Analysis of secondary arc extinction characteristics on UHV line

被引:0
|
作者
Lin, Xin [1 ]
He, Baina [1 ]
Xu, Jianyuan [1 ]
机构
[1] Shenyang University of Technology, School of Electrical Engineering, Shenyang 110023, China
来源
关键词
D O I
暂无
中图分类号
学科分类号
摘要
This paper presents the mechanism theory of secondary arc current generated in ultra-high-voltage (UHV) power transmission system and main suppressing method. The mathematic representations of recovery voltage and secondary arc current can be drawn by circuit principle. Utilizing MATLAB to write the program, the values of recovery voltage and secondary arc current can be obtained. It can simulate the whole circuit by SIMULINK and gets the waveforms of them. The effect of secondary arc suppression at the time when the high speed grounding switch (HSGS) is adopted is studied. The mechanism of secondary arc restriction by HSGS is analyzed. The magnitudes of the secondary arc current and recovery voltage in arc path are obviously reduced after installing HSGS on line. That in turn reduces the extinction time of the secondary arc and assures successful single-phase auto-reclosing.
引用
收藏
页码:7 / 9
相关论文
共 50 条
  • [21] Impacts of operating conditions and line parameters on secondary arc extinction of single-phase autoreclosures
    Luxenburger, Rainer
    Schegner, Peter
    2005 International Conference on Future Power Systems (FPS), 2005, : 253 - 259
  • [22] Influence of Coordinate Controllable Neutral Reactors on UHV Secondary Arc Current
    Wang, Z. J.
    Yin, Z. D.
    Wang, M. M.
    ICEET: 2009 INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT TECHNOLOGY, VOL 2, PROCEEDINGS, 2009, : 156 - 159
  • [23] Research on a novel suppressing methodology for secondary arc extinction based on an impedance paralleled to line circuit breaker
    Li, Qingmin
    Sun, Qiuqin
    Lou, Jie
    Zhang, Li
    Cong, Haoxi
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2014, 24 (02): : 281 - 296
  • [24] Secondary arc extinction by high speed grounding switches
    Han, Yanhua
    Fan, Yue
    Shi, Wei
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2000, 34 (08): : 14 - 17
  • [25] The Experimental Research of Secondary Arc in 1000kV UHV Systems in China
    He, Yanmiao
    Li, Wei
    Yang, Kun
    Cui, Boyuan
    Zhang, Pengfei
    Cao, Rongjiang
    Lin, Jiming
    Yuan, Yichao
    2015 3RD INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2015, : 161 - 165
  • [26] Study on Compensation for Secondary Arc Current on UHV Double-Circuit Lines
    Chen, Lei
    Liu, Haijun
    Wu, Ming
    Wei, Delin
    Niu, Meng
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [27] Consistency analysis between the electric field and audible noise caused by UHV test line and UHV transmission line
    Lu, Yao
    Gan, Zhe-Yuan
    Chen, Yu-Chao
    Li, Ni
    Zha, Xian-Guang
    Gaodianya Jishu/High Voltage Engineering, 2011, 37 (02): : 354 - 360
  • [28] Dynamic Secondary Arc Analysis and Simulation Research Under Different Line Model
    Zhou, Lixia
    Yin, Zhongdong
    Xiao, Xiangning
    Tan, Yueting
    2008 IEEE ASIA PACIFIC CONFERENCE ON CIRCUITS AND SYSTEMS (APCCAS 2008), VOLS 1-4, 2008, : 240 - +
  • [29] Arc effect on single-phase reclosing time of an UHV power transmission line
    Dudurych, I
    Gallagher, T
    Rosolowski, E
    2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, 2004, : 581 - 581
  • [30] Arc effect on single-phase reclosing time of a UHV power transmission line
    Dudurych, IM
    Gallagher, TJ
    Rosolowski, E
    IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) : 854 - 860