Performance comparison of module layout for the mechanical draft wet cooling tower br

被引:4
|
作者
Deng, Weipeng [1 ]
Sun, Fengzhong [1 ]
Wang, Yuhao [1 ]
Zhang, Zhihui [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
关键词
Plume abatement; Water saving; Rhombus module; Rectangular module; Mechanical draft wet cooling tower; PLUME ABATEMENT; THERMAL PERFORMANCE; REDUCE WATER; OPTIMIZATION;
D O I
10.1016/j.icheatmasstransfer.2022.106600
中图分类号
O414.1 [热力学];
学科分类号
摘要
The arrangement of modules with the plume abatement and water saving functions has a great impact on the performance of the mechanical draft wet cooling tower (MCT). The rectangular and rhombus modules are compared by the experiment in this study. The layout of modules in the MCT is divided into single-sided layout and double-sided layout. The ability of MCT to plume abatement, water saving rate, and thermal performance are analyzed. Results show that the MCT with rhombus modules has better ventilation capacity, and that is increased by at least 7.6% compared with the rectangular module. The water saving rate of the rhombus module is at least 5.6% higher than that of installing a rectangular module. After the rhombus module is installed, the temperature and moisture content of air discharged from the MCT decrease amount more than that of the rectangular module, and the plume abatement ability of the rhombic module is better than that of the rectangular module. Compared with the rectangular module, the water temperature drop with the rhombus module is increased by 0.2 degrees C on the single-sided layout module and 0.5 degrees C on the double-sided layout module
引用
收藏
页数:12
相关论文
共 50 条
  • [31] Optimization of guide vane positions in bended inflow of mechanical draft wet-cooling tower
    Klimanek, Adam
    Musiol, Tomasz
    Stechman, Adam
    ARCHIVES OF THERMODYNAMICS, 2011, 32 (03) : 263 - 272
  • [32] Comparison on the cooling performance of mechanical draft dry cooling towers pre-cooled with nozzle spray and wet medium
    Zhao, Cuilin
    Wang, Mingwei
    Gao, Qi
    Cheng, Shen
    Liu, Zhilan
    Geng, Zhe
    Zhang, Shuzhen
    He, Suoying
    Qi, Jianhui
    Han, Kuihua
    Gao, Ming
    Shi, Yuetao
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 156 : 298 - 314
  • [33] EXPERIMENTAL AND NUMERICAL ANALYSIS OF THE FORCED DRAFT WET COOLING TOWER
    Lafta, Noor Samir
    Kareem, Fadhil Abdulrazzaq
    Ghafur, Maha H.
    JOURNAL OF THERMAL ENGINEERING, 2023, 9 (01):
  • [34] Experimental and numerical analysis of the forced draft wet cooling tower
    Lafta, Noor Samir
    Kareem, Fadhil Abdulrazzaq
    Ghafur, Maha
    JOURNAL OF THERMAL ENGINEERING, 2023, 9 (02): : 518 - 529
  • [35] A feedback model to predict parameters for controlling the performance of a mechanical draft cooling tower
    Singh, Kuljeet
    Das, Ranjan
    APPLIED THERMAL ENGINEERING, 2016, 105 : 519 - 530
  • [36] Impact mechanism of different fill layout patterns on the cooling performance of the wet cooling tower with water collecting devices
    Lyu, Dongqiang
    Sun, Fengzhong
    Zhao, Yuanbin
    APPLIED THERMAL ENGINEERING, 2017, 110 : 1389 - 1400
  • [37] Freeze protection performance of natural draft wet cooling tower with different partition water distributions
    Yuan, Wei
    Zuo, Simeng
    Zhou, Jun
    Zhang, Qian
    Zhang, Lei
    APPLIED THERMAL ENGINEERING, 2025, 260
  • [38] Three-dimensional numerical study on thermal performance in a natural draft wet cooling tower
    Zheng, Shuihua
    Jin, Tai
    Fan, Jianren
    ADVANCES IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 614-615 : 169 - +
  • [39] CFD MODELING ANALYSIS OF MECHANICAL DRAFT COOLING TOWER
    Lee, Si Y.
    Bollinger, James S.
    Garrett, Alfred J.
    Koffman, Larry D.
    HT2008: PROCEEDINGS OF THE ASME SUMMER HEAT TRANSFER CONFERENCE - 2008, VOL 2, 2009, : 485 - 493
  • [40] Water Consumption Comparison Between a Natural Draft Wet Cooling Tower and a Natural Draft Hybrid Cooling TowerAn Annual Simulation for Luoyang Conditions
    Xia, Lin
    Li, Jishun
    Ma, Wei
    Gurgenci, Hal
    Guan, Zhiqiang
    Wang, Pei
    HEAT TRANSFER ENGINEERING, 2017, 38 (11-12) : 1034 - 1043