Determination of aerosol deliquescence and crystallization relative humidity for energy saving in free-cooled data centers

被引:18
|
作者
Ferrero, L. [1 ]
D'Angelo, L. [1 ]
Rovelli, G. [1 ]
Sangiorgi, G. [1 ]
Perrone, M. G. [1 ]
Moscatelli, M. [1 ]
Casati, M. [1 ]
Rozzoni, V. [1 ]
Bolzacchini, E. [1 ]
机构
[1] Univ Milano Bicocca, Dept Earth & Environm Sci, POLARIS Res Ctr, I-20126 Milan, Italy
关键词
Conductivity; Aerosol chamber; Hygroscopicity; Models; Energy; Carbon footprint; CHEMICAL-COMPOSITION; VERTICAL PROFILES; PARTICLE-SIZE; ATMOSPHERIC CORROSION; PARTICULATE MATTER; PHASE-TRANSITIONS; MIXING LAYER; MILAN; MODEL; DEGRADATION;
D O I
10.1007/s13762-014-0680-2
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study examines an innovative application of the aerosol deliquescence and crystallization determination, for corrosion prevention and energy-saving strategies in free-cooled data centers. Aerosol deliquescence and crystallization were investigated by combining standardized aerosol sampling techniques (i.e. EN-14907) with the assessment of the electrical effects of aerosol, while varying relative humidity within a specially designed aerosol exposure chamber. Aerosol samples collected in the Po Valley (Northern Italy) were analysed; a clearly defined hysteresis cycle (deliquescence and crystallization at 60.5 +/- A 0.8 and 47.9 +/- A 0.7 % of RH, respectively) was found. Results were applied to a data center designed for the Italian National Oil and Gas Company, making it possible to identify a critical area for direct free cooling at this data center. As a result, aerosol hydration was avoided (thus preventing aerosol from damaging electrical components) and a large amount of energy saved (using free cooling instead of air-conditioning); the potential energy saving achieved in this way was 79 % (compared to the energy consumption of a traditional air-conditioning system): 215 GWh of energy was saved, and 78 fewer kt of equivalent CO2 was emitted per year. Moreover, in order to evaluate whether a real-time estimation of the aerosol hydration state within a data center could be performed, measured deliquescence and crystallization were compared through simulations performed using three different models: two thermodynamic models for deliquescence and a parametric model for crystallization. The results obtained tend to converge in terms of deliquescence, whereas in the case of crystallization, they failed to effectively simulate experimental aerosol behaviour.
引用
收藏
页码:2777 / 2790
页数:14
相关论文
共 9 条
  • [1] Determination of aerosol deliquescence and crystallization relative humidity for energy saving in free-cooled data centers
    L. Ferrero
    L. D’Angelo
    G. Rovelli
    G. Sangiorgi
    M. G. Perrone
    M. Moscatelli
    M. Casati
    V. Rozzoni
    E. Bolzacchini
    International Journal of Environmental Science and Technology, 2015, 12 : 2777 - 2790
  • [2] Control of Air Free-Cooled Data Centers in Tropics via Deep Reinforcement Learning
    Duc Van Le
    Liu, Yingbo
    Wang, Rongrong
    Tan, Rui
    Wong, Yew-Wah
    Wen, Yonggang
    BUILDSYS'19: PROCEEDINGS OF THE 6TH ACM INTERNATIONAL CONFERENCE ON SYSTEMS FOR ENERGY-EFFICIENT BUILDINGS, CITIES, AND TRANSPORTATION, 2019, : 306 - 315
  • [3] Impacts of Increasing Temperature and Relative Humidity in Air-Cooled Tropical Data Centers
    Van Le, Duc
    Zhou, Jing
    Wang, Rongrong
    Tan, Rui
    Duan, Fei
    IEEE TRANSACTIONS ON SUSTAINABLE COMPUTING, 2024, 9 (05): : 790 - 802
  • [4] A data-assisted first-principle approach to modeling server outlet temperature in air free-cooled data centers
    Liu, Yingbo
    Duc Van Le
    Tan, Rui
    FUTURE GENERATION COMPUTER SYSTEMS-THE INTERNATIONAL JOURNAL OF ESCIENCE, 2022, 129 : 225 - 235
  • [5] Radiative free cooling for energy and water saving in data centers
    Aili, Ablimit
    Long, Wenjun
    Cao, Zhiwei
    Wen, Yonggang
    APPLIED ENERGY, 2024, 359
  • [6] Free cooling technologies for data centers: energy saving mechanism and applications
    Zhang, Yin
    Wei, Zhiyuan
    Zhang, Mingshan
    LEVERAGING ENERGY TECHNOLOGIES AND POLICY OPTIONS FOR LOW CARBON CITIES, 2017, 143 : 410 - 415
  • [7] Aerosol Corrosion Prevention and Energy-Saving Strategies in the Design of Green Data Centers
    Ferrero, Luca
    Sangiorgi, Giorgia
    Ferrini, Barbara S.
    Perrone, Maria G.
    Moscatelli, Marco
    D'Angelo, Luca
    Rovelli, Grazia
    Ariatta, Alberto
    Truccolo, Redy
    Bolzacchini, Ezio
    ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2013, 47 (08) : 3856 - 3864
  • [8] Analysis of energy saving potential of air-side free cooling for data centers in worldwide climate zones
    Lee, Kuei-Peng
    Chen, Hsiang-Lun
    ENERGY AND BUILDINGS, 2013, 64 : 103 - 112
  • [9] Experimental Investigation and Energy-saving Analysis of a CO2 Thermosyphon for Free Cooling of Data Centers
    Zhang, Hai-Nan
    Shao, Shuang-Quan
    Tian, Chang-Qing
    Jin, Ting-Xiang
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2017, 38 (09): : 1833 - 1836