AC Test Method for the Dynamic Characteristics of Transformer on-Load Tap Changer

被引:0
|
作者
Zhou, Hongwei [1 ]
Dong, Tian [1 ,2 ]
Liu, Fu [2 ]
机构
[1] SGCC, Jilin Prov Elect Power Co Ltd, Elect Power Res Inst, Beijing, Peoples R China
[2] Jilin Univ, Coll Commun Engn, Changchun 130023, Peoples R China
关键词
power transformer; on-load tap changers; AC waveform; switching process; dynamic response;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this paper, to detect the dynamic characteristics of transformer on-load tap changer (OLTC), an AC test method is introduced. The AC method has advantages of accurate result and unique interpretation. As a new method, the AC waveforms and their judgment of OLTC in transformer are introduced. First, 220V AC power is supplied to the transformer at primary side. Secondly, the current value of OLTC is sampled and transmitted to the host computer. Finally, we could diagnose the faults of OTLC according to the current waveform. Simulation results show that the AC test method proposed in this paper can detect the fault of OLTC effectively.
引用
收藏
页码:523 / 530
页数:8
相关论文
共 50 条
  • [21] Application of the Acoustic Emission Method for Diagnosis of On-Load Tap Changer
    Majchrzak, Henryk
    Cichon, Andrzej
    Borucki, Sebastian
    ARCHIVES OF ACOUSTICS, 2017, 42 (01) : 29 - 35
  • [22] A Segmented Preprocessing Method for the Vibration Signal of an On-Load Tap Changer
    Shang, Rongyan
    Peng, Changqing
    Fang, Ruiming
    ELECTRONICS, 2021, 10 (02) : 1 - 12
  • [23] Mechanical Fault Diagnosis of On-load Tap Changer of Power Transformer by Clustering Algorithm
    Chen, Peilong
    Ma, Xiaohong
    Wang, Fenghua
    Xie, Fangxin
    Zhou, Dongxu
    2018 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2018,
  • [24] Modelling of on-load tap-changer transformer with variable impedance and its applications
    Singapore Polytechnic, Singapore, Singapore
    Proc Int Conf Energy Manage Power Delivery EMPD, (491-494):
  • [25] Modelling of on-load tap-changer transformer with variable impedance and its applications
    Fan, J
    Bo, Z
    PROCEEDINGS OF EMPD '98 - 1998 INTERNATIONAL CONFERENCE ON ENERGY MANAGEMENT AND POWER DELIVERY, VOLS 1 AND 2 AND SUPPLEMENT, 1998, : 491 - 494
  • [26] ON-LOAD TRANSFORMER TAP REGULATION
    WEBB, DA
    ELECTRONICS AND POWER, 1979, 25 (09): : 634 - 640
  • [27] On-Load Tap Changer's Dynamic Resistance Measurement Settings and Interpretation
    Erbrink, J. J.
    Aditya, J.
    Chmura, L. A.
    Smit, J. J.
    Leich, R.
    Quak, B.
    2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 54 - 58
  • [28] Analysis of Dynamic Characteristics and its Influence on Electrical Sequence for On-load Tap Changer Fast Mechanism
    Wei F.
    Wang K.
    Li J.
    Yu Y.
    Zhang S.
    Lu Y.
    Li G.
    Zhang J.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (14): : 5674 - 5682
  • [29] Diagnosis of On-Load Tap Changer (OLTC) Using Dynamic Resistance Measurement
    Aziz, Mohd Azhar Abdul
    Talib, Mohd Aizam
    Arumugam, Ragavan
    2014 IEEE 8TH INTERNATIONAL POWER ENGINEERING AND OPTIMIZATION CONFERENCE (PEOCO), 2014, : 494 - 497
  • [30] Application vibroacoustic in the diagnosis of on-load tap changer
    Raclaw, Marcin
    Gielniak, Jaroslaw
    PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (10): : 126 - 129