Simplified calculation for grounding resistance of transmission tower

被引:0
|
作者
Li, Tianwei [1 ]
He, Min [1 ]
Lu, Benchu [1 ]
Cheng, Siyong [1 ]
机构
[1] Guangxi Electric Power Industry Investigation Design and Research Institute, Nanning 530023, Guangxi Zhuang Autonomous Region, China
来源
关键词
Electric grounding - Towers - Electric power transmission;
D O I
暂无
中图分类号
学科分类号
摘要
In the grounding design of high voltage transmission line the empirical formula is often used to calculate the grounding resistance of transmission tower, so the calculation accuracy is just passable. Considering the non-uniformity of the current dispersed from the grounding electrode, a grounding electrode is divided into sections to calculate their self-resistance coefficients and mutual resistance coefficients, thus the grounding resistance of grounding electrode is solved. The number of conductor sections is dependent upon the requirement to computation accuracy, the more the number of the sections, the higher the computational accuracy. Finally, the grounding resistances of grounding electrode usually used for transmission tower, such as radial grounding electrode and double-ring grounding electrode, under different soil resistivity, conductor radii and depths of burying are analyzed.
引用
收藏
页码:170 / 175
相关论文
共 50 条
  • [21] Traditional and alternative grounding system's impedance and resistance measurements of a 138 kV transmission line tower
    Raizer, Adroaldo
    Elias, Emanoel P.
    da Luz, Mauricio V. Ferreira
    Coelho, Vilson L.
    Raupp, Victor M. A.
    Tello, Marcos
    Giannini Junior, Jose M.
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 231
  • [22] Laboratory investigation of impulse characteristics of transmission tower grounding devices
    He, JL
    Zeng, R
    Tu, YP
    Zou, J
    Chen, SM
    Guan, ZC
    IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (03) : 994 - 1001
  • [23] Backflashover simulation of HV transmission lines with concentrated tower grounding
    Gatta, FM
    Geri, A
    Lauria, S
    ELECTRIC POWER SYSTEMS RESEARCH, 2005, 73 (03) : 373 - 381
  • [24] Research on Impulse Impedance Measurement for Grounding Device of Transmission Tower
    Si Wen-Rong
    Fu Chen-Zhao
    Lu Bing-Bing
    Guo Xiang
    Xu Zhi-Bing
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [25] The impulse grounding impedance computation in HVDe transmission line tower
    Li Tian-wei
    Xiang Yang
    Zhao Yu-ming
    2013 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2013,
  • [26] Measurement and Analysis of Impulse Grounding Impedance for UHV Transmission Tower
    Si, W. R.
    Fu, C. Z.
    Wu, T. Y.
    Wang, S. J.
    Yuan, P.
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [27] TRANSMISSION-LINE TOWER GROUNDING PERFORMANCE IN NONUNIFORM SOIL
    DAWALIBI, F
    FINNEY, WG
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (02): : 471 - 479
  • [28] A New Impulse Grounding Impedance Detection Device for Transmission Tower
    Wang Yue-Qiang
    Zhang Hui-Hua
    Guo Xiang
    Xu Zhi-Bing
    Yuan Peng
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 590 - 593
  • [29] Research on Evaluation Method and Application of Grounding State of Transmission Tower
    Guo, Lei
    Yan, Zhe
    Peng, Honggang
    2023 2ND ASIAN CONFERENCE ON FRONTIERS OF POWER AND ENERGY, ACFPE, 2023, : 531 - 535
  • [30] Simplified aseismic calculation method for a coupled system of high-voltage transmission tower-line
    State Key Laboratory of Coastal and Offshore Engineering, Dalian University of Technology, Dalian 116023, China
    J Vib Shock, 2008, 10 (27-31):