Application and Analysis of a Heat Pump System for Building Heating and Cooling Using Extracting Heat Energy from Untreated Sewage

被引:3
|
作者
Zhuang, Zhaoyi [1 ]
Zhao, Jin [1 ]
Mi, Fengfeng [2 ]
Zhang, Teng [3 ]
Hao, Yuguo [3 ]
Li, Shangyue [4 ]
机构
[1] Shandong Jianzhu Univ, Dept Thermal Energy Engn, Jinan 250101, Peoples R China
[2] Shandong Superego Ground Source Heat Pump Technol, Binzhou 256600, Peoples R China
[3] Shandong Zhong Ke Neng Artificial Environm Co Ltd, Heze 274032, Peoples R China
[4] Univ Glasgow, Sch Engn, Glasgow G12 8QQ, Scotland
基金
中国国家自然科学基金;
关键词
sewage source; heat pump; building heating and cooling; special sewage heat exchanger; energy saving; WATER; PERFORMANCE;
D O I
10.3390/buildings13051342
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Heat pump technology can extract low-level heat energy from urban sewage to heat or cool buildings, which can alleviate the two major problems of energy shortage and environmental pollution to a certain extent. This paper introduces the principle of wastewater source heat pump technology and summarizes the current common system forms and their key core technologies. The proposed special heat transfer technology for sewage can effectively solve the problem of blockage and corrosion in the process of sewage heat transfer. Taking the system of an office building in Qingdao as an example, the system design parameter is introduced in detail. The operation monitoring of the heating and air conditioning seasons of this project was completed through a data collection system, and various performance parameters of the system were studied and analyzed. The data was obtained using measured data from one year of system operation. The testing results show that the sewage temperature of the heat pump system in winter is approx. 13.5 degrees C, the hot water supply temperature is approx. 50 degrees C, the average COP of the unit is 3.95, and the average COP of the system is 2.96. The calculation results show that the heating energy consumption of the heat pump unit is only 50.81% of that of a traditional heating mode coal-fired boiler and 57.57% of that of an air source heat pump system. In summer, the sewage temperature is approx. 22 degrees C, the cold-water supply temperature is approx. 5.5 degrees C, the average COP of the unit is 4.45, and the average COP of the system is 3.25. The cooling energy consumption of the heat pump system is 79.39% of the energy consumption of the traditional chiller and 61.56% of the cooling energy consumption of the air source heat pump system. This shows that the sewage source heat pump system has a remarkable energy-saving effect.
引用
收藏
页数:19
相关论文
共 50 条
  • [21] Air Source Heat Pump Energy Storage Heating System for Smart Building
    Chen Xing-chi
    Zhang Xiao-jing
    Zhao Hai
    PROCEEDINGS OF THE 28TH CHINESE CONTROL AND DECISION CONFERENCE (2016 CCDC), 2016, : 3635 - 3639
  • [22] Heat Pump Performance Design for Heating System in the Building
    Seckova, Slavka
    Martins, Florinda F.
    Janicek, Frantisek
    Smitkova, Miroslava Farkas
    Packa, Juraj
    Perny, Milan
    2024 24TH INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING, EPE 2024, 2024, : 192 - 197
  • [23] Application of heat pump in combined heat and power central heating system and exergy analysis
    Jiang, Zhouming
    Li, Yajun
    ASIA-PACIFIC JOURNAL OF CHEMICAL ENGINEERING, 2019, 14 (03)
  • [24] Thermodynamic analysis of building heating or cooling using the soil as heat reservoir
    Costa, V. A. F.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2006, 49 (21-22) : 4152 - 4160
  • [25] Energy and Cost Analysis of an Integrated Photovoltaic and Heat Pump Domestic System Considering Heating and Cooling Demands
    Arenas-Larranaga, Mikel
    Santos-Mugica, Maider
    Alonso-Ojanguren, Laura
    Martin-Escudero, Koldobika
    ENERGIES, 2023, 16 (13)
  • [26] Comprehensive exergy analysis of a ground-source heat pump system for both building heating and cooling modes
    Bi, Yuehong
    Wang, Xinhong
    Liu, Yun
    Zhang, Hua
    Chen, Lingen
    APPLIED ENERGY, 2009, 86 (12) : 2560 - 2565
  • [27] Study on the Simulation of Heat Pump Heating and Cooling Systems to Hospital Building
    Choi, Young Don
    Han, Seong Ho
    Cho, Sung Hwan
    Kim, Du Sung
    Um, Chul Jun
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2008, 32 (04) : 275 - 282
  • [28] A study on the design and analysis of a heat pump heating system using wastewater as a heat source
    Baek, NC
    Shin, UC
    Yoon, JH
    SOLAR ENERGY, 2005, 78 (03) : 427 - 440
  • [29] Experimental study on viscosity characteristic of sewage in urban untreated sewage source heat pump system
    吴学慧
    张承虎
    赵明明
    孙德兴
    Journal of Harbin Institute of Technology(New series), 2010, (01) : 82 - 84
  • [30] Experimental study on viscosity characteristic of sewage in urban untreated sewage source heat pump system
    吴学慧
    张承虎
    赵明明
    孙德兴
    Journal of Harbin Institute of Technology, 2010, 17 (01) : 82 - 84