Flexible regulation of airport air-conditioning systems: Impact of cooling load variations on temperature stability

被引:0
|
作者
Lin, Lin [1 ,2 ]
Chen, Guodong [1 ]
Wang, Weian [1 ]
Liu, Xiaochen [2 ]
Liu, Xiaohua [2 ]
Zhang, Tao [2 ]
机构
[1] Shanghai Elect Grp Power Transmiss & Distribut Equ, Shanghai 200042, Peoples R China
[2] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
来源
关键词
Flexible regulation; Cooling load variations; Air-conditioning systems; Indoor temperature stability; Renewable energy; DEMAND RESPONSE; FLEXIBILITY; BUILDINGS;
D O I
10.1016/j.jobe.2024.111324
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The integration of renewable energy sources has led to notable supply-demand imbalances due to their intermittent nature. Air-conditioning systems, as significant energy consumers with considerable flexibility, play a crucial role in integrating renewable energy and regulating power systems. This paper delves into the capability of air-conditioning systems in airports to flexibly adjust, particularly examining how varying cooling loads impact indoor temperatures. The energy flexibility of the air-conditioning system is evaluated based on three fundamental cooling load variations (incremental, translational, and discrete), and several evaluation parameters are defined. For areas with smaller cooling load fluctuations, there is a greater adjustment margin, but long adjustment periods should be avoided. For areas with larger fluctuations, the original cooling load curve should be considered in the adjustment strategy. The simulation results show that advancing or delaying the supply by 1 h during peak cooling load periods can ensure indoor temperature stability, and step-type cooling load curves do not adversely affect indoor comfort levels. Practical case studies further demonstrate that utilizing water storage as an active regulation strategy can reduce operational costs by 26 %, and with flexible adjustments, this reduction can increase to 35-54 %. The study offers a framework to optimize air-conditioning flexibility in airports, facilitating better renewable energy integration and grid stability, which holds significant potential to reduce costs and improve energy efficiency, thus contributing to sustainable energy management.
引用
收藏
页数:15
相关论文
共 50 条
  • [41] Flexible flow sensor for large-scale air-conditioning network systems
    Shikida, M.
    Yoshikawa, K.
    Iwai, S.
    Sato, K.
    SENSORS AND ACTUATORS A-PHYSICAL, 2012, 188 : 2 - 8
  • [42] Deep belief network based ensemble approach for cooling load forecasting of air-conditioning system
    Fu, Guoyin
    ENERGY, 2018, 148 : 269 - 282
  • [43] Qualitative analysis of the cooling load in the typical room under continuous and intermittent runnings of air-conditioning
    Zhang, Lili
    Wang, Yating
    Meng, Xi
    Li, Jialun
    Sun, Nan
    Hou, Jiawen
    Long, Enshen
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 405 - 409
  • [44] Research on Air-Conditioning Cooling Load Correction and Its Application Based on Clustering and LSTM Algorithm
    Li, Honglian
    Shang, Li
    Li, Chengwang
    Lei, Jiaxiang
    APPLIED SCIENCES-BASEL, 2023, 13 (08):
  • [45] Key technologies research of load regulation of central air-conditioning based on the demand response
    Ai, Zhen
    Li, Tianyang
    Song, Chencheng
    ADVANCES IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 614-615 : 707 - 711
  • [46] Research on solar high-temperature absorption air-conditioning systems
    Yu, Guoqing
    Tang, Jinhua
    Zou, Zhijun
    PROCEEDINGS OF ISES SOLAR WORLD CONGRESS 2007: SOLAR ENERGY AND HUMAN SETTLEMENT, VOLS I-V, 2007, : 837 - 841
  • [47] Energy performance of air-conditioning systems using an indirect evaporative, cooling combined with a cooling/reheating treatment
    Cianfrini, Claudio
    Corcione, Massimo
    Habib, Emanuele
    Quintino, Alessandro
    ENERGY AND BUILDINGS, 2014, 69 : 490 - 497
  • [48] Experimental investigation of evaporative cooling systems for agricultural storage and livestock air-conditioning in Pakistan
    Hafiz M. U. Raza
    Muhammad Sultan
    Majid Bahrami
    Alamgir A. Khan
    Building Simulation, 2021, 14 : 617 - 631
  • [49] Experimental investigation of evaporative cooling systems for agricultural storage and livestock air-conditioning in Pakistan
    Raza, Hafiz M. U.
    Sultan, Muhammad
    Bahrami, Majid
    Khan, Alamgir A.
    BUILDING SIMULATION, 2021, 14 (03) : 617 - 631
  • [50] Critical Factors in Adopting Cooling Media for Central Air-Conditioning Systems in Hong Kong
    Chan, Kwok Hung
    ARCHITECTURAL ENGINEERING AND DESIGN MANAGEMENT, 2010, 6 (01) : 31 - 47