Numerical procedure for predicting annual energy consumption of the under-floor air distribution system

被引:49
|
作者
Xu, HT [1 ]
Niu, JL [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
UFAD; mixing; CFD; ACCURACY; simulation;
D O I
10.1016/j.enbuild.2005.10.003
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
As compared with the mixing system, indoor air temperature stratification in the under-floor air distribution (UFAD) system offers an opportunity for cooling load reduction in the occupied zone. This stratification is a major feature that offers the energy saving potential, but it has not been thoroughly taken into account in most energy simulation programs. In this article, a numerical procedure, based on coupling two types of modeling, i.e., CFD (computational fluid dynamic) simulation and dynamic cooling load simulation, is proposed to predict annual energy consumption. The dimensionless temperature coefficient is first defined in the UFAD system and obtained from CFD simulation, based on the boundary conditions from a cooling load program ACCURACY. According to this coefficient, temperature stratification input to ACCURACY is then revised to calculate the updated supply and exhaust air temperatures for final annual energy prediction. To demonstrate the method, a small office room is investigated using Hong Kong weather data. With the constant air volume (CAV) supply in the UFAD system, it is found that the dimensionless temperature coefficient is almost a constant, when the locations of heat sources are fixed. As compared with the mixing system, the UFAD system derives its energy saving potential from the following three factors: an extended free cooling time, a reduced ventilation load, and increased coefficients of performance (COP) for chillers. (C) 2005 Elsevier B.V. All rights reserved.
引用
收藏
页码:641 / 647
页数:7
相关论文
共 50 条
  • [31] EVALUATION OF AN UNDER-FLOOR SWINE MANURE FLUSH SYSTEM WITH SETTLING BASIN AND LAGOON
    GILBERTSON, CB
    NIENABER, JA
    TRANSACTIONS OF THE ASAE, 1979, 22 (06): : 1381 - 1384
  • [32] Magnetic Design of a 300 W Under-floor Contactless Power Transfer System
    Zaheer, Adeel
    Budhia, Mickel
    Kacprzak, Dariusz
    Covic, Grant A.
    IECON 2011: 37TH ANNUAL CONFERENCE ON IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2011, : 1408 - 1413
  • [33] Effect of thermal conductivities of shape stabilized PCM on under-floor heating system
    Cheng, Wenlong
    Xie, Biao
    Zhang, Rongming
    Xu, Zhiming
    Xia, Yuting
    APPLIED ENERGY, 2015, 144 : 10 - 18
  • [34] Experimental study of radiation and free convection in an enclosure with under-floor heating system
    Rahimi, Mostafa
    Sabernaeemi, Arnir
    ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (07) : 2752 - 2757
  • [35] Building Energy Simulation, CFD and prototype testing to design an effective Under Floor Air Distribution System
    Webb, Matthew
    LIVING AND LEARNING: RESEARCH FOR A BETTER BUILT ENVIRONMENT, 2015, : 487 - 496
  • [36] A Comparative Study of Leakage Characteristics between an Under Floor Air Distribution System and an Over Head Air Distribution System
    Iyengar, Rupesh S.
    Sekhar, Chandra
    Karimabad, Arash Soleimani
    Haghighat, Fariborz
    Zhu, Kenny
    INTERNATIONAL JOURNAL OF VENTILATION, 2015, 14 (01) : 1 - 10
  • [37] A numerical method for energy consumption prediction of the underfloor air distributioin system
    Xu, HT
    Niu, JL
    INDOOR AIR 2005: PROCEEDINGS OF THE 10TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY AND CLIMATE, VOLS 1-5, 2005, : 1305 - 1310
  • [38] Thermal environment in indoor spaces with under-floor air distribution systems: Part 1. Impact of design parameters (1522-RP)
    Lee, Kisup
    Xue, Guangqing
    Jiang, Zheng
    Chen, Qingyan
    HVAC&R RESEARCH, 2012, 18 (06): : 1182 - 1191
  • [39] Application analysis and economical study on an under-floor electric heating system with superconducting liquid in China
    Shi, Guohua
    Zhang, Xutao
    Liu, Songtao
    Zhang, Weitang
    Wang, Hong
    PROCEEDINGS OF THE ENERGY SUSTAINABILITY CONFERENCE 2007, 2007, : 721 - 727
  • [40] Modeling and simulation of under-floor electric heating system with shape-stabilized PCM plates
    Lin, KP
    Zhang, YP
    Xu, X
    Di, HD
    Yang, R
    Qin, PH
    BUILDING AND ENVIRONMENT, 2004, 39 (12) : 1427 - 1434