Vibration of a Header Wire Due to Dynamic Short Circuit Forces.

被引:0
|
作者
Aula, Antti [1 ]
机构
[1] Pohjolan Voima Oy, Oulu, Finl, Pohjolan Voima Oy, Oulu, Finl
来源
Sahko | 1985年 / 58卷 / 08期
关键词
COMPUTER AIDED ANALYSIS - ELECTRIC FAULT CURRENTS - Short Circuit Currents;
D O I
暂无
中图分类号
学科分类号
摘要
In addition to the nominal current and voltage, one of the most important factors in the dimensioning and selection of equipment for a switching station in an electric power plant is the short circuit current which occurs during a fault. The equipment and structures must be of sufficient strength to withstand, both thermally and mechanically, the short circuit current present in the network, throughout its period of influence. The mechanical performance of a wire-form busbar under short circuit conditions is examined, and a general computer programme suitable for the analysis of wire vibration is presented, together with an example.
引用
收藏
页码:12 / 14
相关论文