Impacts of Increasing Temperature and Relative Humidity in Air-Cooled Tropical Data Centers

被引:0
|
作者
Van Le, Duc [1 ]
Zhou, Jing [2 ]
Wang, Rongrong [1 ]
Tan, Rui [1 ]
Duan, Fei [2 ]
机构
[1] Nanyang Technol Univ, Sch Comp Sci & Engn, Singapore 639798, Singapore
[2] Nanyang Technol Univ, Sch Mech & Aerosp Engn, Singapore 639798, Singapore
来源
基金
新加坡国家研究基金会;
关键词
Cooling; Servers; Temperature measurement; Reliability; Temperature distribution; Costs; Green computing; Data centers; temperature; humidity; energy usage; total cost of ownership analysis; DESIGN;
D O I
10.1109/TSUSC.2024.3379550
中图分类号
TP3 [计算技术、计算机技术];
学科分类号
0812 ;
摘要
Data centers (DCs) are power-intensive facilities which use a significant amount of energy for cooling the servers. Increasing the temperature and relative humidity (RH) setpoints is a rule-of-thumb approach to reducing the DC energy usage. However, the high temperature and RH may undermine the server's reliability. Before we can choose the proper temperature and RH settings, it is essential to understand how the temperature and RH setpoints affect the DC power usage and server's reliability. To this end, we constructed and experimented with an air-cooled DC testbed in Singapore, which consists of a direct expansion cooling system and 521 servers running real-world application workloads. This paper presents the key measurement results and observations from our 11-month experiments. Our results suggest that by operating at a supply air temperature setpoints of 29(degrees)C, our testbed achieves substantial cooling power saving with little impact on the server's reliability. Furthermore, we present a total cost of ownership (TCO) analysis framework which guides settings of the temperature and RH for a DC. Our observations and TCO analysis framework will be useful to future efforts in building and operating air-cooled DCs in tropics and beyond.
引用
收藏
页码:790 / 802
页数:13
相关论文
共 50 条
  • [21] Retrofitting of an air-cooled data center for energy efficiency
    Kuzay, Mustafa
    Dogan, Aras
    Yilmaz, Sibel
    Herkiloglu, Oguzhan
    Atalay, Ali Serdar
    Cemberci, Atilla
    Yilmaz, Cagatay
    Demirel, Ender
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 36
  • [22] Results of data quality assurance of surface air temperature and relative humidity
    Araya Lopez, Jose Luis
    TECNOLOGIA EN MARCHA, 2011, 24 (01): : 33 - 49
  • [23] Data Based Modeling Approach for Greenhouse Air Temperature and Relative Humidity
    Ntoula, E.
    Katsoulas, N.
    Kittas, C.
    Youssef, A.
    Exadaktylos, V.
    Berckmans, D.
    INTERNATIONAL SYMPOSIUM ON ADVANCED TECHNOLOGIES AND MANAGEMENT TOWARDS SUSTAINABLE GREENHOUSE ECOSYSTEMS: GREENSYS2011, 2012, 952 : 67 - 72
  • [24] Determination of aerosol deliquescence and crystallization relative humidity for energy saving in free-cooled data centers
    L. Ferrero
    L. D’Angelo
    G. Rovelli
    G. Sangiorgi
    M. G. Perrone
    M. Moscatelli
    M. Casati
    V. Rozzoni
    E. Bolzacchini
    International Journal of Environmental Science and Technology, 2015, 12 : 2777 - 2790
  • [25] Determination of aerosol deliquescence and crystallization relative humidity for energy saving in free-cooled data centers
    Ferrero, L.
    D'Angelo, L.
    Rovelli, G.
    Sangiorgi, G.
    Perrone, M. G.
    Moscatelli, M.
    Casati, M.
    Rozzoni, V.
    Bolzacchini, E.
    INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2015, 12 (09) : 2777 - 2790
  • [26] Reducing the condensing temperature to improve the efficiency of air-cooled chillers
    Fu, WY
    Kwok, TC
    PROCEEDINGS OF THE 3RD INTERNATIONAL SYMPOSIUM ON HEAT TRANSFER ENHANCEMENT AND ENERGY CONSERVATION, VOLS 1 AND 2, 2004, : 180 - 185
  • [27] Simulation of floating condensing temperature control for air-cooled chillers
    Yu, Fu Wing
    Chan, Kwok Tai
    PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 55 - +
  • [28] Field test of cooling systems in two air-cooled data centers: Various regions, air distributions and evaporative cooling technologies
    Jing, Yang
    Xie, Linfeng
    Li, Fangling
    Zhan, Ziyang
    Wang, Zhenghua
    Yang, Fan
    Fan, Jiale
    Zhu, Zihan
    Zhang, Hao
    Zhao, Ce
    Shi, Zhuofan
    Jiang, Haihua
    Xie, Xiaoyun
    Jiang, Yi
    APPLIED THERMAL ENGINEERING, 2024, 248
  • [29] Thermally Aware, Energy-Based Load Placement in Open-Aisle, Air-Cooled Data Centers
    Demetriou, Dustin W.
    Khalifa, H. Ezzat
    JOURNAL OF ELECTRONIC PACKAGING, 2013, 135 (03)
  • [30] On energy efficient flow provisioning in air-cooled data servers
    Lucchese, Riccardo
    Johansson, Andreas
    CONTROL ENGINEERING PRACTICE, 2019, 89 : 103 - 112