Numerical study on the airflow characteristics and smoke control condition in stair area of subway stations

被引:2
|
作者
Chen, Junfeng [1 ]
Li, Guoqin [2 ]
Pan, Rongliang [1 ]
Long, Zeng [1 ]
Zhong, Maohua [1 ,3 ]
机构
[1] Tsinghua Univ, Inst Publ Safety Res, Dept Engn Phys, Beijing 100084, Peoples R China
[2] Beijing Urban Construct Design & Dev Grp Co Ltd, Beijing 100034, Peoples R China
[3] Tsinghua Univ, Ltd Joint Res Ctr Urban Disaster Prevent & Safety, Dept Engn Phys, Beijing Urban Construct Design & Dev Grp Co, Beijing 100084, Peoples R China
来源
基金
中国国家自然科学基金;
关键词
Subway station; Stair; Fire smoke; Airflow; Mechanical ventilation; VENTILATION MODE; VIRTUAL ORIGINS; SMALL OPENINGS; FIRE; PLATFORM; OPTIMIZATION; TEMPERATURE; EMERGENCY; TRAIN;
D O I
10.1016/j.jobe.2024.108577
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
As the key facility connecting different floors in subway stations, the smoke control in the stair area has been one of the most important goals of fire protection design. But the detailed airflow field and smoke spread process are rarely discussed. With numerical simulation, this work investigated the airflow velocity distribution and critical condition for smoke control in two critical openings of the stair area, which include the opening beneath the ceiling screen and the opening on the top of the stair. The results indicate that (1) In spatial dimension, the airflow velocity distribution shows a nonuniformity within each opening and a difference between two openings. (2) In the temporal dimension, the airflow velocity shows a normal distribution characteristic. The strong turbulence leads to a dynamic airflow field with an unstable smoke spread process. (3) For the critical opening beneath the ceiling screen, the airflow velocity is dominated by thermal buoyancy or inertia force in different areas. The practical smoke control criterion is to ensure the smoke layer is higher than the edge of the ceiling screen. (4) For the critical opening on the top of the stair, airflow velocity shows an exponential decay distribution. The critical condition could be predicted with a virtual fire source within the stair. This work hopes to present the necessity of dynamic and microscopic modeling of the airflow - smoke flow interaction for an accurate prediction of the smoke control condition in the stair area of subway stations.
引用
收藏
页数:19
相关论文
共 50 条
  • [11] Ridership patterns at subway stations of Seoul capital area and characteristics of station influence area
    Kim, Mi-Kyeong
    Kim, Sang-Pil
    Heo, Joon
    Sohn, Hong-Gyoo
    KSCE JOURNAL OF CIVIL ENGINEERING, 2017, 21 (03) : 964 - 975
  • [12] Smoke movement tests in subway stations actually in service -smoke movement characteristics in center platform stations in the early stage of a fire-
    Moriyama, Shuji
    Hasemi, Yuji
    Okazawa, Naomi
    Nam, Dong-Gun
    Ding, Wenting
    Bulletin of Japan Association for Fire Science and Engineering, 2006, 56 (02) : 23 - 35
  • [13] Ridership patterns at subway stations of Seoul capital area and characteristics of station influence area
    Mi-Kyeong Kim
    Sang-Pil Kim
    Joon Heo
    Hong-Gyoo Sohn
    KSCE Journal of Civil Engineering, 2017, 21 : 964 - 975
  • [14] Seismic Response Characteristics of Subway Stations in the Jinan Area: An Experimental and Computational Approach
    Liu, Zhenghao
    Ma, Xianfeng
    Zhang, Haihua
    Song, Qingwen
    Chen, Yuning
    Ma, Chiyuan
    JOURNAL OF EARTHQUAKE ENGINEERING, 2025,
  • [15] Study on Airflow Characteristics of Train Induced by Piston Effect in Subway Tunnel
    Liu, Wanfu
    Luo, Peng
    Qi, Wuqin
    Lu, Shichang
    Cui, Haihao
    4TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY RESOURCES AND ENVIRONMENT ENGINEERING, 2019, 237
  • [16] Numerical study on the influence of subway platform air curtains on smoke diffusion
    Zhang, Tianhong
    Han, Rubing
    CASE STUDIES IN THERMAL ENGINEERING, 2023, 50
  • [17] Study of Combined Simulation of Smoke Control and Evacuation in Subway Station
    Zhu, Wei
    You, Fangli
    Wu, Fang
    THEORY AND PRACTICE OF RISK ANALYSIS AND CRISIS RESPONSE, PROCEEDINGS, 2008, : 572 - +
  • [18] A Study on the Influence of Rail Top Smoke Exhaust and Tunnel Smoke Exhaust on Subway Fire Smoke Control
    Dong, Sihui
    Wang, Kang
    Jia, Chenxu
    SUSTAINABILITY, 2022, 14 (07)
  • [19] Experimental and numerical simulation study on airflow distribution of a subway based on transformation of a bladeless fan
    Wu C.
    Liu S.
    Chen T.
    Ji W.
    Zhang S.
    Chen H.
    Zhongnan Daxue Xuebao (Ziran Kexue Ban)/Journal of Central South University (Science and Technology), 2023, 54 (01): : 81 - 88
  • [20] SMOKE CONTROL IN HOSPITALS - A NUMERICAL STUDY
    HAGGLUND, B
    WICKSTROM, U
    FIRE SAFETY JOURNAL, 1990, 16 (01) : 53 - 63