A Novel Protection Strategy for Single Pole-to-Ground Fault in Multi-Terminal DC Distribution Network

被引:3
|
作者
Yang, Ruixiong [1 ]
Fang, Ke [2 ]
Chen, Jianfu [1 ]
Chen, Yong [1 ]
Liu, Min [2 ]
Meng, Qingxu [2 ]
机构
[1] Guangdong Power Grid Co Ltd, DC Power Distribut & Consumpt Technol Res Ctr, Zhuhai 519099, Peoples R China
[2] Jinan Univ, Energy & Elect Res Ctr, Zhuhai 519070, Peoples R China
关键词
distribution network; single pole-to-ground (SPG) fault; multi-terminal DC; MMC; protection strategy; current derivative; DESIGN;
D O I
10.3390/en16062921
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The single pole-to-ground (SPG) fault is one of critical failures which will have a serious impact on the stable operation of the multi-terminal DC distribution network based on the modular multilevel converter (MMC). It is very significant to analyze fault characteristics for detecting faults and protection design. This paper established the DC SPG fault model, which showed that in the presence of a reactor, the short-circuit current was reduced from 2.3 kA to 1 kA at 6 ms after the fault. Then, a novel SPG fault protection strategy was proposed, which detected the current derivative in connection transformer grounding branch. When the value increases past the threshold of current derivative, small resistance was switched on to increase fault current. Thus, the reliability of differential protection was enhanced. Compared with the traditional protection method, the proposed method does not need communication, and improved the speed of protection. Finally, the simulation model was established in PSCAD/EMTDC. The model included three converter stations: T1, T2 and T3. Among them, T1 outputs power, and T2 and T3 receive power. The results of RTDS showed that the DC circuit breaker operated within 3 ms, the three-port circuit breaker worked within 50 ms, which proves that the proposed strategy was effective. At this time, the system switched from the T1-T2-T3 three-terminal networking operation mode to the T1-T2 two-terminal hand-in-hand operation mode. Since the T3 terminal no longer received power, the transmission power of the T1 terminal decreased, and the received power of the T2 terminal remained unchanged.
引用
收藏
页数:16
相关论文
共 50 条
  • [41] Online Parameter Estimation for Fault Identification in Multi-Terminal DC Distribution Grids
    Wang, Ting
    Liang, Liliuyuan
    Feng, Xinrang
    Ponci, Ferdinanda
    Monti, Antonello
    ENERGIES, 2021, 14 (18)
  • [42] Hierarchical power flow control strategy and algorithm for multi-terminal interconnected AC/DC distribution network
    Peng K.
    Xian R.
    Zhang X.
    Chen Y.
    Lu H.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2016, 40 (14): : 72 - 77
  • [43] Optimization of Limiting Reactors Design for DC Fault Protection of Multi-terminal HVDC Networks
    Kontos, E.
    Rodrigues, S.
    Pinto, R. Teixeira
    Bauer, P.
    2014 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2014, : 5347 - 5354
  • [44] DC protection of a multi-terminal HVDC network featuring offshore wind farms
    Parker, Max
    Finney, Stephen
    Holliday, Derrick
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 2195 - 2201
  • [45] Pole-to-ground fault ride through strategy for half-/full-bridge hybrid MMC-based radial multi-terminal HVDC systems with low-impedance grounded
    Lin, Lei
    He, Zhen
    Hu, Jiabing
    He, Zhiyuan
    Xu, Kecheng
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (04) : 1038 - 1044
  • [46] Multi-terminal Flexible DC control and protection cooperation based on fault current limiting
    Xue, Shimin
    Zhang, Haoming
    Liu, Baibing
    Zhang, Junting
    Yin, Wenxiang
    Li, Botong
    Electric Power Systems Research, 2025, 245
  • [47] Operation and control of a Multi-terminal DC Network
    Pinto, R. Teixeira
    Rodrigues, Silvio
    Bauer, P.
    Pierik, J.
    2013 IEEE ECCE ASIA DOWNUNDER (ECCE ASIA), 2013, : 474 - 480
  • [48] Line Protection for Multi-terminal Flexible DC Distribution System Based on Control and Protection Coordination
    Wang C.
    Jia K.
    Bi T.
    Zhao Q.
    Feng T.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (08): : 2559 - 2567
  • [49] Dc Fault Protection of Multi-Terminal VSC-HVDC System with Hybrid Dc Circuit Breaker
    Li, Yalong
    Shi, Xiaojie
    Wang, Fred
    Tolbert, Leon M.
    Liu, Jin
    2016 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2016,
  • [50] A modified DC fault protection scheme for multi-terminal HVDC grid based on fault current limiters
    Tang, Song
    Jia, Guanlong
    Zhang, Chenghao
    Chen, Min
    2019 4TH IEEE WORKSHOP ON THE ELECTRONIC GRID (EGRID), 2019, : 235 - 239