A numerical study on the effect of column layout on air distribution and performance of column attachment ventilation

被引:28
|
作者
Yin, Haiguo [1 ]
Li, Linna [1 ]
Wu, Rui [1 ]
Wang, Yuanyuan [1 ]
Li, Angui [1 ]
机构
[1] Xian Univ Architecture & Technol, Sch Bldg Serv Sci & Engn, Xian 710055, Shaanxi, Peoples R China
基金
中国国家自然科学基金;
关键词
column attachment ventilation; air distribution; column layout; performance evaluation; large space buildings; IMPINGING JET VENTILATION; STRATUM VENTILATION; DISPLACEMENT VENTILATION; THERMAL ENVIRONMENT; COOLING SYSTEM; DESIGN; FLOW;
D O I
10.1007/s12273-020-0699-x
中图分类号
O414.1 [热力学];
学科分类号
摘要
Based on the structural characteristics of existing buildings and the disadvantages of current mixed ventilation mode in the application to large space buildings, an original column attachment ventilation (CAV) has been proposed. In this study, the experiment utilized a room space with four columns uniformly distributed in the space to visualize the movement of attached airflow along the cylinder surface and the floor, the numerical technique was employed to study the effects of the column layout (i.e., uniform, centralized, dispersed, and crossed distribution) on the air distribution of CAV mode in a standard four-column full scale model of a shopping mall. Seven indices, including airflow pattern, air diffusion performance index (ADPI), air temperature distribution, heat removal effectiveness, draught rate (DR), predicted mean vote (PMV), and carbon dioxide (CO2) concentration, were used to assess the ventilation performance. In the CAV mode with a uniform column layout scheme, the experimental results indicated that the air supply flows downward along the wall surface, forming a secondary attachment with the ground and spreading along the floor in a fan radiation flow mode. Further, an "air lake"-like speed and temperature distribution similar to displacement ventilation (DV) was formed in the occupied zone. In all simulation cases, it was found that the average air velocity was less than 0.25 m/s in occupied zone, the effectiveness for heat removal was more significant than 1.0, DR value was less than 20%, the PMV level can also satisfy most people. The average CO(2)concentration was around 470 ppm in the occupied breathing zone. These results indicated that the CAV mode could be an efficient air distribution method. They demonstrated the technical feasibility of applying the CAV in the space under different column layout schemes.
引用
收藏
页码:1095 / 1108
页数:14
相关论文
共 50 条
  • [41] Experimental study on the seismic performance of a prefabricated steel column-column connection
    Yang, Yong
    Xu, Longkang
    Feng, Shiqiang
    Sun, Dongde
    Xue, Yicong
    Yu, Yunlong
    JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2022, 194
  • [42] Three Column Website Layout vs. Grid Website Layout: An Eye Tracking Study
    Namoun, Abdallah
    DESIGN, USER EXPERIENCE, AND USABILITY: DESIGNING INTERACTIONS, DUXU 2018, PT II, 2018, 10919 : 271 - 284
  • [43] Experimental study of regularity of effect of bottom air column length on cut blasting
    Fu, JG
    Qin, WS
    Li, YR
    THEORY AND PRACTICE OF ENERGETIC MATERIALS, VOL 5, PARTS A AND B, 2003, : 1059 - 1062
  • [44] Numerical Investigation on Effect of Vapor Split Ratio to Performance and Operability for Dividing Wall Column
    Maralani, Laleh Torab
    Yuan Xigang
    Luo Yiqing
    Gong Chao
    Yu Guocong
    CHINESE JOURNAL OF CHEMICAL ENGINEERING, 2013, 21 (01) : 72 - 78
  • [45] Investigating air compressibility effects in numerical modeling of oscillating water column wave energy converters: a case study on performance and accuracy
    Eskandari Shal, Javad
    Shafaghat, Rouzbeh
    Alizadeh Kharkeshi, Behrad
    COASTAL ENGINEERING JOURNAL, 2025,
  • [46] Column separation with the effect of air release in viscoelastic pipes
    Warda, H.A.
    Kandil, H.A.
    Elmiligui, A.A.
    Wahba, E.M.
    1600, Alexandria University (41):
  • [47] Numerical Study of the Dynamic Response of Stone Column and Geosynthetic Encased Stone Column in Soft Clay
    Zheng, Yewei
    Wang, Jiaxin
    Ji, Mingchang
    GEO-CONGRESS 2023: FOUNDATIONS, RETAINING STRUCTURES, AND GEOSYNTHETICS, 2023, : 447 - 455
  • [48] Hydrodynamic Performance of an Oscillating Water Column with Inclined Walls and a Submerged Plate: A Numerical Study
    Vasanthakumar, S.
    Sannasiraj, S. A.
    Sundar, V
    OCEANS 2024 - SINGAPORE, 2024,
  • [49] Experimental and numerical study on the seismic and shear performance of PSRC beam-column joints
    Wang, Wenkang
    Liang, Shuting
    Zhu, Xiaojun
    Han, Tiancheng
    Yang, Jian
    Xu, Yiwei
    STRUCTURES, 2025, 74
  • [50] The effect of pressure on the performance of bubble column dehumidifier
    Sharqawy, Mostafa H.
    Liu, Huicheng
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 87 : 212 - 221