Thermal fatigue analysis of district heating pipeline under variable frequency regulation of circulating water pump

被引:1
|
作者
Liu, Fuqiang [1 ]
Song, Chongfang [1 ]
Pan, Wuxuan [1 ]
Wang, Guowei [2 ]
Zhang, Huijie [1 ]
Lei, Yonggang [1 ]
机构
[1] Taiyuan Univ Technol, Taiyuan, Peoples R China
[2] Taiyuan Municipal Engn Design & Res Inst, Taiyuan 030000, Peoples R China
关键词
District-heating pipelines; Rainflow counting method; Fatigue cycle times; Variable frequency regulation of circulating; water pump;
D O I
10.1016/j.applthermaleng.2024.122535
中图分类号
O414.1 [热力学];
学科分类号
摘要
The use of variable frequency control of circulating water pumps is an important energy-saving operation strategy to cope with changes in heating load. However, it can lead to low cycle fatigue failure of the pipeline when the cyclic stress generated by frequent water temperature fluctuations reaches the fatigue limit. Accurately prediction of the maximum total temperature difference cycles of pipelines is of great significance for ensuring the safe operation of centralized heating networks with frequent water flow rates regulation. Based on the actual operating data of 360,000 heat exchange stations, the stress amplitude and corresponding temperature difference cycles of pipelines at different operating temperatures were calculated, the maximum total temperature difference cycle of pipelines for 30 years was predicted. We calculated the stress limit of pipelines at different safety levels, and evaluated the impact of temperature on the fatigue life of pipelines under different building types and working conditions. The results show that the number of temperature difference cycles in primary network pipelines is three times that in secondary network pipelines, and the number of temperature difference cycles in pipelines of different building types varies greatly. The lower the operating temperature of the pipeline, the smaller the temperature difference fluctuation and the greater the contribution of pipeline fatigue damage when regulating the variable flow rate of the circulating water pump. The stress limit values of primary network supply and return water pipelines are 650 MPa and 759 MPa, while the stress limit values of secondary network supply and return water pipelines are 811 MPa and 946 MPa.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] A novel thermal water pump for circulating water in a solar water heating system
    Roonprasang, Natthaphon
    Namprakai, Pichai
    Pratinthong, Naris
    APPLIED THERMAL ENGINEERING, 2009, 29 (8-9) : 1598 - 1605
  • [2] Thermal Fatigue Analysis of the Secondary Network of District Heating Systems in China
    Zan, Zhuoyu
    Song, Chongfang
    Jing, Shenglan
    Zhang, Jianwei
    Lei, Yonggang
    Wang, Fei
    JOURNAL OF PIPELINE SYSTEMS ENGINEERING AND PRACTICE, 2020, 11 (03)
  • [3] Thermal-Fatigue Analysis of District-Heating Pipelines in China
    Jing, Shenglan
    Zan, Zhuoyu
    Song, Chongfang
    Zhang, Jianwei
    Lei, Yonggang
    Wang, Fei
    Li, Xinyi
    JOURNAL OF PIPELINE SYSTEMS ENGINEERING AND PRACTICE, 2020, 11 (02)
  • [4] Variable frequency regulation plan analysis of the pump units in Huinanzhuang Pump Station
    Yang, Wei
    Wang, Fujun
    Xiao, Ruofu
    Yao, Zhifeng
    Shuili Xuebao/Journal of Hydraulic Engineering, 2015, 46 (07): : 853 - 858
  • [5] Application and Economic Analysis of Water Jet Pump in New District Heating System
    Yin Peng
    Hu Wenju
    Li Deying
    Li Xiaoyu
    Zeng Xiping
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 996 - 1003
  • [6] Failure Analysis of Welded type 304 in Cooling Water Pipeline of District Heating System
    Jeong, Joon-Cheol
    Kim, Woo-Cheol
    Kim, Kyung Min
    Sohn, Hong-Kyun
    Kim, Jung-Gu
    Lee, Soo-Yeol
    Kim, Heesan
    CORROSION SCIENCE AND TECHNOLOGY-KOREA, 2020, 19 (06): : 296 - 301
  • [7] Energy Performance Analysis of an Integrated Distributed Variable-Frequency Pump and Water Storage System for District Cooling Systems
    Zhang, Yichi
    Chen, Chuanxin
    Xia, Jianjun
    APPLIED SCIENCES-BASEL, 2017, 7 (11):
  • [8] Statistical Analysis of Circulating Water Quality Parameters under Variable-Frequency Vertical Electromagnetic Fields
    He, Fang
    Wang, Jianguo
    PROCESSES, 2018, 6 (10):
  • [9] COMPARATIVE ANALYSIS OF THERMODYNAMIC PERFORMANCES OF HEAT PUMP HEATING AND EXPANDER HEATING UNDER VARIABLE WORKING CONDITIONS
    He X.
    Zhao Z.
    Zheng L.
    Yu Z.
    Lu S.
    Gu Y.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (02): : 334 - 343
  • [10] Transient Characteristic Analysis of Variable Frequency Speed Regulation of Axial Flow Pump
    Zuo, Zilei
    Tan, Linwei
    Shi, Weidong
    Chen, Cheng
    Ye, Jincheng
    Francis, Egbo Munachi
    SUSTAINABILITY, 2022, 14 (18)