s12273-017-0410-z
中图分类号
O414.1 [热力学];
学科分类号
摘要
Large variation in indoor air quality (IAQ) and thermal comfort can occur in partitioned office spaces due to heterogeneous air mixing. However, few published studies examined IAQ, thermal comfort, and energy performance of partitioned occupied spaces, which are commonly found in today's buildings. The objective of this study is to evaluate indoor environmental quality and air conditioning performance of a partitioned room under two typical ventilation modes: (1) mixing ventilation and (2) displacement ventilation. For a total of six representative air-conditioning scenarios, three-dimensional computational fluid dynamics (CFD) simulations are performed to examine temperature distribution, ventilation effectiveness, energy consumption, and local thermal comfort for two partitioned spaces. Simulation results indicate that temperature distribution in a partitioned room is a strong function of ventilation strategy (mixing vs. displacement), but marginally affected by diffuser arrangements. Local age-of-air (air freshness) significantly varies with both diffuser arrangement and ventilation strategy. Regarding energy consumption, displacement ventilation can achieve an indoor set-point temperature in the partitioned spaces about two times faster than mixing ventilation. Under mixing ventilation, the time to achieve a set-point temperature was notably reduced when each partitioned space is served by its own diffuser. For the same supply airflow rate, displacement ventilation can generate local draft risk at ankle level, while mixing ventilation may result in a draft sensation in wider areas around an occupant. Overall, the results suggest that mixing ventilation system can save energy if each partitioned zone is served by its own diffuser such as a multi-split air conditioning. However, when multiple partitioned zones are served by only one diffuser, displacement ventilation is more energy-efficient and can achieve higher ventilation effectiveness than mixing ventilation.
引用
收藏
页码:561 / 574
页数:14
相关论文
共 50 条
  • [31] The effect of opening on the enhancement of natural ventilation in indoor spaces
    Abdi, A.
    Abessi, O.
    Khavasi, E.
    INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2023, 20 (02) : 1875 - 1886
  • [32] The effect of opening on the enhancement of natural ventilation in indoor spaces
    A. Abdi
    O. Abessi
    E. Khavasi
    International Journal of Environmental Science and Technology, 2023, 20 : 1875 - 1886
  • [33] Ventilation performance study of a high-speed train cabin based on displacement ventilation and mixed ventilation
    Wu, Songbo
    Li, Tian
    Zhang, Jiye
    PHYSICS OF FLUIDS, 2024, 36 (07)
  • [34] INDOOR ENVIRONMENT OF A CLASSROOM IN A PASSIVE SCHOOL BUILDING WITH DISPLACEMENT VENTILATION
    Wang, Yang
    Kuckelkorn, Jens
    Zhao, Fu-Yun
    Spliethoff, Hartmut
    BUILDING SIMULATION 2013: 13TH INTERNATIONAL CONFERENCE OF THE INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION, 2013, : 1902 - 1909
  • [35] Experimental Study of Indoor Temperature Distribution for Displacement Ventilation System
    Li, Jingshan
    Guo, Xianmin
    Min, Kai
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1388 - 1395
  • [36] Study on the character of indoor air in house with displacement ventilation system
    Xuan, Wu
    Gao, Jinfang
    2011 2ND INTERNATIONAL CONFERENCE ON CHALLENGES IN ENVIRONMENTAL SCIENCE AND COMPUTER ENGINEERING (CESCE 2011), VOL 11, PT B, 2011, 11 : 1001 - 1007
  • [37] Co-occupant's exposure to exhaled pollutants with two types of personalized ventilation strategies under mixing and displacement ventilation systems
    Li, X.
    Niu, J.
    Gao, N.
    INDOOR AIR, 2013, 23 (02) : 162 - 171
  • [38] Performance of "ductless" personalized ventilation in conjunction with displacement ventilation: Impact of intake height
    Halvonova, Barbora
    Melikov, Arsen K.
    BUILDING AND ENVIRONMENT, 2010, 45 (04) : 996 - 1005
  • [39] Thermal and ventilation performance of combined passive chilled beam and displacement ventilation systems
    Shan, Wenyu
    Rim, Donghyun
    ENERGY AND BUILDINGS, 2018, 158 : 466 - 475
  • [40] Concentration characteristics of ozone and product for indoor occupant surface chemical reaction under displacement ventilation
    Wang, Jun
    Chen, Yong
    ENERGY AND BUILDINGS, 2016, 130 : 378 - 387