Lightning Surge Analysis of a Transmission Line Tower With an XLPE Power Cable and Metallic Cleats Using the FDTD Method

被引:7
|
作者
Tatematsu, Akiyoshi [1 ]
机构
[1] Cent Res Inst Elect Power Ind, Yokosuka, Kanagawa 2400196, Japan
关键词
Poles and towers; Coaxial cables; Finite difference methods; Surges; Wires; Power cables; Lightning; Electromagnetic transient analysis; finite-difference time-domain method (FDTD); lightning; power cables; transmission line (TL) towers; TRANSIENT ELECTROMAGNETIC-FIELDS; AIR-INSULATED SUBSTATION; THIN WIRES; SIMULATION; BOUNDARY;
D O I
10.1109/TEMC.2019.2956931
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A direct lightning strike to a transmission line tower may cause overvoltages and insulation failures, and to avoid unexpected insulation failures and protect power equipment, it is necessary to install effective lightning protection measures. To design effective countermeasures, the prediction of lightning surge phenomena is required. The finite-difference time-domain (FDTD) method, one of the full-wave numerical approaches, which do not require the assumption of the transversal electromagnetic mode, has been an effective tool for predicting electromagnetic transient phenomena in 3-D structures, such as transmission line towers. In this article, using a technique for representing coaxial cables in the FDTD method, we simulate a reduced-scale model of a transmission line tower with a power cable, calculate the surge phenomena in the tower model when a surge current is injected into the top of the tower, and compare the FDTD results with the measured results for validation. Furthermore, we propose a technique for simulating the influence of using metallic cleats to fix a power cable to a transmission line tower for FDTD simulations in a 3-D arrangement, and we calculate surge phenomena in practical cross-linked polyethylene power cables placed over a ground plane and installed in a real-scale 77 kV transmission line tower. The FDTD results are validated through the comparison with measured results obtained in a previous study.
引用
收藏
页码:1796 / 1806
页数:11
相关论文
共 50 条
  • [31] Assessment of the transmission line theory in the modeling of multiconductor underground cable systems for transient analysis using a full-wave FDTD method
    Duarte, Naiara
    De Conti, Alberto
    Alipio, Rafael
    Rachidi, Farhad
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 223
  • [32] Surge Voltage and Environmental Electromagnetic Field Analysis for HV Composite Transmission Tower under Lightning Strokes
    Huangfu, Youpeng
    Wang, Shuhong
    Tao, Xi
    Wang, Song
    Yang, Bin
    Wang, Guolin
    Zhang, Yuxi
    2014 IEEE INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC), 2014, : 445 - 450
  • [33] Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line
    Mohajeryami, Saeed
    Doostan, Milad
    2016 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2016,
  • [34] A method of a lightning surge analysis recommended in Japan using EMTP
    Ametani, A
    Kawamura, T
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) : 867 - 875
  • [35] Analysis of tower surge impedance using the finite element method
    Alvares Mota, Paulo Cesar
    Carnacho, Jose Roberto
    Ribeiro Chaves, Marcelo Lynce
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 152 : 184 - 193
  • [36] Performance Analysis of a Overhead Power Transmission Line Tower Using Polymer Composite Material
    Selvaraj, M.
    Kulkarni, S. M.
    Rameshbabu, R.
    INTERNATIONAL CONFERENCE ON ADVANCES IN MANUFACTURING AND MATERIALS ENGINEERING (ICAMME 2014), 2014, 5 : 1340 - 1348
  • [37] Modeling and Insulation Performance Analysis of Composite Transmission Line Tower Under Lightning Overvoltage
    Huangfu, Youpeng
    Wang, Shuhong
    Wang, Guolin
    Xu, Weijie
    Zhang, Haijun
    IEEE TRANSACTIONS ON MAGNETICS, 2015, 51 (03)
  • [38] Research on a mixed method of the on-line monitoring of high voltage power cable with XLPE insulation
    Sun, HM
    Luo, LF
    Lu, HZ
    Fang, Z
    Xue, LF
    ICEMS 2003: PROCEEDINGS OF THE SIXTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1 AND 2, 2003, : 844 - 847
  • [39] FDTD Simulation of Back-Flashover at the Transmission-Line Tower Struck by Lightning Considering Ground-Wire Corona
    Thang, Tran Huu
    Baba, Yoshihiro
    Itamoto, Naoki
    Rakov, Vladimir A.
    2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2016,
  • [40] Application of the FDTD-based simulation code VSTL REV to the lightning surge analysis of a nuclear power plant
    Tatematsu, Akiyoshi
    Motoyama, Hideki
    Tanigawa, Akihiro
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 178